ROOM LEGEND
801 MEN'S TOILET
802 WOMEN'S TOILET DRAWING REFERENCE NOTES
803 CORRIDOR
CA 804 CORRIDOR O RELOCATED AIR HANDLING UNIT, RECONNECT TO EXISTING PIPING,
805 CLOSET WIRING AND CONTROLS, REINSTALL EXISTING AUXILIARY DRAIN PAN
CORRIDOR 806 CORRIDOR AND PR❑VIDE A MOISTURE SENSOR IN PAN TO DE–ENERGIZE UNIT,
PR❑VIDE NEW SUPPLY AIR AND RETURN AIR DISTRIBUTI❑N SYSTEMS,
ORECONNECT EXISTING FLEXIBLE SUPPLY AIR DUCT FOR ADJACENT
AREA TO NEW SUPPLY AIR DISTRIBUTION SYSTEM,
e
ORECONNECT EXISTING OUTSIDE AIR DUCT TO NEW INTAKE PLENUM International
WITH A NEW MANUAL VOLUME DAMPER, ADJUST TO 160 CFM.
I I I I
�� O4 PR❑VIDE NEW INTAKE PLENUM FULL SIZE OF AIR HANDLING UNIT Design Partnership
INTAKE,
O5 RELOCATED THERMOSTAT, SEE SHEET M-1, Incorporated
�6 NEW 6' X 6' EXHAUST AIR REGISTER, ADJUST DAMPER FOR THE
I MECHANICAL ROOM INDICATED AIR QUANTITY, 30 W. Mashta Drive
N.I.C. Key Biscayne, Fl 33149
O NEW 24' X 24' PERFORATED FACE CEILING DIFFUSER WITH Tel: 305.365.8338/Fax: 305.365.8339
INDICATED NECK SIZE ( SEE FLEXIBLE DUCT SIZE) , BLOW PATTERN
AND AIR QUANTITY,
24' X 24' FILTER BACK RETURN AIR GRILLE, CONNECT TO NEW
INTAKE PLENUM, No. Issue Date
C I — — — O9 RELOCATE EXISTING FIRE SPRINKLERS TO NEW LOCATI❑NS
INDICATED, SEE SHEET M-1. PR❑VIDE ALL NEW FULLY CONCEALED
TYPE HEADS AND ADJUST TO NEW CEILING HEIGHTS AND LAYOUTS AS
0 o REQUIRED,
I� I 10 10' X 10' UP TO NEW EXHAUST FAN E-1 ON ROOF ABOVE,
TRANSITION AND CONNECT TO FAN AS REQUIRED. COORDINATE EXACT
o� o o L❑CATI❑N WITH OTHER EQUIPMENT AND UTILITIES WHICH ARE T❑�
)� g REMAIN, SEE GENERAL NOTE RELATED TO CUTTING OF SLAB,
_ 11 EXISTING CONDENSER WATER MAINS TO REMAIN AS IS, COORDINATE
110 9– NEW WORK TO SUIT,
6 CFM 215 801 O 3 12 NEW 8' X 8' EXHAUST C M } O HA AIR REGISTER, ADJUST DAMPER FOR THE
INDICATED AIR QUANTITY,
9 5 8 CLIENT APPROVAL
I I I have reviewed these plans and have been
CFM 10' given the opportunity to ask questions about
6 4 them prior to issue. These plans conform
11 C) to our requirements. I understand that any
X modifications to these plans will be an
� x5 � additional service with potential impact on
construction cost and scheduling.
E] ACCEPTED AS IS
a j J AHU i OUTSIDE AIR CALCULATIONS ❑ ACCEPTED AS NOTED
TOTAL GROSS AIR CONDITIONED AREA. . . . . . . . . 536 S. F. signature: Date:
)): CORRIDOR AREA . . . . . . . . . . . . . . . . . . 170 S. F.
10 5x10 170 S. F. X 0. 05 CFM/S, F. X. . . . . . . . 9 CFM
I CFM 1 x6
6 7 TOILET AREASI All drawings and written material herein, as instruments
9 140 50 CFM/WC)K X 6 X 0. 5)KX _ 150 CFM of service, shall remain the property of International
L__-�i� Design Partnership, Inc. (IDP) and shall not be reproduced
10x8 CFM TOTAL REQUIRED OUTSIDE AIR = . . . . . . . . . . 159 CFM or copied, in whole or in part, without the expressed
11x6 TOTAL OUTSIDE AIR PROVIDED BY RELOCATED AHU . . . 160 CFM written consent of IDP and may not be used or
8 0 referenced for any other project. Information contained
CCherein represents proprietary information of International
Design Partnership and/or its Client and shall not be
10' – IN ACCORDANCE WITH ASHRAE 62_1989 disclosed to others. Those who use these documents
O
IN ACCORDANCE WITH ASHRAE 62-1989, PARAGRAPH do so in confidence.
�(D� i F802 9 6. 1. 3. 4 FOR INTERMITTENT OR VARIABLE OCCUPANCY,
7 Architect of Record:
12 F 0 295 C M
i APPROVED FOR Charles Myers
BUILDING PERMITTING PURPOSES
12 I BY MIAMI-DAD State of Florida
E COUNTY FIRE DEPARTMENT
Registration #
T FIRE PROTECTION CONTRACTOR'S AR0014546
804 WOR!<ING PLAN AS PER NFPA 13
5 SHALL BE SUBMITTED FOR APPROVAL
OE TO MIAMI-DADE FIRE DEPARTMENT
806 BEFORE INSTALLED ROREMODELED REMODELED
N.I.C.
ry
DATE BY�� �
\ \\ %
I I
INTERVAL
'� _ �� _ _ _ _ _ �� _ 805 VENTILATION EQUIPMENT SCHEDULE
_ N.I.C. INTERNATIONAL
MARK MAKE MODEL TYPE CFM TIP SP RPM HP V/PH DRIVE
SPEED IN. 8th Floor
E-1 GREENHECK G-95—D I CENTRIF, PRV 1 510 3755 1 3/8 1 1319 1/8 1 120/1 DIRECT
N❑TESI 6262 Sunset Drive
807 1. FAN INSTALLED ON THE EXTERI❑R OF THE BUILDING SHALL BE CONSTRUCTED AND INSTALLED Miami, F1 33143
N.iC
TO WITHSTAND A WIND PRESSURE OF 60 PSF FROM ANY DIRECTI❑N.
2. FAN SHALL HAVE MOTOR PR❑TECTI❑N, SINGLE PHASE FAN MOTOR SHALL HAVE INHERENT
PROTECTION.
C3 ) 3. FAN SHALL HAVE UL APPROVED L❑CAL DISCONNECT MEANS,
4 ) 4 J _�/ 4. ROOF MOUNTED FAN SHALL HAVE 12' HIGH (ABOVE ROOF SURFACE), ALUMINUM, PRE– Owner: Jeff Weiss
FABRICATED CURB WITH LINER, DAMPER TRAY AND SEAL. 433 Plaza Real, Suite 275
8 I+� FLOOR PARTIAL FLOOR PLAN 5. ROOF FAN SHALL HAVE B IRDSCREEN, Boca Raton, FL 33432
6. POWER ROOF VENTILAT❑R AND BASE SHALL BE OF ALUMINUM C❑NSTRUCTI❑N.
N SCALE: 1/4"=1'-0" 7. E-1 SHALL BE ELECTRICALLY INTERLOCKED TO OPERATE WITH RELOCATED AHU, Contact: Jeff Weiss, (561) 416-4600
8. E-1 SHALL BE COMPLETE WITH GRAVITY SHUTTER,
9. COORDINATE EXACT L❑CATION OF INSTALLATION WITH OTHER EXISTING ROOF MOUNTED
EQUIPMENT AND UTILITIES WHICH ARE TO REMAIN, Date: 03-20-01
10. SEE GENERAL NOTE RELATED TO CUTTING OF SLAB, Project No: 2013.00
11. FAN SHALL BE COMPLETE WITH SPEED CONTROLLER INSTALLED AT FAN FOR BALANCING
PURPOSES ONLY. Drawn By: SJB
Checked By: JEA
/AxB AIR VOLUME H VA C DESIGN REQUIREMENTS CADD File 00-55\MECHANICAL.DWG
(A+C)x6 - / EXTRACTOR BRANCH DUCT OR
SIDEWALL OUTLET COLLAR HVAC DESIGN REQUIRES, YES NO Title:
MVD DUCT SMOKE DETECTOR X
AIR FLOW
FIRE DAMPERS X MECHANICAL
SMOKE DAMPERS X 4 -_ -
MVD FIRE RATED ENCLOSURE X _
DXB _ j � ! (� {�S�►� -- _ __- -_
DISTRIBUTION DUCT FIRE RATED ROOF/FLOOR X ' SCQIE: AS INDICATE-O
- CxB CEILING ASSEMBLY I �I`�I 98OacR #
FIRE STOPPING X f w CERTIFICATE OF^AUTHORIZATION 1438 Sheet NO.:
' 'i = NDERSON
SMOKE CONTROL
X -�`'�' ILLIAM ;Oi�1SUlTINS EN6INEER5 I�IO.a
117 MAJORCA AVE.-COMAE GAB'LIES, FLORIDA.33_134
TYPICAL DUCT TEE DETAIL TYPICAL DUCT TAKEOFF DETAIL ,- TELEPHONE (305) 442-15033
NTS NTS AWCE-JOB#: 00-55 _ ^
- - _ Sheet liuril36f ..2 _ of: 3