01-0610-017 Revisions: FIRE PROTECTION SYMBOL LEGEND Z m SYMBOL DESCRIPTION 0 EIRE PROTECTION GENERAL NOTES © PENDANT SPRINKLER HEAD. �p O EXISTING PENDANT SPRINKLER HEAD. /® W M 1- THE FIRE PROTECTION SYSTEM SHALL CONFORM TO NFPA 13 (1994), NEW UPRIGHT SPRINKLER HEAD. SFBC 1994 DADE COUNTY EDITION AND FAC 59A-3 (2000). ?a 2- SPRINKLERS SHALL COVER THE ENTIRE AREA OF THE ROOM EXISTING UPRIGHT SPRINKLER HEAD INCLUDING ALCOVES, SPRAY SHALL NOT BE BLOCKED BY WALLS OR < 0 PARTITIONS OR CURTAINS. _® NEW SIDEWALL SPRINKLER HEAD me 3- CHECK ALL ARCHITECTURAL, HVAC AND ELECTRICAL CONTRACT EXISTING SIDEWALL SPRINKLER HEAD. DRAWINGS AND COORDINATE PIPING AND SPRINKLER HEAD LAYOUTS O < WHERE INTERFERENCE OCCURS, THE CONTRACTOR SHALL CONSULT ��o INDICATES TO REMOVE EXISTING SPRINKLER w WITH OTHER TRADES AND RELOCATE PIPING, ETC. AS REQUIRED AFTER CONSULTATION WITH ENGINEER. HEADS AND REPLACE/ REUSE AS REQUIRED. � EXTEND EXISTING PIPING AS REQUIRED 0 ONE" 4- KEEP ALL PIPING AS CLOSE TO STRUCTURE ABOVE AS POSIBLE TO NEW LOCATION. p Q *V SO AS TO AVOID INTERFERENCE WITH DUCTS, LIGHTS, RF SHIELDING AND F NEW FIRE PROTECTION PIPE. N <a : ELECTRICAL CONDUITS, WHERE POSSIBLE KEEP PIPES AT LEAST 4 INCHES APPART. - -- F- -- EXISTING FIRE PROTECTION PIPE. v>t 5- ALL SPRINKLERS SHALL BE QUICK RESPONSE TYPE, 1657. oG 6- HANGERS AND PIPE SUPPORTS SHALL BE LOCATED AND INSTALLED O.S & Y VALVE. r® IN ACCORDANCE WITH NFPA 13, 4-52. -��- CHECK VALVE. v/ O 7- USE HANGERS IN ALL ARMOVERS EXCEEDING 24" LENGTH. da ZONE VALVE AND TAMPER SWITCH. 8- ALL DROPS AND ARMOVERS TO BE 1" PIPE. 9- ALL MATERIALS INSIDE OF RF SHEILDING ENVELOPE TO BE NON-FERROUS y FLOW INDICATOR SWITCH. NON-MAGNETIC. SIAMESE FIRE DEPARTMENT CONNECTION, 0 FR SPECIAL DRY HEAD FOR FREEZER. t ® FIRE PUMP. 0 JP JOCKEY PUMP. FLOW METER. >� � o vs ® NEW TO EXISTING CONNECTION. 0 DENOTES HYDRAULIC CALCULATION POINT. 0 ALL SYMBOLS SHOWN ARE NOT NECESSARILY USED FOR THIS 0 ch x w , eV CONCRETE ANCHOR NO POWDER DRIVEN FASTENERS SHALL BE USED. S '� I b DIELECTRIC UNION I STRUCTURE a� STRUCTURE STEEL PIPE I HANGER SEE DETAIL O I AND NOTE 8 1 1/2"OF THREAD I FOR ROD DIA. & SPACING BRASS FEEDTHRU I @ EA. END OF ROD I SEE SPECS. WAVEGUIDE i 2" ISOLATION (TYP.) I � FOR MATERIALS AND INSTALLATION INSIDE RF SHEILDING ENVELOPE SEE DETAIL THIS SHEET V� ------------ -r - ------------- U BRASS LOCKNUTS i FOR PIPE SIZE 1 MINIMUM PIPE SIZE SEE F.P. DWGS. i 0 W RF PANEL W/ COPPER ARMOVER HANGER RING Z SHIELD � 1" x 1/2" OR 1" x 3/4" i •• Z BUSHING AS APPLICABLE _ _ Q COPPER PIPE CONCEALED SPRINKLER ; NOTE: i HEAD BASE BRACKET I EXISTING CEILING W CO HANGERS AND INSTALLATION TO 0 Z BE PER NFPA 13. LLI 0 I J ALL MATERIALS INSIDE RF SHEILDING ENVELOPE TO BE I J WAVEGUIDE DETAIL NON-FERROUS, NON MAGNETIC. 1 FIRE PROTECTION HANGER DETAIL 0 N.T.S. COORDINATE ALL INSTALLATION SPRINKLER COVER W/ SHEILD PROVIDER. N.T.S. W ARMOVER DETAIL m N.T.S. tt O t -q{ 7O�.a t._•`Lam:o< +.;"t t l.,` `"Y E..<: �... BY fjfl SHALL BE. EzD FOR ct:-.::. f�'L.,�: p�..':i.�+�i w f j.._'.`.t;':1, a`3r•�," T..., All, DRAWN: Yj3/Jj3/RL L !'�?:� f•'.+•:y ;rlr'i.: ''Rui�-�T;J;. .1'F�IL"i� CHECKED: J.L..C./R.R DP1,TE B DATE: 05/10/2001 LO cz SCALE: AS SHOWrt U c-t SEAL Ln g a.) 1�1 THE RC GROUP 3 Consulting Engineers Sheet NO. 10621 N.Kendall Drive. o Suite 216 EM Miami, Florida 33176 4 v 308 278-6083 ELECT. ENG.:ME L CRUZ REG. 51901 FP-1 N F- ENG.: ROBERT W. ROMER MG. 38005 m RC# 21314 cu JOB # 21026