01-0597-018 0 ROOM LEGEND 801 MEN'S TOILET 802 WOMEN'S TOILET DRAWING REFERENCE NOTES 803 CORRIDOR CA 804 CORRIDOR O RELOCATED AIR HANDLING UNIT, RECONNECT TO EXISTING PIPING, 805 CLOSET WIRING AND CONTROLS, REINSTALL EXISTING AUXILIARY DRAIN PAN CORRIDOR 806 CORRIDOR AND PR❑VIDE A MOISTURE SENSOR IN PAN TO DE–ENERGIZE UNIT, PR❑VIDE NEW SUPPLY AIR AND RETURN AIR DISTRIBUTI❑N SYSTEMS, ORECONNECT EXISTING FLEXIBLE SUPPLY AIR DUCT FOR ADJACENT AREA TO NEW SUPPLY AIR DISTRIBUTION SYSTEM, e ORECONNECT EXISTING OUTSIDE AIR DUCT TO NEW INTAKE PLENUM International WITH A NEW MANUAL VOLUME DAMPER, ADJUST TO 160 CFM. I I I I �� O4 PR❑VIDE NEW INTAKE PLENUM FULL SIZE OF AIR HANDLING UNIT Design Partnership INTAKE, O5 RELOCATED THERMOSTAT, SEE SHEET M-1, Incorporated �6 NEW 6' X 6' EXHAUST AIR REGISTER, ADJUST DAMPER FOR THE I MECHANICAL ROOM INDICATED AIR QUANTITY, 30 W. Mashta Drive N.I.C. Key Biscayne, Fl 33149 O NEW 24' X 24' PERFORATED FACE CEILING DIFFUSER WITH Tel: 305.365.8338/Fax: 305.365.8339 INDICATED NECK SIZE ( SEE FLEXIBLE DUCT SIZE) , BLOW PATTERN AND AIR QUANTITY, 24' X 24' FILTER BACK RETURN AIR GRILLE, CONNECT TO NEW INTAKE PLENUM, No. Issue Date C I — — — O9 RELOCATE EXISTING FIRE SPRINKLERS TO NEW LOCATI❑NS INDICATED, SEE SHEET M-1. PR❑VIDE ALL NEW FULLY CONCEALED TYPE HEADS AND ADJUST TO NEW CEILING HEIGHTS AND LAYOUTS AS 0 o REQUIRED, I� I 10 10' X 10' UP TO NEW EXHAUST FAN E-1 ON ROOF ABOVE, TRANSITION AND CONNECT TO FAN AS REQUIRED. COORDINATE EXACT o� o o L❑CATI❑N WITH OTHER EQUIPMENT AND UTILITIES WHICH ARE T❑� )� g REMAIN, SEE GENERAL NOTE RELATED TO CUTTING OF SLAB, _ 11 EXISTING CONDENSER WATER MAINS TO REMAIN AS IS, COORDINATE 110 9– NEW WORK TO SUIT, 6 CFM 215 801 O 3 12 NEW 8' X 8' EXHAUST C M } O HA AIR REGISTER, ADJUST DAMPER FOR THE INDICATED AIR QUANTITY, 9 5 8 CLIENT APPROVAL I I I have reviewed these plans and have been CFM 10' given the opportunity to ask questions about 6 4 them prior to issue. These plans conform 11 C) to our requirements. I understand that any X modifications to these plans will be an � x5 � additional service with potential impact on construction cost and scheduling. E] ACCEPTED AS IS a j J AHU i OUTSIDE AIR CALCULATIONS ❑ ACCEPTED AS NOTED TOTAL GROSS AIR CONDITIONED AREA. . . . . . . . . 536 S. F. signature: Date: )): CORRIDOR AREA . . . . . . . . . . . . . . . . . . 170 S. F. 10 5x10 170 S. F. X 0. 05 CFM/S, F. X. . . . . . . . 9 CFM I CFM 1 x6 6 7 TOILET AREASI All drawings and written material herein, as instruments 9 140 50 CFM/WC)K X 6 X 0. 5)KX _ 150 CFM of service, shall remain the property of International L__-�i� Design Partnership, Inc. (IDP) and shall not be reproduced 10x8 CFM TOTAL REQUIRED OUTSIDE AIR = . . . . . . . . . . 159 CFM or copied, in whole or in part, without the expressed 11x6 TOTAL OUTSIDE AIR PROVIDED BY RELOCATED AHU . . . 160 CFM written consent of IDP and may not be used or 8 0 referenced for any other project. Information contained CCherein represents proprietary information of International Design Partnership and/or its Client and shall not be 10' – IN ACCORDANCE WITH ASHRAE 62_1989 disclosed to others. Those who use these documents O IN ACCORDANCE WITH ASHRAE 62-1989, PARAGRAPH do so in confidence. �(D� i F802 9 6. 1. 3. 4 FOR INTERMITTENT OR VARIABLE OCCUPANCY, 7 Architect of Record: 12 F 0 295 C M i APPROVED FOR Charles Myers BUILDING PERMITTING PURPOSES 12 I BY MIAMI-DAD State of Florida E COUNTY FIRE DEPARTMENT Registration # T FIRE PROTECTION CONTRACTOR'S AR0014546 804 WOR!<ING PLAN AS PER NFPA 13 5 SHALL BE SUBMITTED FOR APPROVAL OE TO MIAMI-DADE FIRE DEPARTMENT 806 BEFORE INSTALLED ROREMODELED REMODELED N.I.C. ry DATE BY�� � \ \\ % I I INTERVAL '� _ �� _ _ _ _ _ �� _ 805 VENTILATION EQUIPMENT SCHEDULE _ N.I.C. INTERNATIONAL MARK MAKE MODEL TYPE CFM TIP SP RPM HP V/PH DRIVE SPEED IN. 8th Floor E-1 GREENHECK G-95—D I CENTRIF, PRV 1 510 3755 1 3/8 1 1319 1/8 1 120/1 DIRECT N❑TESI 6262 Sunset Drive 807 1. FAN INSTALLED ON THE EXTERI❑R OF THE BUILDING SHALL BE CONSTRUCTED AND INSTALLED Miami, F1 33143 N.iC TO WITHSTAND A WIND PRESSURE OF 60 PSF FROM ANY DIRECTI❑N. 2. FAN SHALL HAVE MOTOR PR❑TECTI❑N, SINGLE PHASE FAN MOTOR SHALL HAVE INHERENT PROTECTION. C3 ) 3. FAN SHALL HAVE UL APPROVED L❑CAL DISCONNECT MEANS, 4 ) 4 J _�/ 4. ROOF MOUNTED FAN SHALL HAVE 12' HIGH (ABOVE ROOF SURFACE), ALUMINUM, PRE– Owner: Jeff Weiss FABRICATED CURB WITH LINER, DAMPER TRAY AND SEAL. 433 Plaza Real, Suite 275 8 I+� FLOOR PARTIAL FLOOR PLAN 5. ROOF FAN SHALL HAVE B IRDSCREEN, Boca Raton, FL 33432 6. POWER ROOF VENTILAT❑R AND BASE SHALL BE OF ALUMINUM C❑NSTRUCTI❑N. N SCALE: 1/4"=1'-0" 7. E-1 SHALL BE ELECTRICALLY INTERLOCKED TO OPERATE WITH RELOCATED AHU, Contact: Jeff Weiss, (561) 416-4600 8. E-1 SHALL BE COMPLETE WITH GRAVITY SHUTTER, 9. COORDINATE EXACT L❑CATION OF INSTALLATION WITH OTHER EXISTING ROOF MOUNTED EQUIPMENT AND UTILITIES WHICH ARE TO REMAIN, Date: 03-20-01 10. SEE GENERAL NOTE RELATED TO CUTTING OF SLAB, Project No: 2013.00 11. FAN SHALL BE COMPLETE WITH SPEED CONTROLLER INSTALLED AT FAN FOR BALANCING PURPOSES ONLY. Drawn By: SJB Checked By: JEA /AxB AIR VOLUME H VA C DESIGN REQUIREMENTS CADD File 00-55\MECHANICAL.DWG (A+C)x6 - / EXTRACTOR BRANCH DUCT OR SIDEWALL OUTLET COLLAR HVAC DESIGN REQUIRES, YES NO Title: MVD DUCT SMOKE DETECTOR X AIR FLOW FIRE DAMPERS X MECHANICAL SMOKE DAMPERS X 4 -_ - MVD FIRE RATED ENCLOSURE X _ DXB _ j � ! (� {�S�►� -- _ __- -_ DISTRIBUTION DUCT FIRE RATED ROOF/FLOOR X ' SCQIE: AS INDICATE-O - CxB CEILING ASSEMBLY I �I`�I 98OacR # FIRE STOPPING X f w CERTIFICATE OF^AUTHORIZATION 1438 Sheet NO.: ' 'i = NDERSON SMOKE CONTROL X -�`'�' ILLIAM ;Oi�1SUlTINS EN6INEER5 I�IO.a 117 MAJORCA AVE.-COMAE GAB'LIES, FLORIDA.33_134 TYPICAL DUCT TEE DETAIL TYPICAL DUCT TAKEOFF DETAIL ,- TELEPHONE (305) 442-15033 NTS NTS AWCE-JOB#: 00-55 _ ^ - - _ Sheet liuril36f ..2 _ of: 3