09-18-01 (5)1.15 ICS! 13 9 AIIR CONDITiONINra- NQTE3 1.0 GENERAL NOTES 1.1 PROVIDE ( FURNISH AND INSTALL ) ALL NECESSARY MATERIALS AND LABOR FOR A COMPLETELY OPERATIONAL AIR CONDITIONING, HEATING AND VENTILATING SYSTEM AS SHOWN ON THE DRAWINGS AND HEREIN SPECIFIED INSTALL IN ACCORDANCE WITH THE SOUTH FLORIDA BUILDING CODE, ASHR45, SMACNA, NFPA, AND LOCAL ORDINANCES. 12 SCOPE OF WORK PROVIDE THE FOLLOWING COMPLETE SYSTEMS A. SUPPLY AND RETURN DUCT SYSTEM. B. EXHAUST SYSTEM FOR BATHROOMS AND KITCHEN. C. AiR CONDITIONING UNiTS WiTH REFRIGERANT PIPING AND CONTROLS. 13 PAY FOR ALL FEES, INSPECTIONS AND CONNECTION CHARGES REQUIRED 1.A VERIFY AT JOB SITE ALL SPACE CONDITIONS, DIMENSIONS AND EQUIPMENT SIZES PRIOR TO DUCT FABRICATION OR INSTALLATION. COORDINATE REQUIREMENTS TO AVOID INTrzRPERENCE WITH OTHER 'TRADES. 1.5 SUBMIT SHOP DRAWINGS FOR ARCHITECT / ENGINEER A OWNER APPROVAL BEFORE PROCEEDING WITH THE PURCHASE OP INSTALLATION OF EQUIPMENT AND MATERIALS. 1.6 GUARANTEE ALL WORK FREE OF DEFECTS IN MATERIALS AND WORKMANSHIP FOR A PERIOD OP ONE YEAR FROM DATE OF ACCEPTANCE. 2.0 i'''iATEISIALS 2.1 DUCTWORK 2.1.1 GENERAL. ALL DUCT SIZES SHOWN ARE CLEAR INSIDE DIMENSIONS. 212 MATERIAL. 5 POUNDS DENSITY THICK GL.A55FIBER DESIGNED, CONSTRUCTED AND INSTALLED IN ACCORDANCE WITH SMANCNA'S LOW PRESSURE DUCT MANUAL. ALL DUCT JOINTS SHALL BE SEALED AND TAPED. 22 REFRIGERANT PIPING. SEAMLESS COPPER TYPE 'L' AND HARD OR SOFT DRAWN ON ACR COPPER TUBING WITH WROUGHT COPPER SOLDER JOINT FITTINGS, SOLDER SHALL BE 95/5 APPLIED WITH SUITABLE FLUX. 23 INSULATE ALL REFRIGERANT SUCTION PIPING WiTH 3/4' CLOSED CELL POLYETHYLENE PREMOLDED PIPE INSULATION, WiTH AN APPROVED PIPE AND SMOKE JACKET. PAINT ALL EXPOSED INSULATION WITH TWO COATS OF WHITE LATEX PAINT. 2A PROVIDE AIR CONDITIONING UNITS WITH MATCHING LOW VOLTAGE HEAT -COOL THERMOSTATS WITH ON -OFF AUTO SUS -BASE SWITCH, FURNISHED BY THE EQUIPMENT MANUFACTURER. 2.5 ALL AIR CONDITIONING COMPRESSORS SHALL BE WARRANTED FOR A MINIMUM OF FiVE YEARS AFTER DATE OP ACCEPTANCE OF THE PROJECT. 2.6 AIR DISTRIBUTION PRODUCTS 2:1.1 PROVIDE SUPPLY AND RETURN GRILLES AND DIPFUSERS AS INDICATED ON THE DRAWINGS. 2.12 PROVIDE EXTRUDED ALL ALUMINIUM AIR DISTRIBUTION PRODUCTS. 2.13 PROVIDE FINISHES AND TYPES OF MOUNT IN COORDINATION WITH THE CEILING: TYPES AS SHOWN ON ARCHITECTURAL DRAWINGS, 2.1.4 PROVIDE OPPOSED BLADE, KEY OPERATED DAMPERS BEHIND ALL AIR SUPPLY OUTLETS. 3.m INSTALLATION 3.1 INSTALL ALL EQUIPMENT IN ACCORDANCE TO THE MANUFACTURER'S MANUAL AND RECOfw MENDATiONS PAYING SPECIAL ATTENTION To REQUIRED CLEARANCES FOR INSTALLATION, OPERATION AND SERVICE. PROVIDE EQUIPMENT MAINTENANCE AND MANUALS, 3.2 BALANCE ALL SYSTEMS TO PROVIDE AIR QUANTITIES AND CAPACITIES. INDICATED ON DRAWINGS, SUBMIT FiNAL TEST AND BALANCE REPORT TO ARCHITECT / ENGINEER FOR ACCEPTANCE. SCi -IEDU MANUFACTURER : AIR GUIDED MODEL CB BLOW AS SHOWN IN SUPPLY DIFi -USER EAN SCI- IEDULE EF -A : BROAN MODEL 610 50 CFM VS 1/8' ESP 0,80 AMPS, 120 -1 -60 VACLT. SW. OPERATED WITH BACKDRAFT DAMPER FURNISH LOW VOLTAGE ROOM THERMOSTAT WITH I -STEP COOL, I -STEP HEAT, I -PAN AUTO SWITCH. MECHANICAL L rAEND DUCTWORK NEW a/c 2 DUCTUJORK TO REMAIN area eervead DUCTWORK TO BE REMOVED `_____-- - --- -j DIFFUSER Lnj RETURN AIR GRILLE z VOIwUME DAMPER ___j VD SPL ITTER DAMPER gp D SMOKE DETECTOR Fs D THERMOSTAT 0 TURNINS VANE TV EXHAUST FAN x I REPRIG, LINES TO G.U. OUTDOORS CONDENSATE DRAT INSIDE PARTITION TO OUTDOORS P -TRAP ON GREEN AREA. 5FL i`1" 5Y8TEM SCHEDULE unit designation a/c I a/c 2 a/c 3 area eervead - -- - -- ___ manufacturer rhaem FUJITSU FUJITSU Pan Coll unit model no. rCba2451a - -- - -- condaneing unit model no, ramb- 024jax - -- - -- seer 111 10.0 10.0 total capacity btuh 22/000 2-3A00 29,500 sensible capacity btuh 16,600 21,400 21,400 evaporator coil rcga rcga rcga call entering condition 80/61 deg. 80/61 deg. 60/61 deg. ambient temperature 95 deg w deg 95 deg cfm euppiy 800 1000 1000 external static pressure 030 030 030 F.c.u. fan hp. 1/4 I/A 1/4 hp heater kw 5 kw 5 kw 5 kw conden6ing unit Fla 19.2 M2 192 Voltage 240/1/60 240/1/60 240/1/60 reflg. line suction 3/4' reFrig. line Iiq. 5/16' 9/16" 2 TONS ACCESSORY MOUNTING BRACKETS WiTH 3/8' SCREWS ATTACHED TO PARTITION STUDS -TOTAL OF 4 ACCESSORY GRILLE ARTITION WAL-L —HUNG FGU, MOUNTING C)r=TAL C 2.5 TONS 2.5 TONS HvAG DESIGN REQUIREMENTS JYirSI No DUCT SMOKE DETECTOR � X FIRE DAMPERS Z X SMOKE DAMPERS cm X FIRE RATED ENCLOSURE � X FiRE RATED ROOF/FLOOR /CLG. � X PIPE STOPPING 0 X SMOKE CONTROL X PROVIDE 4'0 METAL EXHAUST DUCT FROM THE TOILET FAN TO THE OUTSIDE OF THE ROOF - EXTEND DUCT (o' ABOVE ROOF. m m MECHANICAL FLOOR PLAN GRAPHIC SCALE 0 5' qG iT ' LINE5 CN TH AWAMEX >ENCLOSE CHASE. :EYES IN .L I o� 1 � ao � r Z Z W � ao � r Z Z c cm � � V � ` 0 r' H X W in ~ W � W �- W U. LL. v W p � to tD W U v O p o W Z � Q a b7 co � Z Co J z 0 N } w ot W A 3 X ~ z 0 N } w ot M �1 c' 0 0 M'I � )b No. F-* 01-030 W ~ � W �- U. W J p � U o Z � a � Co d M �1 c' 0 0 M'I � )b No. F-* 01-030