01-0679-037 ELECTRICAL GENERAL NOTES 1, DRAWINGS ARE DIAGRAMMATIC. D❑ NOT SCALE DRAWINGS FOR EXACT LOCATION OF EQUIPMENT. THESE DRAWINGS ARE NOT INTENDED TO 17, ALL OUTSIDE EQUIPMENT, OUTLETS, LIGHTING FIXTURES, SHOW EVERY MINOR DETAIL. HOWEVER, THE CONTRACTOR SHALL ENCLOSURES, ETC. SHALL BE WEATHERPROOF, FURNISH AND INSTALL ALL ITEMS REQUIRED FOR A COMPLETE AND ACCEPTABLE WORKING INSTALLATION PER CODE. 18. THE CONTRACTOR SHALL PROVIDE ALL REQUIRED CONNECTIONS FOR ALL OTHER TRADES. 2. ALL WORK SHALL BE DONE IN ACCORDANCE WITH THE LATEST EDITION OF THE NEC AND SHALL COMPLY WITH ALL LOCAL RULES AND 19, THE CONTRACTOR SHALL OBTAIN ALL PERMITS FOR WORK UNDER THIS ORDINANCES. CONTRACT. 20. THE NUMBER, EXACT LOCATION AND MOUNTING HEIGHTS OF ALL BLITSTEIN 3. ALL MATERIAL SHALL BE NEW AND SHALL BEAR UL LABEL WHERE OUTLETS, LIGHTS AND ELECTRICAL FIXTURES SHALL BE DETERMINED APPLICABLE. THE CONTRACTOR SHALL FURNISH ALL LABOR, BY THE OWNER AND ARCHITECT. THE CONTRACTOR SHALL VERIFY ALL MATERIALS AND EQUIPMENT RIN A COMPLETE INSTALLATION, ALL NUMBERS AND LOCATIONS WITH ARCHITECT AND OWNER PRIOR TO BID DESIGN MOUNTING HARDWARE AND WIRING HARDWARE SHALL BE FURNISHED BY AND TO INSTALLATION. THE CONTRACTOR, 4. CIRCUITS SHOWN ON THESE PLANS ARE SYMBOLICALLY SHOWN TO 21. THE CONTRACTOR SHALL PROVIDE ROUTING FOR ALL FLOOR MOUNTED PANEL TYPE: PANEL BOARD-MLO AIC: 22000 AMPS PANEL TYPE: PANEL BOARD-MLO 2 SECTION AIC: 22000 AMPS ASSOCIATES DETERMINE LOAD DATA AND EQUIPMENT SIZES. THE CONTRACTOR OUTLETS AND OTHER LOADS AND CONNECTIONS NOT READILY VOLTAGE: 3 PH 1201240 PANEL: MAINS: 400 AMPS VOLTAGE: 1 PH,120/240 PANEL: MAINS: 250 AMPS SHALL PHYSICALLY PR❑VIDE CIRCUITS AND ROUTING OF CONDUITS TO ACCESSIBLE VIA WALL OR CEILING. THE CONTRACTOR SHALL SUIT JOB CONDITIONS. THE LOADS SHALL BE BALANCED COORDINATE WITH ARCHITECT AND OWNER TO DETERMINE THE METHOD OC PROTECT: 400 AMPS A LOCATION: BACK OF TENANT SPACE OC PROTECT: 250 AMPS © LOCATION: BACK OF TENANT SPACE . THROUGHOUT. THE CONTRACTOR SHALL ENSURE THAT NEUTRAL WIRES TO OLSERVE S)CH AREAS (I. E. TRENCHING, CORE AND BORING, POWER MOUNTING: FLUSH FED FROM: TENANT MAIN MOUNTING:SURFACE FED FROM: PANEL"A" Architecture AND EQUIPMENT GROUND WIRES ARE INSTALLED WHERE EVER Interior Design APPLICABLE. 22 SLABRSHALLYBEp�SPACEDEA MINIMUMIOFDTHREEODIAMETERSDOFRTHE WIRE CON LOAD BRK BK BK BRK LOAD CON WIRE WIRE CON LOAD BRK BK BK BRK LOAD CON WIRE 5. THE CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING WITH THE POWER UTILITY TO OBTAIN TEMPORARY POWER DURING LARGEST CONDUIT OR PIPE OF ANY OTHER SERVICE. ITEM SIZE SIZE A SIZE NO A B C NO SIZE VA SIZE SIZE ITEM ITEM SIZE SIZE VA SIZE NO A B NO SIZE A SIZE SIZE ITEM 285 Sevilla Avenue CONSTRUCTION. THE CONTRACTOR SHALL IMMEDIATELY CONTACT THE 23. ALL RACEWAYS UNDERGROUND AND/OR LARGER THAN 2 INCHES IN PANEL"B" 250 2-112" 52,599 250 1 A 2 90 RECEPTACLES GFI #12 1/2" 750 20 1 A 2 20 1,250 1/2" #12 LIGHTS Coral Gables, Fl 33134 POWER UTILITY TO SCHEDULE INSTALLATION OF TEMPORARY POWER S❑ THAT CONSTRUCTION DELAYS ARE AVOIDED. DIAMETER SHALL BE GALVANIZED RIGID STEEL, PVC SCH 40 WILL MCM 250 3 B 4 90 27,000 1-114" #3 WATER HEATER PEDICURE #12 112" 1000 20 3 B 4 20 1250 112' #12 LIGHTS BE ACCEPTABLE IF APPROVED BY LOCAL REGULATIONS CONTRACTOR (305) 444-4433 6. THE CONTRACTOR SHALL COORDINATE WITH THE POWER UTILITY TO TO VERIFY. ALL OTHER RACEWAYS 2' AND SMALLER IN DIAMETER 40 5 CI 6 190 RECEPTACLES GFI #12 1/2" 720 20 5 A 6 20 1500 1/2" #12 LIGHTS OBTAIN PERMANENT POWER IN ACCORDANCE WITH THESE DRAWINGS. MAY BE EMT. THE CONTRACTOR SHALL IMMEDIATELY CONTACT THE POWER UTILITY SHALL 1 #8 314" 10,500 40 7 A 8 35 6,000 3/4" #8 SAUNA RECEPTACLES #12 112" 720 20 7 B 8 20 1,650 112" #12 LIGHTS 24. OUTLET BOXES ,)HALL BE PRESSED STEEL IN DRY LOCATIONS AND 40 9 T❑ SCHEDULE THE INSTALLATION OF PERMANENT POWER SO THAT B 10 35 RECEPTACLES #12 1/2" 720 20 9 A 10 20 800 112" #12 LIGHTS CAST ALLOY WITH THREADED HUBS IN WET OR DAMP LOCATIONS, DELAYS ARE AVOIDED, IT IS THE CONTRACTOR' S RESPONSIBILITY 70 11 C 12 30 5,000 314" #10 DRYER RECEPTACLES #12 1/2" 720 20 Ill B 12 20 1,425 1/2" #12 LIGHTS TO CONTACT THE POWER UTILITY EARLY ON TO IDENTIFY ANY ISSUES 25. DISCONNECT SWITCHES SHALL BE HORSEPOWER RATED, HEAVY DUTY, AFFECTING PERMANENT POWER SERVICE AND TO WORK TOWARDS QUICK MAKE, QUICK BREAK, IN NEMA 1 OR NEMA 3R ENCLOSURES AS RTU 2 #4 1-1/4" 19,968 70 13 Al 14 30 RECEPTACLES #12 1/2" 720 20 13 A 14 20 1,200 1/2" #12 LIGHTS 1 RESOLVING ANY ISSUES REGARDING PERMANENT SERVICE. REQUIRED BY EXPOSURE. 70 15 131 116 20 696 3/4" #12 EXHAUST FAN RECEPTACLES #12 112" 720 20 15 B 16 20 825 11211 #12 LIGHTS 1 7. THE CONTRACTOR SHALL COORDINATE WITH THE TELEPHONE COMPANY 26. THE ELECTRICAL. SYSTEM SHALL BE COMPLETELY AND EFFECTIVELY 17 IC118 RECEPTACLES #12 1/2" 360 20 17 A 18 20 800 1/2" #12 LIGHTS TO OBTAIN TELEPHONE SERVICE. THE CONTRACTOR SHALL GROUNDED PER NEC REQUIREMENTS AND STATE AND LOCAL CODE IMMEDIATELY CONTACT THE TELEPHONE COMPANY TO SCHEDULE REQUIREMENTS. RECEPTACLES #12 112" 1,500 20 19 A 20 20 1200 1/2" #12 SIGN 1 RECEPTACLES #12 1/2" 720 20 119 B 20 20 1200 112" #12 LIGHTS INSTALLATION OF TELEPHONE SERVICE. IT IS THE CONTRACTOR' S RECEPTACLES #12 1/2" 1500 20 21 B 22 RECEPTACLES #12 1/2" 720 20 21 A 22 20 RESPONSIBILITY TO CONTACT THE TELEPHONE COMPANY EARLY ON TO 27. ALL WORK SHALL. BE PERFORMED BY A LICENSED ELECTRICAL 1,350 1/2" #12 LIGHTS IDENTIFY ANY ISSUES AFFECTING TELEPHONE SERVICE AND TO WORK CONTRACTOR IN A FIRST CLASS WORKMANLIKE MANNER. THE 23 C 24 RECEPTACLES #12 1/2" 720 20 23 B 24 20 1350 112° #12 LIGHTS TOWARDS RESOLVING ANY ISSUES DELAYING INSTALLATION, COMPLETE SYSTEM SHALL BE FULLY OPERATIVE. ACCEPTANCE BY ENGINEER/ARCHITECT MUST BE A CONDITION OF THE CONTRACT. SINGLE PHASE AMPS= 219 RECEPTACLES #12 112" 720 20 25 A 26 20 975 112" #12 LIGHTS S. IF APPLICABLE, THE CONTRACTOR SHALL COORDINATE WITH THE 28, IT IS NOT THE INTENTION ❑F THESE DRAWINGS TO ESTABLISH TOTAL CONNECTED LOAD: THREE PHASE AMPS- RECEPTACLES #12 112" 720 20 27 B 28 20 1,100 1/2" #12 LIGHTS CABLE TV COMPANY IN THE SAME MANNER AS DESCRIBED IN PARAGRAPHS 6 AND 7 FOR POWER AND TELEPHONE UTILITIES, LIGHTING LEVELS OF ANY KIND. THE NUMBER, STYLE AND LOCATION 125,963 VA 73,364 / 416 PEDICURI #12 10 1,000 20 29 1A 30 20 1 1,540 1/2" #12 LIGHTS OF LIGHTING FIXTURES ARE DETERMINED BY THE ARCHITECT AND/DR 9. IF ANY OR ALL OF THE UTILITIES (ELECTRICAL, TELEPHONE, CATV) THE OWNER. THE LIGHTING FIXTURE SCHEDULE IF APPEARING ON THREE PHASE AMPS= 176 RECEPTACLES #12 112" 540 20 31 B 32 20 975 112" #12 LIGHTS ARE EXISTING, IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO THESE DRAWINGS IS FOR INFORMATIONAL PURPOSES AND HAS BEEN DEMAND AMPS,APH=BPH= 396 RECEPTACLES #12 112" 500 20 33 A 34 20 775 1/2" #12 LIGHTS BECOME FAMILIAR WITH THE EXISTING SYSTEMS PRIOR TO BID. THE DEVELOPED BY THE ARCHITECT AND/OR OWNER. FOR DETAILED CONTRACTOR SHALL TRACE DOWN ALL CIRCUITS AND WIRING AND QUESTIONS REGARDING LIGHTING FIXTURES CONTACT THE ARCHITECT (1)TIE TO TIME CLOCK. HI LEG AMPS =C PH= 176 RECEPTACLES #12 1/2" 500 20 35 B 36 20 500 1/2" #12 FOUNTAIN SHALL VERIFY THAT CAPACITY IS AVAILABLE FOR THE SCOPE OF THE OR OWNER. RECEPTACLES #12 1/2" 500 20 37 A 38 20 360 1/2" #12 RECEPTACLES GFI PROJECT, THE CONTRACTOR SHALL FIELD INSPECT ALL EXISTING EQUIPMENT AND SHALL ENSURE THAT ALL RATINGS, FUSES, 29, EXISTING LIGHTING FIXTURES WHEN REUSED ARE TO BE RECIRCUITED I PEDICURE #12 1/2" 1,000 20 39 B 40 20 500 1/2" #12 EXHAUST FAN AND RECONNECTED, THE ARCHITECT AND/OR OWNER SHALL BE ENCLOSURES, ETC, ARE PROPER FOR THE SCOPE OF THE PROJECT, INFORMED OF AI4D SHALL APPROVE THE REUSE OF ALL REUSED LIGHT PEDICURE #12 1/2" 1,000 20 41 A 42 20 500 1/2" #12 RECEPTACLES GFI THE CONTRACTOR SHALL INSPECT ANY EQUIPMENT, WIRING ETC, THAT IS REUSED AND SHALL GUARANTEE THE PERFORMANCE OF SUCH FIXTURES. ALL REUSED LIGHTING FIXTURES SHALL BE RELAMPED, PEDICURE #12 112" 1,000 20 43 B 44 20 1,000 1/2" #12 PEDICURE CLEANED AND REPAIRED IF NECESSARY. ANY EXISTING LIGHTING PEDICURE #12 112" 1,000 20 45 A 46 20 1,000 112° #12 PEDICURE EQUIPMENT FOR ONE YEAR. THE CONTRACTOR SHALL REPLACE ANY FIXTURE BEYOND REPAIR SHALL BE REPLACED. ALL LIGHTING EQUIPMENT THAT IS DAMAGED OR IN POOR CONDITION. A LIST OF FIXTURES SHAD_ BE GUARANTEED FOR A PERIOD OF ONE YEAR. EQUIPMENT IDENTIFIED FOR REPLACEMENT SHALL BE PROVIDED TO RECEPTACLES #12 1/2" 540 20 47 113 48 500 SPARE THE OWNER (OR THE OWNER'S REPRESENTATIVE) AND THE ENGINEER PRIOR TO REPLACEMENT. 30. IT IS THE CONTRACTOR'S RESPONSIBILITY TO ENSURE THAT ALL RECEPTACLES #12 112" 500 20 49 Al 50 1 500 SPARE ELECTRICAL SERVICES TO MECHANICAL EQUIPMENT IS ACCOUNTED FOR RECEPTACLES #12 112" 500 20 51 B 52 500 SPARE 10, THE CONTRACTOR SHALL THOROUGHLY REVIEW THESE DRAWINGS AND PRIOR TO BID. IN ADDITION, ALL MECHANICAL EQUIPMENT SHALL VISIT AND BECOME FAMILIAR WITH THE JOB SITE AND ALL SUBSTITUTIONS ARE TO BE ACCOUNTED FOR PRIOR TO BID AND SHALL RECEPTACLES #12 1/2" 500 20 53 A 54 500 SPARE EXISTING CONDITIONS PRIOR TO BID. ANY QUESTIONS, COMMENTS, BE COORDINATED ELECTRICALLY. WASH MACHINE #12 1/2" 1200 20 55 B 56 473 SPARE DISCREPANCIES OR PERCEIVED AMBIGUITIES SHALL BE DISCUSSED WITH THE ENGINEER PRIOR TO BID. 31. FOR HVAC EQUIPMENT THE MECHANICAL CONTRACTOR SHALL PROVIDE RECIRC.PUMP #12 1/2" 500 20 57 A 58 SPACE THE SMOKE DETECTOR, IF REQUIRED, AND THE ELECTRICAL ROOF RECEPT #12 112" 500 20 59 B 60 SPACE il, ELECTRICAL DESIGN IS BASED UPON THE BEST AVAILABLE CONTRACTOR SHALL INSTALL THE SMOKE DETECTOR. LIGHTING LOAD(VA}=19,965 INFORMATION. THE CONTRACTOR SHALL REVIEW NAMEPLATE DATA AND MANUFACTURER SUPPLIED LITERATURE FOR ALL PIECES OF EQUIPMENT 32. THE ELECTRICAL CONTRACTOR SHALL COORDINATE WITH THE PRIOR TO ROUGH ELECTRICAL WIRING. THE CONTRACTOR SHALL MECHANICAL CONTRACTOR FOR INSTALLATION OF ALL MECHANICAL TOTAL CONNECTED LOAD: 125%LIGHTING LOAD(VA) 241956 CHECK ALL EQUIPMENT FOR PROPER VOLTAGE, PHASE AND AMP RATING CONTROLS. ,608 VA 47 100%REMAINING LOAD(VA) 27,643 PRIOR TO INSTALLATION, THE CONTRACTOR SHALL CONTACT DEMAND LOAD(VA)= 52,599 ENGINEER PRIOR TOO ANY FIELD ADJUSTMENTS. 33. NONMETALLIC SHEATHED CABLE ('roMex') MAY BE USED WHERE project name ALLOWED BY NEC REQUIREMENTS AND WHERE APPROVED BY OWNER, 12. ALL CONDUCTORS SHALL BE COPPER WITH THWN INSULATION, ARCHITECT AND LOCAL JURISDICTION. 34. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO FORWARD ANY (1)TIE TO TIME CLOCK. I3. ALL PANELS SHALL BE CLEARLY LABELED ON THE OUTSIDE FOR QUICK SHOP DRAWINGS TO THE ARCHITECT/OWNER. SHOP DRAWINGS ARE NOT PROVIDE TWO(2)30 POSITION PANELS AMPS= 52,599 / 240 AND EASY IDENTIFICATION. ALL CIRCUITS IN ALL PANELS SHALL SOLICITED BY THE ENGINEER. WITH SUBFEED LUGS. AMPS- 219 BE CLEARLY IDENTIFIED AND SHALL APPEAR WITH COMPLETE INFORMATION (DESCRIPTION OF CIRCUIT, BREAKER SIZE, NUMBER OF POLES AND BREAKER POSITION NUMBERS) ON THE PANEL 35. IT IS THE CONTRACTOR'S RESPONSIBILITY TO ENSURE THAT DIRECTORIES. IN ADDITION, THE VOLTAGE, PHASE AND AMP RATING FIRE STOPPING MEASURES ARE PROVIDED PER LOCAL BUILDING DEPT. OF THE PANEL SHALL CLEARLY BE IDENTIFIED ON THE INSIDE DOOR. REQUIREMENTS. THE FIRE STOPPING MATERIAL AND ITS bellgzza THE ABOVE APPLIES FOR ANY AND ALL EXISTING TO REMAIN PANEL INSTALLATION SHALL BE UL APPROVED. ALL FIRE STOPPING BOARDS AND CIRCUITS, MATERIAL SHALL BE NON WATER SOLUBLE. 14. PLANS SHOWING AS-BUILT CHAN ES SHALL BE DELIVERED TO 36. ALL CASH REGISTER AND COMPUTER RECEPTACLES ARE T❑ BE PROVIDED , Spa • Salon - Boutique THE OWNENERS REPRESENTATIVE UPON COMPLETION OF WORK, WITH DEDICATED CIRCUITS AND SEPARATE, ISOLATED GROUNDS. 15. IT IS THE RESPONSIBILITY OF THE CONTRACTOR TO MAKE THIS CONTRACTOR SHALL COORDINATE WITH ARCHITECT AND OWNER EXISTING NEW INSTALLATION IN COMPLIANCE WITH ALL FIRE PREVENTION CODES PRIOR TO BID TO IDENTIFY ALL RECEPTACLES REQUIRING ELECTRICAL ROOM TENANT SPACE 7245 SW 57 CT SUPERCEDING ALL DRAWINGS, SPECIFICATIONS AND NOTES. THE ISOLATED GROUND CONNECTIONS. CONTRACTOR SHALL COMMUNICATE AND COORDINATE WITH THE FIRE MId1� FL MARSHALL AND SHALL PROVIDE ALL NECESSARY INFORMATION NEEDED Miami, TO SATISFY THAT LIFE SAFETY SYSTEMS ARE TO LOCAL CODE ACCEPTANCE. 16. ALL SERVICE ENTRANCE EQUIPMENT IS TO BE RATED AT 100,000 AIC ELECTRICAL �E G E N D UNLESS OTHERWISE NOTED, TO PROVIDE SERVICE ENTRANCE EQUIPMENT WITH LOWER RATINGS THE CONTRACTOR SHALL PROVIDE IN WRITING INFORMATION FROM THE POWER UTILITY VERIFYING THAT SYMBOL project number CALCULATED FAULT CURRENTS ARE AT AN ACCEPTABLE LEVEL TO DESCRIPTION SYMBOL DESCRIPTION ACCOMMODATE THE LOWER RATED EQUIPMENT. IF SERVICE ENTRANCE EQUIPMENT IS EXISTING, THE CONTRACTOR SHALL VERIFY THAT AIC 1' X 4' FLUORESCENT FIXTURE 0104-032 RATINGS OF EXISTING EQUIPMENT ARE PROPER. THE CONTRACTOR �0 WALL MTD LIGHT FIXTURE ® SURFACE OR PENDANT MTD SHALL COORDINATE WITH THE POWER UTILITY AND THE ENGINEER X 8' FLUORESCENT FIXTURE EXISTING 3 PHASE NEW 4 — 600MCM THWN 120 240 VOLT d a t e 1' PRIOR TO BID. SURFACE MOUNTED LIGHT FIXTURE (�--� SURFACE OR PENDANT MTD DEL A SERVICE CU IN A 4" CONDUIT 0 RECESSED MOUNTED LIGHT FIXTURE p® POLE MTD LIGHT FIXTURE - � NEW — 250 MCM THWN revision © 2' X 4' FLUORESCENT TROFFER 0 ELECTRICAL JUNCTION BOX CU IN A 2-1 /2" CONDUIT Q B.D.c. S/2/01 2 DUPLEX RECEPTACLE, 20A, 120V ' X 2' FLUORESCENT TROFFER � CLAN 5 S/2 ■ IG W/ISOLATED GROUND © �� 8/01 FLUORESCENT STRIP FIXTURE NEW ( PANEL PANEL i---I ELECTRICAL PLUG MOLD NOTE: NEW NEW 400 A. MAIN 3 OF 3. METER ® EXIT LIGHT W/BATTERY COMPUTER OUTLET 400A 250A SERVICE MAINS FOR THIS 400A I MLO MLO EMERGENCY LIGHT W/BATTERY TELEVISION OUTLET PROJECT DO NOT EXCEED 6. C MCB � 3 PH NEW SECTION drawn by $ TOGGLE SWITCH, SINGLE POLE, 20A H TELEPHONE OUTLET PANEL AE $ TOGGLE SWITCH, THREE WAY, 20A DISCONNECT SWITCH - "B" a �zo POLE AMP/FUSE $4 TOGGLE SWITCH, FOUR WAY, 20A M ILO 4 MOTOR, NUMBER INDICATES HP sheet t i t l e M LO $p DIMMER SWITCH RATED FOR CKT LOAD ELECTRICAL PANEL #3/0-CU IN 3/4"C. ( SECS ION 5CHEIDULEs, � SINGLE RECEPTACLE, 20A, 120V � POWER BRANCH CKT HOME RUN NEW p 2 HOT LEGS, 1 NEUTRAL I`15ER AN[) NOTES DUPLEX RECEPTACLE, 20A, 120V AFF ABOVE FINISHED FLOOR Iti '�1 `J QUADRAPLEX RECEPTACLE, 20A, 120V BFC BELOW FINISHED CEILING FOUNDATION STEEL. 3/4"C TO = (2) 5/8„X10'-0” DRIVEN GROUND RODS DUPLEX RECEPTACLE, 20A, 120V W/ WP WEATHER PROOF COPPERLAND, SEPARATED 6'-0" MIN. PREPARED BY, GFI GROUND FAULT CIRCUIT INTERRUPT SCAL I=-: A$ SHOWN 240V GROUNDED RECEPTACLE MH MOUNTING HEIGHT Engineering Inc. sheet n u m b e r HTD DUPLEX RECEPT, 120V, 20A FLOOR NOTE, ALL SYMBOLS DO NOT NECESSARILY 13780 S.W. 56th Street, Suite 215 APPEAR IN THIS LEGEND. SEE OTHER SHEETS, ;, . •...., , Miami, Forida 3317 5 UNLESS OTHERWISE NOTED WALL OUTLETS Y Bus. (305) 383-8989 SPECIAL PURPOSE RECEPTACLE ARE MOUNTED 12'AFF, SWITCHES 40'AFF E LE C T R I CA L RISER FAX (305) 383-9949 E = 3 (;• I E-MAIL: ucaeng®bellsouth net R. J. MIRANDA PE NO. 35579 G 5 ; DAVID A. BELSKY PE NO. 37234 a Professional Electrical/Mechanical -,_ Engineers