01-0610-025 Revisions: ELECTRICAL LEGEND < < < ` ` < < ELECTRICAL NOTES 0 SYM SIZE DESCRIPTION REMARKS SUPPLIED AND INSTALLED BY CUSTOMER CONTRACTOR � , � , < , < , < , , , , , , , 1) COMPLIANCE: ELECTRICAL WORK SHALL BE IN COMPLIANCE / WITH THE LATEST EDITION OF THE NATIONAL ELECTRICAL CODE B 3-PHASE 440/480 VOLTS MAIN CIRCUIT BREAKER, SHUNT TRIP, 150 AMPS., MOUNTED FLUSH I (NFPA-70), O.S.H.A. REGULATIONS, AS WELL AS APPLICABLE WITH FINISHED WALL AT 5'-0" CENTER ABOVE FINISHED FLOOR. < < REGULATIONS OF CITY, COUNTY, STATE AND FEDERAL AGENCIES. BREAKER TO BE FED FROM HOSPITAL'S SUPPLY ON THE INPUT, FEEDING UPS. PROVIDE MATERIALS AND EQUIPMENT THAT COMPLY TO ANSI, IEEE AND NEMA STANDARDS. WHERE APPLICABLE, PROVIDE ONLY --- EMERGENCY POWER OFF BUTTON TO CONTROL SHUNT TRIP DEVICE IN C81 AND UPS. MATERIALS AND PRODUCTS THAT ARE U.L. LISTED AND LABELED. L EPO TO BE RECESSED OR SHIELDED; MUST PREVENT RESETTING CB1 WHEN IN OFF CUSTOMER'S/CONTRACTOR'S WORK SHALL COMPLY WITH THE RDI AG © POSITION LATEST EDITION OF NECA STANDARD OF INSTALLATION. Q RDIAG TO 13E +1 © S.B.C. PULL BOX MOUNTED FLUSH WITH FINISHED WALL AT 5'-6" CENTER A.F.F.(FOR ALARM). 2) QUALITY ASSURANCE: THE CONTRACTOR SHALL VERIFY EXISTING CONDITIONS IN THE FIELD TO INSURE THAT THE NEW EQUIPMENT ROOM © --- TERMINATION POINT OF RACEWAYS #10, #11 AND #12 ABOVE THE MAGNET CABLE WORK WILL FIT TO THE EXISTING STRUCTURE AS SHOWN ON THE PO OPENING. TO BE FIELD LOCATED. PROVIDE OPENINGS IN THE BOTH ENDS OF EACH DRAWINGS. SHOULD ANY CONDITIONS EXIST OR BE DISCOVERED o RACEWAY. THAT PREVENT THE INSTALLATION OF WORK AS SHOWN, THE 1 TO BE FIELD CONTRACTOR SHALL NOTIFY THE OWNER'S REPRESENTATIVE PRIOR TO 00 LOCATED (2) 2 1/2"0 CONDUIT DROPS THROUGH FINISHED CEILING, TO END AT THE TOP OF COMPUTER FABRICATION OF EQUIPMENT, OR THE PERFORMANCE OF ANY WORK CABINET (TO BE FIELD LOCATED). IN ADDITION POWER CONDUIT SHOULD TERMINATE THAT MAY BE AFFECTED. DO NOT ALTER DRAWINGS, DIMENSIONS, OR AT 12 CCA. SPECIFICATIONS IN ANY WAY WITHOUT CONTACTING AND RECEIVING 11 CC LOCATED �CA.ED E� F --- TERMINATION POINT OF RACEWAYS #10 #11 AND #12 ABOVE THE FILTER PLATE. WRITTEN CONFIRMATION FROM SMS PROGRAM MANAGER. ALL 5 O TO BE FIELD LOCATED. PROVIDE OPENINGS IN THE BOTH ENDS OF EACH RACEWAY. DIMENSIONS ARE FROM FINISHED SURFACES. CONDUIT AND PULL BOXES TO BE INSTALLED BY THE CUSTOMER/CONTRACTOR WITH B ``+\ 3 LOCATIONS BEING FIELD VERIFIED BY SMS PROJECT MANAGER. E-: `-_� ® S.B.C. WALL MOUNTED, RECESSED JUNCTION BOX WITH ONE 1" SPLIT CHASE NIPPLE ON 8 SPLIT, REMOVABLE COVER FLUSH WITH FINISHED WALL AT 6" CENTER A.F.F. 3) POWER SUPPLY SOURCE: POWER SUPPLIES FOR SIEMENS MEDICAL SYSTEMS EQUIPMENT SHALL BE DEDICATED SERVICES KEPT S.B.C. PULL BOX MOUNTED FLUSH WITH FINISHED WALL AT 5 -6 A,F,F, ON WALL CLOSET 10 2 Cgt INSIDE THE RF CABIN (FOR MAGNET STOP). PROVIDE CONNECTING PIECE OF NON- ENTIRELY FREE AND INDEPENDENT OF ALL OTHER BUILDING WIRING • F - ;----------------------------- AND EQUIPMENT, SUCH AS: ELEVATORS, GENERATORS, PUMPS, HVAC------------------------- FERROUS CONDUIT TO THE INSIDE OF THE CLOSET. � ® 7 pS 6 ! SYSTEMS, ETC. THE CONTRACTOR SHALL COORDINATE THIS WORK M q TIP --- CEILING MOUNTED JUNCTION BOX FOR CONNECTION TO UPS, (UPS SUPPLIED BY WITH THE CUSTOMER/UTILITY COMPANY FIELD REPRESENTATIVE. M OO MED-LAB, INSTALLED BY CONTRACTOR). EQUAL E4U 4) WORK FURNISHED BY CUSTOMER/CONTRACTOR: WORK NOT I~ M 1 SIZE AS REQUIRED CONDUIT FROM POWER SOURCE TO CB1. SEE DETAIL E-501/1 PROVIDED BY SIEMENS MEDICAL SYSTEMS BUT SHOWN ON DRAWINGS MS AB PO ! � TO BE FURNISHED AND INSTALLED BY CUSTOMER/CONTRACTOR 2 SIZE AS REQUIRED CONDUIT FROM C81 TO UPS. SEE DETAIL E-501/1 INCLUDES THE FOLLOWING BUT IS NOT LIMITED TO UNLESS NOTED •9 1 OTHERWISE: ELECTRICAL RACEWAYS AND DUCTS, WIRING TROUGHS, 3 SIZE AS REQUIRED CONDUIT FROM UPS TO CCA. SEE DETAIL E-501/1 PULL BOXES, CONDUITS, CIRCUIT BREAKERS, EMERGENCY OFF 2 BUTTONS, DOOR SWITCHES, WARNING LIGHTS, WIRING, WIRING MC i 4 (1) 1/2"� CONDUIT FROM C61 TO EPO. SEE DETAIL E-501/1 DEVICES, CONNECTORS, LIGHTING EQUIPMENT AND GROUNDING. low 3 5 (1) 1/2"0 CONDUIT FROM EPO TO UPS. SEE DETAIL E-501/1 5) RACEWAY AND CONDUIT NOTES: RACEWAY SHALL BE ELECTRIC 1=4 L� 6 (2) 1/2"0 CONDUIT FROM EPO TO EPO. SEE DETAIL E-501/1 METALLIC TUBING (EMT) FOR RIGID CONDUIT WORK, OR WHERE 0. ® 7 SHORT OFF-SET CONNECTIONS ARE REQUIRED LIQUIDTIGHT FLEXIBLE O �H O (1) 2 1/2"0 ONE EMPTY CONDUIT FROM "CCA" TO JUNCTION BOX "AB". RUN ABOVE FINISHED METAL CONDUIT SHALL BE USED. FIELD BENDS SHALL NOT BE LESS [� Q Q RDIAG ! CEILING AND IN THE PARTITION. THAN AS SHOWN IN TABLE 346-10 OF THE NATIONAL ELECTRICAL ® � N <c CODE. PROVIDE A JETLINE "SUPER TRUE TAPE", OR EQUIVALENT M=111 �..p � r�•w w1 MRI SCAN ROOM CONTROL AREA QSER O8 (1) 2 1/2"� TWO,EMPTY CONDUITS IN PARTITION AND ABOVE FINISHED CEILING FROM "MC" CONDUIT MEASURING TAPE FISH LINE IN ALL RACEWAYS AND �G =0+12" TO "CCA$'. CONDUITS. i 9 (1) 2 1/2"0 ONE EMPTY CONDUIT FROM "MC" TO JUNCTION BOX "AB". RUN IN THE PARTITION. 1:14 :3 *uv) CONDUIT BODIES SHALL NOT BE USED. WHERE A CONDUIT ENTERS A ------- 0 10 12"W x 4"D ALUMINIUM RACEWAY WITH COVERS, DIVIDED INTO THREE EQUAL SIZE COMPARTMENTS. BOX, FITTING, OR OTHER ENCLOSURE, AN INSULATED THROAT i i MOUNTED ABOVE FINISHED CEILING IN RF CABIN. RACEWAY IS REQUIRED TO SUPPORT CONNECTOR SHALL BE PROVIDED TO PROTECT THE WIRE FROM i____________ ________ ! INTERCONNECTING CABLES BETWEEN SIEMENS COMPONENTS. ABRASION. CONNECTORS SHALL BE DOUBLE SET SCREW TYPE, STEEL CONCRETE TIGHT. —I F-1 I El :1 F_ _71 i I 11 4"W x 4"D ALUMINIUM RACEWAY WITH COVERS (FOR GRADIENT CABLES). RACEWAY T4 BE MOUNTED KEEP RACEWAYS AT LEAST 6 INCHES AWAY FROM PARALLEL RUNS OF ABOVE FINISHED CEILING IN RF CABIN. RACEWAY IS REQUIRED TO SUPPORT GRADIENT CABLES BETWEEN FILTER PLATE AND MAGNET. FLUES OR STEAM AND HOT WATER PIPES. INSTALL HORIZONTAL RACEWAY RUNS ABOVE WATER AND STEAM PIPES PROVIDED THAT 12 4"W x 4"D ALUMINIUM RACEWAY WITH COVERS, MOUNTED ABOVE FINISHED CEILING IN RF CABIN, CABLE RUN DISTANCES ARE MAINTAINED. USE TEMPORARY CLOSURES RUNNING BETWEEN FILTER PLATE AND MAGNET (FOR WATER HOSES). TO PREVENT FOREIGN MATTER FROM ENTERING RACEWAY. CONDUIT RUNS ARE SHOWN SCHEMATICALLY. INSTALL CONDUIT WITH ALL JUNCTION BOXES, RACEWAYS, ETC. FOR SIEMENS EQUIPMENT SHOULD BE A MINIMUM OF BENDS IN THE SHORTEST PRACTICAL DISTANCE POSITIONED UNDER MED-LAB'S SUPERVISION. CONSIDERING THE BUILDING CONSTRUCTION AND OBSTRUCTIONS, PROVIDE BUSHINGS AS NECESSARY. EXCEPT AS OTHERWISE INDICATED. THE CONTRACTOR SHALL MAKE E: S.B.C.= SIZE BY CONTRACTOR CERTAIN THAT ANY CONDUIT/RACEWAY RUNS CONTAINING SIEMENS CCA MEDICAL SYSTEMS CABLES DO NOT EXCEED THE SPECIFIED MAXIMUM �1 DISTANCES AS SHOWN ON THE ELECTRICAL DETAILS. > PROVIDE ENCLOSED METAL RACEWAY SYSTEM (WIRE DUCT) WHERE . 3 SHOWN ON DRAWINGS WITH DIVIDERS TO SEPARATE THE DUCT (FOR *Two - POWER AND SIEMENS MEDICAL SYSTEMS CABLING). DIVIDERS AND y CROSSOVER PIECES TO BE PROVIDED AS NECESSARY. - 'n .c PROVIDE WIRE DUCT/RACEWAY WITH ACCESSIBLE REMOVABLE COVERS. CONTRACTOR SUPPLIED CABLES LOCATIONS OF OPENINGS TO BE CUT IN FIELD ARE TO BE 0 cu COORDINATED WITH SIEMENS PROJECT MANAGER. ELECTRICAL PULL ; FROM VIA TO DESCRIPTION REMARKS BOXES AND RACEWAY COVERS SHALL BE INSTALLED IN A MANNER TO ALLOW ACCESSIBILITY FOR INSTALLATION AND MAINTENANCE. IN- w I FLOOR TRENCH DUCT AND FLUSH FLOOR BOXES SHALL BE PROVIDED e ; 1 CB1 3 PHASE CONDUCTORS, 1 NEUTRAL, 1 ISOLATED GROUND (ALL TO BE SEE DETAIL E-501/1 WITH FULLY GASKETED REMOVABLE COVERS. EQH1SA THE SAME SIZE) AND 1 CASE GROUND TO BE SIZED BY ELECTRICAL WIRE DUCT RACEWAY SHALL BE MADE ELECTRICALLY CONTINUOUS CONTRACTOR. THROUGHOUT ITS LENGTH BY MEANS OF BONDING TOGETHER DUCT ; J ELECTRICAL PLAN C61 2 UPS 3 PHASE CONDUCTORS, 1 NEUTRAL, 1 ISOLATED GROUND (ALL TO BE SECTIONS AT ALL JOINTS WITH AN EQUIPMENT BONDING JUMPER. THE SAME SIZE) SIZED BY ELECTRICAL CONTRACTOR. BONDING JUMPERS SHALL BE A MINIMUM #8 AWG BARE STRANDED COPPER CONDUCTOR AND CONNECTED BY MEANS OF AN EXOTHERMIC SCALE: 1 /4$) = 1 —O" UPS 3 CCA 3 PHASE CONDUCTORS, 1 NEUTRAL, 1 ISOLATED GROUND (ALL TO BE WELDING PROCESS. SHEET METAL SCREWS SHALL NOT BE USED THE SAME SIZE) SIZED BY ELECTRICAL CONTRACTOR. TO CONNECT GROUNDING CONDUCTORS. J , , CB1 4 EPO 2 #12 6) WIRING: WIRING SHALL BE INSTALLED IN METAL RACEWAY, 600 VOLT CLASS, STRANDED TYPE THHN-THWN, SINGLE CONDUCTOR EPO 5 UPS 2 #12 ANNEALED COPPER FOR A MAXIMUM OPERATING TEMPERATURE OF 75' C (165- F). SIZED AS INDICATED. THE CUSTOMER/CONTRACTOR EPO 6 EPO 4 #12 SHALL LEAVE MINIMUM 10 FT. WIRE TAILS AT ALL OUTLET POINTS WITH WIRE IDENTIFICATION TAGGED AT BOTH ENDS FOR FINAL O r�► CONNECTION BY SIEMENS MEDICAL SYSTEMS. �J 7) GROUNDING REQUIREMENTS: NONCURRENT-CARRYING CONDUCTIVE SURFACES SHALL BE GROUNDED BY A #6 A.W.G. INSULATED GREEN COPPER CONDUCTOR INSTALLED IN THE METAL a T RACEWAY WHICH CONTAINS THE BRANCH-CIRCUIT CONDUCTORS 0 SUPPLYING THE EQUIPMENT. SIEMENS SUPPLIED CABLES 8) IN ADDITION TO THE CIRCUIT BREAKER LOAD CURRENT RATING, CONSIDERATION MUST ALSO BE GIVEN TO SELECTING CIRCUIT BREAKERS THAT HAVE A HIGH ENOUGH SHORT CIRCUIT CURRENT FROM VIA TO DESCRIPTION REMARKS WITHSTAND RATING TO SAFELY COORDINATE WITH THE POWER SYSTEM AVAILABLE SHORT CIRCUIT CURRENT. GENERALLY, WHEN THE 480 VOLT, 3 PHASE, X-RAY EQUIPMENT IS SERVED FROM A POWER SUPPLY SYSTEM THAT IS PROVIDED WITH A 500 KVA OR SMALLER o� CCA --- FILT MAXIMUM LENGTH 4'-0". TRANSFORMER, A STANDARD 14,000 RMS AMPERE WITHSTAND a RATED CIRCUIT BREAKER WILL BE ADEQUATE. HOWEVER, IF THE F 1 1 B MAXIMUM LENGTH 26 -0'. POWER SUPPLY SYSTEM TRANSFORMER IS LARGER THAN 500 KVA, ++ CABLE LENGTH RESTRICTIONS POWERWARE UPS SPECIFICATIONS --- THEN THE CIRCUIT BREAKERS HAVING A SHORT CIRCUIT WITHSTAND F MS MAXIMUM LENGTH 49'-0". RATING GREATER THAN 14,000 RMS AMPERES MAY BE REQUIRED. 1) THE STANDARD CABLE LENGTH OF THE GRADIENT CABLES FROM CCA 8 MC MAXIMUM LENGTH 75'-0". THE FILTER PLATE CONNECTING TO THE LEFT REAR CORNER OF THE MAGNET IS 16 FEET. POWERWARE MODEL 80/80 SPECIFICATIONS (80 KVA/64 KW) CCA 7 AB MAXIMUM LENGTH 75'-0". POWER QUALITY INPUT VOLTAGE: 480 VOLTS 2) THE STANDARD CABLE LENGTH OF THE GRADIENT CABLES FROM THE FILTER PLATE TO THE TOP OF THE GCA IS 3 FEET. IF IT IS OUTPUT VOLTAGE: 480 VOLTS NOT POSSIBLE TO POSITION THE ELECTRONICS CABINET DIRECTLY INPUT FREQUENCY: 60 HZ BENEATH THE FILTER PANEL, EXTENDED CABLE SETS ARE AVAILABLE POOR POWER WILL ALTER EQUIPMENT PERFORMANCE ,. WITH CABLE LENGTHS UP TO 42 FEET. THE EXTENDED CABLE SET HEAT DISSIPATION: 22,000 BTU/HR MUST BE SPECIFIED IN THE EQUIPMENT ORDER. NOMINAL INPUT AMPS: 105 POWER SPECIFICATIONS CONTAINED HEREIN MUST BE MET 3) CABLES MAY BE SPECIAL ORDERED IF NECESSARY WITH A MAXIMUM INPUT AMPS: 131 AT ALL TIMES. GROUNDING, LINE IMPEDANCE, AND MAXIMUM LENGTH OF 65 FEET FROM THE ELECTRONICS CABINET TO INPUT BREAKER: 150 AMPS OTHER DESIGN CONSIDERATIONS MUST BE REVIEWED THE LEFT REAR CORNER OF THE MAGNET TO BE DIVIDED INSIDE BY AN EXPERT PRIOR TO CONSTRUCTION. AND OUTSIDE THE RF ROOM AS SPECIFIED BY THE PLANNER. AC OUTPUT NOMINAL AMPS: 96 AC OUTPUT MAXIMUM (10 MIN.): 120 AMPS AUDIBLE NOISE: 65 dBA. TOTAL BATTERY TIME: 7 MINUTES AT FULL LOAD (64 KW) DIMENSIONS: 62"W x 31.5"D x 73.5"H SYMBOLS TOTAL WEIGHT: 5,050 LBS. J J _ Z ALL MAY NOT APPLY LIGHTING GUIDELINES � ® CAUTION OR WARNING W � ® CRITICAL NOT EXAM, CONTROL, AND EVALUATION ROOMS: ® EZZI CIRCUIT BREAKER BY CUSTOMER/CONTRACTOR 1) THE ROOM LIGHTING MUST REMAIN FUNCTIONAL WHEN THE MR 4 SYSTEM IS SWITCHED OFF AND/OR WHEN EMERGENCY SHUTDOWN ® OPENING IN RACEWAY OR TRENCHDUCT BUTTONS ARE ACTIVATED, Z W 2) IT MUST BE POSSIBLE TO CONTROL THE INTENSITY OF W ® PULLBOX IN (FLOOR/WALL/CEILING) ILLUMINATION OF APPROXIMATELY 46 FOOT-CANDLES THROUGH GROUP W OPENING IN ACCESS FLOORING CONNECTION. ALL LIGHTS IN THE EXAMINATION ROOM ARE POWER REQUIREMENTS CONNECTED TO A COMMON SWITCH IN THE CONTROL ROOM. THERE W ® WARNING LIGHT (MAGNET ON) SHOULD BE SEPARATE SWITCHES IN THE EXAMINATION ROOM FOR RATED LINE VOLTAGE 440, 480 VOLTS (±10%), 3 PHASE, 60 Hz THE GROUPS OF LIGHTS ABOVE AND NEAR THE PATIENT TABLE, AS DS DOOR SAFETY SWITCH INTERNAL RESISTANCE 0.2 OHMS FOR ALL VOLTAGES WELL AS FOR THE GROUP OF LIGHTS ABOVE THE MAGNET. THE (EPO) POWER OFF BUTTON EPO) EMERGENCY 50 KVA WYE OR DELTA CONNECTION SWITCHES ARE TO BE LOCATED OUTSIDE THE EXAM ROOM. CURRENT 100 AMPS (TOTAL AT 480 VOLTS) EXAMINATION ROOM: Uj 0 ® TRENCHDUCT 150 AMP, 80 KVA SERVICE REQUIRED WHEN EXIDE PLUS 80/80 1) THE MAGNETIC FIELD ADVERSELY AFFECTS THE OPERATING LIFE U.P.S. SYSTEM IS UTILIZED WITH THE MAGNETOM SYSTEM. OF LIGHT BULBS LOCATED IN THE IMMEDIATE VICINITY OF THE U. E - - CEILING DUCT MAGNET, THE FILAMENT IN THE BULB OSCILLATES WITH THE PERMISSIBLE POWER 2% MAXIMUM BETWEEN PHASES FREQUENCY OF THE POWER SUPPLY. DURING SCANNING, IT IS UNDER FLOOR DUCT SUPPLY FLUCTUATIONS REQUIRED THAT LIGHT FIXTURES IN THE VICINITY OF THE MAGNET ® VERTICAL DUCT PERMISSIBLE FREQUENCY (IN EXAMINATION ROOM) BE CONNECTED TO A DC VOLTAGE SUPPLY. FLUCTUATIONS f1Hz @ 50/60 Hz. THE RESIDUAL RIPPLE OF THE DIRECT VOLTAGE SHOULD BE t5%. ETHERNET CONNECTION TO CUSTOMER'S INFORMATION WHEN INSTALLING THE LIGHT SOCKET, ENSURE THAT THE POLARITY IS ETH > SYSTEMS NETWORK (VERIFY WITH SMS PROJECT MANAGER). PERMISSIBLE HIGH CORRECT. STANDARD TELEPHONE LINE FOR REMOTE EQUIPMENT 30 kHz RANGEE. LINE INTERFERENCES FREQUENCY (CONTINUOUS) <1 VOLT WITH THE . KHz TO 2) FLUORESCENT LIGHTS, ENERGY-SAVING LIGHTS, AND DIMMERS DIAGNOSTICS. THE PHONE LINE MUST BE DATA-QUALITY ARE NOT PERMITTED. RDIAG WITH DIRECT DIAL-IN AND DIAL-OUT CAPABILITY SIMILAR <100 VOLT PEAK BETWEEN PHASES DRAWN: YjS/Jj3/R.L TO A FAX LINE. DO NOT ROUTE THE PHONE LINE PERMISSIBLE INTERFERENCE AND BETWEEN PHASES AND CONTROL AND EVALUATION ROOM: THROUGH HOSPITAL PBX OR SWITCHBOARD. PEAKS NEUTRAL OR GROUND FOLLOW THE APPROPRIATE GUIDELINES FOR LIGHTING IN ROOMS WITH CHECKED: JL.C./R.R D STANDARD TELEPHONE LINE FOR SERVICE. DO NOT ALL VALUES MEASURED AT ELECTRONICS CABINET (CCA). MONITOR WORKSTATIONS. SER ROUTE THROUGH HOSPITAL PBX OR SWITCHBOARD. +XX 110 VOLT, 20 AMP, FOR REASONS OF OPERATIONAL SAFETY, AUXILIARY EQUIPMENT (E.G. DATE: 05/10/2001 HOSPITAL GRADE DUPLEX OUTLET AIR CONDITIONING UNITS) MUST NOT BE CONNECTED TO THE SYSTEM EQUIPMENT ROOM: c LOCATED NEAR THE RDIAG PHONE LINE. POWER SUPPLY. ILLUMINATION INTENSITY SHOULD BE APPROXIMATELY 46 FOOT-CANDLES. ro SCALE: AS SHOIUV a SEAL­_ , LO ro 0 RIC .. cn ` t .rte i • � d �s r•r�r� '..tty`. .yam THE RC GROUP 3 Consulting Engineers Sheet No. Lo 10821 N.Kendall Drive. C) Suite 215 a- ]diami, Florida 33178 (308) 275-8083 cu ELECT. ENG.: JORGE L CRUZ MG. 51901 t v NECH. ENG.: ROBERT A ROSNER REG. 38005 m RC# 21314 cu JOB # 21026