Loading...
01-0597-017 0 _ I I I I I I ( A I I ," - ------ --------------- DRAWING REFERENCE NOTES \ Ol REMOVE EXISTING EXHAUST AIR REGISTER COMPLETELY INCLUDING RELATED EXHAUST AIR DUCTWORK, OREMOVE EXISTING EXHAUST AIR DUCTWORK IN WORK AREA, CAP DUCT AT WALL PENETRATION. • EXISING FIRE SPRINKLER HEADS SHALL BE REMOVED AND REPLACED International WITH NEW HEADS AT NEW LOCATIONS AS SHOWN ON SHEET M-2, C(7- EXISTING AIR HANDLING UNIT SHALL BE RELOCATED ALONG WITH ALL Desi n Partnershi C° ) � I O OF ITS PIPING WIRING AND CONTROL C❑NNECTI❑NS AND AUXILIARY I I I DRAIN PAN, SEE SHEET M-2, REMOVE ALL ASSOCIATED SUPPLY AIR AND RETURN AIR DUCTWORK ( UNLESS OTHERWISE INDICATED) , INLETS Incorporated AND OUTLETS, DISCONNECT EXISTING OUTSIDE AIR DUCT CONNECTI❑N FOR RECONNECTION AFTER UNIT IS RELOCATED, 30 W. Mashta Drive OEXISTING CONTROL THERMOSTAT SHALL BE RELOCATED AS SHOWN ON Key Biscayne, Fl 33149 SHEET M-2, Tel: 305.365.8338/Fax: 305.365.8339 FLEXIBLE SUPPLY AIR DUCT FOR ADJACENT SPACE BEYOND THE WORK ' I AREA SHALL REMAIN FOR RECONNECTION TO THE NEW SUPPLY AIR DISTRIBUTION SYSTEM, SEE SHEET M-2. No. Issue Date I I I � x C - — - -- - - - - - - ------- - - - - - - - ----------------- - - - - - - - - QB � I o o to 0 0 l 3 GENERAL NOTES I I 1. COORDINATE NEW DUCTWORK AND NEW AND RELOCATED EQUIPMENT WITH LIGHTING, PLUMBING, STRUCTURAL SYSTEMS AND CEILING SYSTEMS. 2. DUCT ACCESS PANELS ADEQUATE FOR SERVICE SHALL BE PROVIDED AT ALL DAMPERS AND CONTROLS, --� 3. CONTRACTOR SHALL COORDINATE LOCATION AND SIZE OF ALL I' �1 2 I j PENETRATIONS THROUGH ROOF, WALLS, CEILING AND FLOOR WITH OTHER TRADES, CLIENT APPROVAL L — I 4. ALL DUCT SIZES SHOWN ARE ACTUAL AIR PATH SIZES, I have reviewed these plans and have been 5. ALL ELECTRICAL CONTROL ITEMS MOUNTED OUTSIDE SHALL BE given the opportunity to ask questions about I I WEATHERPROOF, them prior to issue. These plans conform 4 to our requirements. I understand that any 6. CEILING ACCESS PANELS SHALL BE PROVIDED FOR EQUIPMENT, modifications to these plans will be an (C"0 �) I I F_ — � I DAMPERS AND CONTROLS INSTALLED ABOVE OTHERWISE NON— additional service with potential impact on 1 oci) 1 I 3 1 I 3 I ACCESSIBLE CEILINGS, ACCESS PANELS SHALL NOT BE LESS construction cost and scheduling. I ' I THAN 20' X 20' . E] ACCEPTED AS IS 1 I I AHU J i I 7. MOUNT ROOM THERMOSTAT 5 FEET ABOVE FLOOR, El ACCEPTED AS NOTED — — I 81 ALL EQUIPMENT LOCATED OUTSIDE SHALL BE CONSTRUCTED AND INSTALLED TO WITHSTAND A WIND PRESSURE OF 60 POUNDS PER signature: Date: 6 I SQUARE FOOT FROM ANY DIRECTI❑N, I 9. DUCTWORK PENETRATI❑NS OF ROOF AND WALLS SHALL BE SEALED r 5 I AIR AND WATER TIGHT. — — — — — — — — — — 10. NO EQUIPMENT OR MATERIALS SHALL BE PURCHASED OR � � — �o \ � All drawings and written material herein, as instruments —I INSTALLED PRIOR❑R TO FINAL APPROVAL ❑F SHOP DRAWINGS, of service, shall remain the property of International 11. EXISTING EQUIPMENT, PIPING, DUCTWORK, OUTLETS, Design Partnership, Inc. (I P) and shall not be reproduced �\ L�'' L L — — CONTROLS, ETC, WHERE S❑ NOTED SHALL BE REMOVED OR or copied, in whole or in part, without the expressed ( ---- - - _ - — L y -------_-------_--- - - - - - - REL❑GATED AS PART ❑F THIS CONTRACT, written consent of IDP and may not on used or �z referenced for an other project. Information contained 12, THE CONTRACTOR SHALL PR❑VIDE A SET OF PRINTS CLEARLY herein represents proprietary information of International I� _ I 3 MARKED TO SHOW AS—BUILT CONDITIONS AT THE COMPLETION OF Design Partnership and/or its Client and shall not be I �� �\ I CONSTRUCT I❑N, disclosed to others. Those who use these documents IL J� I L _ 13. FLOOR AND ROOF SLABS ARE POST TENSIONED STRUCTURES, do so in confidence. _ — — — — — — — �— ]Z — STEEL REINFORCING SHALL BE LOCATED AND CAREFULLY AVOIDED WHEN CUTTING NEW OPENINGS. F-1 _ °� I 3 14. THE CONTRACT AREA IS NOW FULLY PROTECTED WITH FIRE Architect of Record: II j o 1� I I ( ) I ,`. SPRINKLERS, THE HEAD L❑CAT I❑NS SHALL BE ADJUSTED AS Charles Myers ILJ-` I L L — — — INDICATED TO SUIT THE NEW PARTITI❑N AND CEILING LAYOUT, I 1 1 ALL NEW HEADS SHALL BE OF THE FULLY CONCEALED TYPE, State of Florida Registration # or 1 II k` �j� 3 AR0014546 lL J_ I L \ / z YX x LEGEND INTERVAL AHU AIR HANDLING UNIT Ol DRAWING REFERENCE NOTE C �, CENTRIF, CENT CFM CUBIC FEET PER MINUTE RIFUGALFRIGERATI❑N INSTITUTE DIAMETER x I 1Z INTERNATIONAL CLG. CEILING QT THERMOSTAT, ROOM CONN. CONNECT, CONNECTION DN DOWN FLEXIBLE DUCT 8th Floor DWG DRAWING Z NEW DUCTWORK 6262 Sunset Drive EA. EACH EXISTING DUCTWORK FLA FULL LOAD AMPS' Z AND PIPING Miami, F1 33143 HP HORSEPOWER IN. INCHES r-- MANUAL VOLUME DAMPER MVD MANUAL VOLUME DAMPER O CONCEALED FIRE SPRINKLER HEAD NTS NOT TO SCALE Owner: Jeff Weiss \ PRV POWER ROOF VENTILATOR 433 Plaza Real, Suite 275 PSF POUNDS PER SQUARE FOOT Boca Raton, FL 33432 PSI POUNDS PER SQUARE INCH RPM" REV❑LUTI❑NS PER MINUTE Contact: Jeff Weiss, (561) 416-4600 63, 4 4-.5 5 S. F. SQUARE FEET SP STATIC PRESSURE 8th FLOOR PARTIAL FLOOR PLAN TYP, TYPICAL N V/PH VOLTAGE/PHASE Date: 03-20-01 (DEMOLITION) 1/4`=1'-0`SCALE; 1/4`=1�—� WC WATER CLOSET DrawntBy• S B3.00 Checked By: i JEA CADD File 00-55\MECHANICAL.DWG Title: JOHN! DERSON - ----- _ _-- _ -- _MECHANICAL F r E1 $90 , --- _ __: _ _ _ -^- _SCALD: AO IND?CATE0 CERTIFICATE OF AUTHORIZATION #1438 A A Sheet NO.: NDERSON ILLIAMS- CONSULTING ELIGtNEEPS-_INC. - / 117 MAJORCA AVE:S6RAh:GABLE, FL01?IDA 331.34 TELEPHONE (305) 442-8033 AWCE JOB#: 00-55 Sheet Numbs? i - of: 3