01-0610-013 Revisions: HVAC DESIGN REQUIREMENTS EXISTING AHU SCHEDULE HVAC GENERAL (VOTES HVAC SYMBOL LEGEND YES NO UNIT DESIGNATION (EXIST) AHU-2 SYMBOL DESCRIPTION DUCT SMOKE DETECTOR X (EXIST.) 1- ALL WORK SHALL BE IN ACCORDANCE WITH NFPA 90 (1993), < RELOCATED S.F.B.C. (1994) AND F.A.C. 59A-3 ( 2000 ). ® SUPPLY DUCT ® L. FIRE DAMPER(S) X (EXIST.) 1-0 pong SMOKE DAMPERS X (EXIST. 2 AND ARCHITECTURAL S NID WITH REFLECTED OTHER TRADES. PLAN RETURN/EXHAUST DUCT .^. ( ) ) SUPPLY AIR BEFORE/AFTER 22000/22525 FIRE RATED ENCLOSURE X (EXIST.) 3- ALL PIPING AND DUCTS IN FINISHED ROOMS OR SPACES SHALL w FIRE RATED ROOF/CEILING ASSEMBLY X RETURN AIR BEFORE/AFTER 18800/19405 BE CONCEALED IN FURRED CHASES OR SUSPENDED CEILINGS. FLEXIBLE CONNECTION 00 W M 4- ACCESS PANELS IN SUSPENDED CEILINGS ARE REQUIRED FOR ALL H FIRE STOPPING X (EXIST.) OUTSIDE AIR BEFORE/AFTER 3200/3120 DAMPERS, VALVES AND EQUIPMENT REQUIRING MAINTENANCE. ELBOW WITH VANES off_ SMOKE CONTROL X 5- ALL DUCTWORK SHALL BE IN ACCORDANCE WITH SMACNA < C C STANDARDS FOR DUCT CONSTRUCTION. }-� MANUAL VOLUME DAMPER FILTER-FINAL 90% 6- PROVIDE TURNING VANES AT ALL SQUARE ELBOWS. w < O:;� 7- ALL DUCTWORK SHALL BE METALLIC, INSULATED WITH FSD FIRE SMOKE DAMPER V FIBERGLASS BLANKET (MIN R=4.5) UNLESS INDICATED OTHERWISE. N m"MCC 8- DUCT SIZES SHOWN ARE CLEAR INSIDE DIMENSIONS. FIRST r.i o FIGURE OF DUCT SIZE INDICATES FACE SHOWN OR INDICATED. EXHAUST REGISTER V) o �.. 9- SUBMIT PRIOR TO START CONSTRUCTION 3/8 SCALED DUCTWORK N <4: SHOP DRAWINGS INDICATING EACH COMPONENT TO BE USED. �" POINT OF CONNECTION-NEW TO EXISTING m=I "A w 10- PLANS ARE DIAGRAMMATIC; CONTRACTOR SHALL NOT SCALE rr��,, 2 DRAWINGS FOR DIMENSIONS. L3A SMOKE DETECTOR dad 11- DESIGN IS BASED ON ONE MANUFACTURER PRODUCTS. EQUIVALENT 0 PRODUCTS ARE ACCEPTABLE SUBJECT TO SHOP DRAWINGS THERMOSTAT APPROVAL. THE CONTRACTOR WILL BE RESPONSIBLE FOR ALL O CHANGES AND EXPENSES REQUIRED TO ACCOMMODATE SUBSTITUTE X: AIR DEVICE TYPE EQUIPMENT INCLUDING REDESIGN. EXHAUST _x \ #: CFM 12 T TESTED E TED AXB: IE X I S EXISTING -AN SCHEDULE INDEPENDENT CERTIFIED AND BALANCE CONTRACTOR. GRIL LE E SIZE FOR RETURN OR EXHAUST. SUBMIT RESULTS TO A/E. 13- PROVIDE EACH SUPPLY OUTLET WITH A DAMPERING DEVICE BEFORE AFTER TO PERMIT BALANCING. / EXISTING TO BE REMOVED � 14- MAINTAIN MINIMUM 7" CLEARANCE BETWEEN DUCTWORK AND ANY CORRIDOR WALL, OR FIRE WALL. — — — — — EXISTING TO REMAIN W. n EXHAUST FAN #4 1065/985 15- ALL DUCTS SHALL PENETRATE THE WALLS AT 90 DEGREES ANGLE. >� a THERE SHALL BE NO ELBOWS OR OTHER FITTINGS AT THE WALL w PENETRATION. 16- CONTRACTOR SHALL VISIT THE JOB SITE AND THOROUGHLY �y FAMILIARIZE WITH ALL EXISTING CONDITIONS. - 1 17- DUCTS OR PIPING SHALL NOT BE INSTALLED WITHIN REQUIRED CLEARANCES FOR SPACES DEDICATED FOR PANELBOARDS. ® ® x COORDINATE ALL WORK WITH OTHER TRADES. pi�+ �+ 18- ALL DUCT AND PIPING SUBJECT TO THERMAL EXPANSION AND/OR �1� ' AIR DISTRIBUTION SCHEDULE NOSTALLEDIOAS TESTED EAND RAAPPROVED BY OR PARTITIONS PROVDE COPY LOFE MANUFACTURER'S INSTRUCTIONS AT THE AHCA INSPECTIONS. 19- THESE DRAWINGS SHALL BE REVIEWED AND APPROVED BY ) SYMBOL SERVICE MAN8UFACTURER MODEL N0. DESCRIPTION REMARKS AHCA, ANY CHANGES OR AHCA RECOMMENDATIONS SHALL BE J ,-- INCLUDED ON THESE DRAWINGS OR ISSUED AS AN ADDENDUM TO O TITUS TDC-AA LOUVER FACE CEILING DIFFUSER THIS CONTRACT. ; SUPPLY AIR WITH FLANGE FRAME, AND OBD. 20- DUCTWORK, ISIUESROVRTFIS2E AMAMM FITTINGS O5 AND A MAXIMUM SMOKE DEVELOPED RATING OF 50. , OB RETURN TITUS SOF EGG CRATE GRILLE, FLANGE FRAME WITH OBD. 21- A COPY OF THE TEST AND BALANCE REPORT SHALL BE AVAILABLE AT THE FINAL AHCA INSPECTION. 22- PRIOR TO COMMENCING DEMOLITION WORK ALL SPACES SHALL BE AIR O r� OC EXHAUST TITUS 50F EGG CRATE GRILLE, FLANGE FLOW TESTED AND RESULTS RECORDED. FAN AND AIR HANDLER �l FRAME WITH OBD. PERFORMANCE SHALL BE VERIFIED FOR NEW WORK. DISCREPANCIES SHALL BE REPORTED TO ARCHITECT/ENGINEER FOR RESOLUTION. 23- TEST AND BALANCE REPORT SHALL BE SUBMITTED FOR ENGINEER'S a ' OE EXISTING APPROVAL AND A COPY OF THE REPORT SHALL BE AVAILABLE AT THE FINAL AHCA INSPECTION. °$ NOTES: 24- PRIOR TO DEMOLITION EXISTING HVAC EQUIPMENT IN PROJECT AREA SHALL BE AIR FLOW TESTED DISCREPANCIES SHALL BE REPORTED TO THE 1- PROVIDE WITH FLANGE FOR SURFACE MOUNTING. ENGINEER 2- PROVIDE WITH OPPOSED BLADE DAMPER. Z 3- PROVIDE SUPPLY DIFFUSER WITH EQUALIZING GRID. 4 tj a ABBREVIATIONS W REHEAT TERM SCHEDULE z MARK CV-1 SA SUPPLY AIR Z O RA RETURN AIR EA EXHAUST AIR CFM 900 OA OUTDOOR AIR AFF ABOVE FINISH FLOOR Z CFM CUBIC FEET PER MINUTE Uj INLET 10" GPM GALLONS PER MINUTE 0 � ACU AIR CONDITIONING UNIT Uj AHU AIR HANDLING UNIT RUNOUT 12" CEF CEILING EXHAUST FAN PRE POWER ROOF EXHAUSTER J MIN INLET S.P IN H BDD BACKDRAFT DAMPER 2O 0.5 MVD MANUAL VOLUME DAMPER O MD MOTORIZED DAMPER o EAT OF 50 FD FIRE DAMPER z SD SMOKE DAMPER FSD FIRE-SMOKE DAMPER LAT °F 90 SH-E STEAM HUMIDIFIER-EXISTING HC HEATING COIL BTUH 38880 GPM 1800 WATER 4.0 PIPE SIZE V" NOTE: DRAWN: Y:G/ jCZ/RL EQUAL TO TITUS PESV SIZE 10 WITH CONSTANT VOLUME CONTROL CHECKED: J.L.C./R.R AND HOT WATER COIL. BOX TO BE PRESSURE INDEPENDENT WITH PNEUMATIC, OPERATOR DATE: 05/10/2001 AND WALL CONTROLLER. BOX LINING TO BE NON-ERODING. rr SCALE: AS SHOUN cc U 0o SEAL CU Cu LO a—I 7 - .' ro U cm U THE RC GROUP Consulting Engineers Sheet No. 10621 N.Kendall Drive. CD Suite 215 U ro ami, Florida. 33176 (305) 275-8083 m ELECT. ENG.: JORGE L CRUZ REG. 51901 AC- 1 N F. ENG.: ROBERT W. ROSNER REG. 380D5 q m RC# 21314 JOB # 21026