01-0412-024
D NOTES O o I. ALL SWITCHES AND COVERPLATE5 FOR DEVICES CONNECTED TO THE a EMERGENCY SYSTEM SHALL BE RED IN COLOR TYPICAL THROUGHOUT e THIS PROJECT. 2. CONTRACTOR SHALL INSTALL A GREEN EQUIPMENT GROUNDING WIRE M ALL CONDUITS AND SHALL BOND THE GROUND WIRE TO AL ELECTRICALLY WIRED EQUIPMENT. BONDING SHALL BE IN ACCORDANCE WITH THE N.E.C. REQUIREMENTS. GROUND WIRES SHALL BE S►ZED IN ACCORDANCE WITH TABLE 250-95 OF THE 00 N.E.G. a 0 3. ALL CONDUIT USED TO SUPPLY LIGHTS, WIRING DEVICES, HVAG EQUIPMENT, OR ANY OTHER LINE VOLTAGE EQUIPMENT IN PATIENT o CARE AREAS M THI5 FACILITY SHALL BE STEEL CONDUIT. ° ® 0 CONDUIT MAY BE RIGID GALVANIZED STEEL OR ELECTRICAL METALLIC TUBING INSTALLED IN ACCORDANCE WITH THE SPECIFICATIONS. 4. ALL ESSENTIAL ELECTRICAL SYSTEM WIRING FOR THE LIFE SAFETY CH, CRITICAL BRANCH, AN F'McTit BRANCH SHALL BE --- ----- ----- --- - - --- -- - -- GALVANIZED -- - ---- INSTALLED IN ELECTRICAL METALLIC TUBING OR RIGID G STEEL CONDUITS. TYPICAL THROUGHOUT THI5 PROJECT. 5. CONTRACTOR SHALL REFER TO THE ARCHITECTURAL REFLECTED ®® CEILING PLANS FOR EXACT LOCATIONS OF ALL CEILING MOUNTED EQUIPMENT. 6. ALL DEVICES, COVERPLATE5 AND EQUIPMENT IN THE PATIENT A ---- -- ACCESSIBLE AREAS SHALL BE EQUIPPED WITH TAMPER PROOF EG2-4 I I EC2-4 EG3-2 SCREWS. TYPICAL THROUGHOUT THIS PROJECT. Q Q -- -- - - - 1 EG3-2 l. PATIENT BED-LIGHT EQUIPPED WITH PUSH BUTTON FOR BED TASK LIGHTING. SWITCH AT ROOM ENTRANCE TO CONTROL UP LIGHT ONLY ON LIGHTS INDICATED WITHIN RESPECTIVE ROOM. -- - - -- -- G G - - - -- --- _ - G BED-LIGHTS SHALL BE SECURELY FASTENED TO THE WALL ' G STRUCTURE (METAL STUD WORK). AN ANCHOR SYSTEM FOR © Q ATTACHING THE FIXTURE TO THE DRYWALL IS NOT ACCEPTABLE. -- -- ANY DAMAGE TO THE WALL DURING INSTALLATION SHALL BE - REPAIRED BY THE CONTRACTOR TYPICAL. -- EC2-4 EC? 4 EG3-2 8 8. PATIENT NIGHT-LIGHT EQUIPPED WITH PUSH BUTTON FOR ON-OFF �. ACTIVATION. SECURE FIXTURE TO WALL STRUCTURE AS EC3-2 DESCRIBED IN NOTE 'l, ABOVE. TYPICAL. �---m NL --- ----, - - 9. FLUSH RECESSED LIGHT WITHIN NEW DRYWALL CEILING. FIXTURE 8 8 8 SHALL BE SECURELY FASTENED TO THE BUILDING STRUCTURE. G -- - -G G - -- -- - TYPICAL. EC2-4 EC2-4 11 EC3-2 A3-1 10-RUN NEW WIR(NCs AND CONDUIT DOWN TO CONVENIENCE OUTLET NL NL 11 NL H WITHIN THIS ROOM. 11. REUSE EXISTING CIRCUITS AT DEVICE OR FIXTURE LOCATION. - -_-._._ ;P_ - _--_--- ------ -- ------- -------- _ FOR ALL CIRCUITS INDICATED WITHIN THE PATIENT tt - - . - -- ------ ------ ROOMS. TYPICAL T - ---- - _ - -- _