AIIR CONDITiONINra- NQTE3
1.0 GENERAL NOTES
1.1 PROVIDE ( FURNISH AND INSTALL ) ALL NECESSARY
MATERIALS AND LABOR FOR A COMPLETELY OPERATIONAL
AIR CONDITIONING, HEATING AND VENTILATING SYSTEM AS
SHOWN ON THE DRAWINGS AND HEREIN SPECIFIED
INSTALL IN ACCORDANCE WITH THE SOUTH FLORIDA
BUILDING CODE, ASHR45, SMACNA, NFPA, AND LOCAL
ORDINANCES.
12 SCOPE OF WORK
PROVIDE THE FOLLOWING COMPLETE SYSTEMS
A. SUPPLY AND RETURN DUCT SYSTEM.
B. EXHAUST SYSTEM FOR BATHROOMS AND KITCHEN.
C. AiR CONDITIONING UNiTS WiTH REFRIGERANT PIPING
AND CONTROLS.
13 PAY FOR ALL FEES, INSPECTIONS AND CONNECTION
CHARGES REQUIRED
1.A VERIFY AT JOB SITE ALL SPACE CONDITIONS, DIMENSIONS
AND EQUIPMENT SIZES PRIOR TO DUCT FABRICATION OR
INSTALLATION. COORDINATE REQUIREMENTS TO AVOID
INTrzRPERENCE WITH OTHER 'TRADES.
1.5 SUBMIT SHOP DRAWINGS FOR ARCHITECT / ENGINEER A
OWNER APPROVAL BEFORE PROCEEDING WITH THE
PURCHASE OP INSTALLATION OF EQUIPMENT AND MATERIALS.
1.6 GUARANTEE ALL WORK FREE OF DEFECTS IN MATERIALS
AND WORKMANSHIP FOR A PERIOD OP ONE YEAR FROM
DATE OF ACCEPTANCE.
2.0 i'''iATEISIALS
2.1 DUCTWORK
2.1.1 GENERAL. ALL DUCT SIZES SHOWN ARE CLEAR INSIDE
DIMENSIONS.
212 MATERIAL. 5 POUNDS DENSITY THICK GL.A55FIBER
DESIGNED, CONSTRUCTED AND INSTALLED IN ACCORDANCE
WITH SMANCNA'S LOW PRESSURE DUCT MANUAL. ALL
DUCT JOINTS SHALL BE SEALED AND TAPED.
22 REFRIGERANT PIPING. SEAMLESS COPPER TYPE 'L' AND
HARD OR SOFT DRAWN ON ACR COPPER TUBING WITH
WROUGHT COPPER SOLDER JOINT FITTINGS, SOLDER
SHALL BE 95/5 APPLIED WITH SUITABLE FLUX.
23 INSULATE ALL REFRIGERANT SUCTION PIPING WiTH 3/4'
CLOSED CELL POLYETHYLENE PREMOLDED PIPE
INSULATION, WiTH AN APPROVED PIPE AND SMOKE
JACKET. PAINT ALL EXPOSED INSULATION WITH TWO
COATS OF WHITE LATEX PAINT.
2A PROVIDE AIR CONDITIONING UNITS WITH MATCHING LOW
VOLTAGE HEAT -COOL THERMOSTATS WITH ON -OFF AUTO
SUS -BASE SWITCH, FURNISHED BY THE EQUIPMENT
MANUFACTURER.
2.5 ALL AIR CONDITIONING COMPRESSORS SHALL BE
WARRANTED FOR A MINIMUM OF FiVE YEARS AFTER DATE
OP ACCEPTANCE OF THE PROJECT.
2.6 AIR DISTRIBUTION PRODUCTS
2:1.1 PROVIDE SUPPLY AND RETURN GRILLES AND DIPFUSERS
AS INDICATED ON THE DRAWINGS.
2.12 PROVIDE EXTRUDED ALL ALUMINIUM AIR DISTRIBUTION
PRODUCTS.
2.13 PROVIDE FINISHES AND TYPES OF MOUNT IN COORDINATION
WITH THE CEILING: TYPES AS SHOWN ON ARCHITECTURAL
DRAWINGS,
2.1.4 PROVIDE OPPOSED BLADE, KEY OPERATED DAMPERS
BEHIND ALL AIR SUPPLY OUTLETS.
3.m INSTALLATION
3.1 INSTALL ALL EQUIPMENT IN ACCORDANCE TO THE
MANUFACTURER'S MANUAL AND RECOfw MENDATiONS
PAYING SPECIAL ATTENTION To REQUIRED CLEARANCES
FOR INSTALLATION, OPERATION AND SERVICE. PROVIDE
EQUIPMENT MAINTENANCE AND MANUALS,
3.2 BALANCE ALL SYSTEMS TO PROVIDE AIR QUANTITIES AND
CAPACITIES. INDICATED ON DRAWINGS, SUBMIT FiNAL TEST
AND BALANCE REPORT TO ARCHITECT / ENGINEER FOR
ACCEPTANCE.
SCi -IEDU
MANUFACTURER : AIR GUIDED MODEL CB
BLOW AS SHOWN IN SUPPLY DIFi -USER
EAN SCI- IEDULE
EF -A : BROAN MODEL 610 50 CFM VS 1/8' ESP
0,80 AMPS, 120 -1 -60 VACLT. SW. OPERATED WITH
BACKDRAFT DAMPER
FURNISH LOW VOLTAGE ROOM THERMOSTAT WITH
I -STEP COOL, I -STEP HEAT, I -PAN AUTO SWITCH.
MECHANICAL L
rAEND
DUCTWORK NEW
a/c 2
DUCTUJORK TO REMAIN
area eervead
DUCTWORK TO BE REMOVED
`_____-- - --- -j
DIFFUSER
Lnj
RETURN AIR GRILLE
z
VOIwUME DAMPER
___j VD
SPL ITTER DAMPER
gp D
SMOKE DETECTOR
Fs D
THERMOSTAT
0
TURNINS VANE
TV
EXHAUST FAN
x I
REPRIG, LINES
TO G.U. OUTDOORS
CONDENSATE DRAT
INSIDE PARTITION
TO OUTDOORS
P -TRAP ON GREEN
AREA.
5FL i`1" 5Y8TEM SCHEDULE
unit designation
a/c I
a/c 2
a/c 3
area eervead
- --
- --
___
manufacturer
rhaem
FUJITSU
FUJITSU
Pan Coll unit model no.
rCba2451a
- --
- --
condaneing unit model no,
ramb- 024jax
- --
- --
seer
111
10.0
10.0
total capacity btuh
22/000
2-3A00
29,500
sensible capacity btuh
16,600
21,400
21,400
evaporator coil
rcga
rcga
rcga
call entering condition
80/61 deg.
80/61 deg.
60/61 deg.
ambient temperature
95 deg
w deg
95 deg
cfm euppiy
800
1000
1000
external static pressure
030
030
030
F.c.u. fan hp.
1/4
I/A
1/4 hp
heater kw
5 kw
5 kw
5 kw
conden6ing unit Fla
19.2
M2
192
Voltage
240/1/60
240/1/60
240/1/60
reflg. line suction
3/4'
reFrig. line Iiq.
5/16'
9/16"
2 TONS
ACCESSORY MOUNTING BRACKETS
WiTH 3/8' SCREWS ATTACHED TO
PARTITION STUDS -TOTAL OF 4
ACCESSORY GRILLE
ARTITION
WAL-L —HUNG FGU,
MOUNTING C)r=TAL
C
2.5 TONS 2.5 TONS
HvAG DESIGN REQUIREMENTS JYirSI No
DUCT SMOKE DETECTOR
�
X
FIRE DAMPERS
Z
X
SMOKE DAMPERS
cm
X
FIRE RATED ENCLOSURE
�
X
FiRE RATED ROOF/FLOOR /CLG.
�
X
PIPE STOPPING
0
X
SMOKE CONTROL
X
PROVIDE 4'0 METAL EXHAUST DUCT FROM THE TOILET FAN
TO THE OUTSIDE OF THE ROOF - EXTEND DUCT (o' ABOVE ROOF.
m m
MECHANICAL FLOOR PLAN
GRAPHIC SCALE
0 5'
qG
iT
' LINE5
CN
TH AWAMEX
>ENCLOSE
CHASE.
:EYES IN
.L
I
o�
1
�
ao
�
r
Z
Z
W
�
ao
�
r
Z
Z
c
cm
�
�
V
�
`
0
r'
H
X
W
in
~
W
�
W
�-
W
U.
LL.
v
W
p
�
to
tD
W
U
v
O
p
o
W
Z
�
Q
a
b7
co
�
Z
Co
J
z
0
N
}
w
ot
W
A
3
X
~
z
0
N
}
w
ot
M �1 c'
0
0
M'I �
)b No. F-*
01-030
W
~
�
W
�-
U.
W
J
p
�
U
o
Z
�
a
�
Co
d
M �1 c'
0
0
M'I �
)b No. F-*
01-030