01-0386-019 DATE REVISIONS W.
FAN SCHE DUl_E HOOD &CHE IDUL_ E
MANUFACTURER ELECT. SERVICE DIMENSIONS WEIGHT MANUFACTURER
FAN AND MODEL NO, RPM HP CFM S" S.P. VOLTS/PH/Hz WxLxH (IN.) LBS. REMARKS LENGTH W H(IN) XAHUST/COLLAR SUPPLY/COLLAR REMARKS
EXIST. BROAN 696 AND MODEL NO. -
EF 01,2 43 1500 1/80 10061/8" 115/1/60 10x10x6 10 /GRILLE , 4"� S/M DUCT, DAMPER SAV ON AIR SU1E UL LISTED STANLESS STEEL HOOD
EXIS i. 4 ROOF CAP KIT HOO 108" 46" 24" 2340 CFM /12"X16" 1800 CFM,/ 38"XS"
UJ/ANSUL F.P. SYSTEM,LIGHT 4 FILTER '
GREENHECK CUBE 161 W/VENTED 4 HINGED ROOF CURB,
EF 04 1200 3/4 234063/4" 208-230/1/60 29DIAX25H 21 5IRD5CREEN. MOTOR 5TARTER4DISC,
LMDG - QD UL162 LISTED •
BF 05 GREENHECK RSF 100 LMDX 780 3/4 180063/8" " 41X4IX25 ___ UJ/ROOF CURB, DUCT ADAPTOR M,
STARTER 4 DISCON.
HOOD NOTES:
I. INSTALLATION SHALL COMPLY W-NFPA S6/LOCAL CODES.
2, 1400D SHALL BE 18 GAGE STAINLESS STEEL (TYPE 304). ALL SEAMS AND JOINTS SHALL BE
LIQUID TIGHT CONTINUOUS EXTERNAL WELD.
3. A. EXHAUST DUCTWORK SHALL BE 16C CARBON STEEL ALL WELDED CONSTRUCTION.
B. SUPPLY DUCTWORK SHALL BE 22C GALVANIZED STEEL.
4. HOOD SHALL HAVE: A WET CHEMICAL FIRE PROTECTION SYSTEM NOZZLES EXPLOSION PROOF
LIGHT, STEEL MESH GREASE FILTERS, GREASE DRIP TRAY DRAINING TO 22 GAGE STAINLESS STEEL
GREASE RECEPTACLE.
10' MIN. EXH. HOOD FAN EXHAUST FAN NOTE:
FILTERED
SUPPLY FAN 16 GAUGE WELDED STEEL FAN 814ALL BE MOUNTED ON NON-COMBUSTIBLE ROOF CURB ACCORDING TO NFPA-96. DISCHARGE
GREASE EXH. DUCT OF FAN SHALL BE 40" MIN. FROM ROOF SURFACE AND 10' MIN. HORIZONTALLY FROM ANY FRESH AIR
16 GAUGE WELDED STEEL INTAKE OR THE SUPPLY FAN. FIRE MODE REQUIRES EXHAUST FAN t0 BE ON WHENEVER THE
12" CURB GREASE EXH. DUCT METAL STUDS EXTINGUISHING SYSTEM IS ACTIVATED.
MIN.(TYP) STEEL 42"
MIN PREF. ROOF CURB MANUF. 5/8" GYPSUM BOARD TYPE X
ROOF JOIST 7 BY GREENHECK
n VENTED [21 GAUGE GALV. OR STAINLESS STEEL PLATE SUPPLY FAN NOTE:
METAL STUDS FAN SHALL BE MOUNTED ON ROOF CURB 10" MIN. FROM EXHAUST FAN OR PLUMBING VENT. S. FAN
n/ "n/ SHALL BE ELECTRICALLY INTERLOCKED WITH EXHAUST FAN AND WITH HOOD FIRE SUPPRESSION SYSTEM
5/8" GYPSUM BOARD TYPE X TO BE "OFF" IN CASE OF FIRE,
n n
n n 6..
22 GAUGE GALV. OR STAINLESS STEEL PLATE
Hnd n
F.D. n 6" AIR SPACE Ell KITCHEN VENTILATION NOTES:
I. THE KITCHEN VENTILATION SYSTEM HAS BEEN DESIGNED WITH THE INTENT TO MANTAIN A
CEILING TILE o n NEGATIVE PRESSURE, NEVER OVER .02" W.C. RELATIVE TO ALL INDOOR SPACES SURROUNDING
THE KITCHEN SPACE, DURING COOKING HOURS, COMPLYING WITH "THE FLORIDA ENERGY
lo
24, n ANSUL SYSTEM FZPKNOZZLE EFFICIENCY CODE" SECTION 303.1 (A).
lz�_UL. APPROVED
INCAND. VAPOR n WASHABLE REMOVABLE 2. ALL EXHAUST AND MAKE UP AIR SYSTEM COMPONENTS (FANS, DAMPERS, ETC-) SHALL BE
PROOF LIGHH 45' n NON-COMBUSTIBLE ALUMINIUM INTERLOCKED IN SUCH A WAY THAT THE BALANCE PRESCRIBED IN (1) ABOVE IS MAINTAINED
FILTERS (UL. APPROVED) THROUGHOUT ALL COOKING HOURS, AND ALL VARIATIONS OF COOKING OPERATIONS. PROVIDE
PILOT LIGHT IN KITCHEN AREA INTERLOCKED TO SUPPLY 4 EXHAUST FANS.
Tr REMOVABLE GREASE RECEPT. 1 HR FIRE RATED ENCLOSURE
ADJUSTABLE VANE 2�� n LESS THAN I GAL. CAPACITY NTS / a. SUPPLY AND EXHAUST FANS ARE INTERLOCKED WITH PILOT LIGHT IN KITCHEN AREA,
SUPPLY AIR DIFF, no / b. FIRE MODE REQUIRES EXHAUST FAN CONTINUES TO OPERATE AND SUPPLY FAN STOPS.
/c. HOOD EXHAUST FANS SHALL OPERATE WHENEVER THE EXTINGUISHING SYSTEM IS
ACTIVATED.
41-C 11 n TENANT PREPARATION J d. FIXED PIPE EXTINGUISHING SYSTEMS IN A SINGLE HAZARD AREA SHALL BE ARRANGED FOR ol
n PROTECTION OVERLAP SIMULTANEOUS AUTOMATIC OPERATION UPON ACTIVATION OF ANYONE OF THE SYSTEMS.
THE HOOD WITH THE
6" n PROTECTION BY 18"
EACH SIDE ALL THE
'-0 AX. n 6
WAY DOWN " BELOW
6" n COOKING SURFACE i
(ALL AROUND)
n PARTITION
"
PULLEY ELBOW-TYPICAL
1/2" DIAMETER
DETECTION CABLE
CONDUIT
SERIES DETECTOR W/
360 DEC. F FUSIBLE LINK
DUCT NOZZLE SP-2
3/8" DIAMETER
KITCHEN HOOD I / AGENT PIPING
SYSTEM DETAIL, t0 MECHANICAL ._
N.T.S. GAS VALVE
i
I APPLIANCE NOZZLE SW TERMIMINAL DETECTOR
I W/ 360 DEC. F Drawings and Specifications as instrument of service are and shall remain the
FUSIBLE LINK property of the Architect and shall remain the property of the Architect wheth
the project for which they were made is executed or not.They are not to be ue
in any manner on other projects or extensions to this project except by agrees
in writing and with the appropriate compensation to the Amhitec t.Reproducti
U REMOTE of drawings and ifica6ons without the written consent of the Architect is
PULL STATION I � �
I prolubited.
u EXPELLAN
2 -011 / PIPING
CAPTURE HOOD 101 PLENUM NOZZLE
AREA, OVER ITEM 0
O
FLYER 3/8" APPLIANCE.NOZZLE 5W _ .'®•
9'-0" CAPTURE AREA. '��+�
3 GALLON ASNSULEX
TANK W/WALL BRACKET
i
JOHN R MEDINA&ASSOCIATES,Architects,
PLENUM NOZZLE i ofce(305)740 05554 %F5)7405355
I OVER ITEM O
�— 22 GAUGE GALV. OR STAINLESS 0 f�ANGEfz,It FLORIDACERTRrICAT ION NUMBER.RA14867
MIN. STEEL PLATE CERTIFICATE OF CORPORATE AUTHORIZATION AA00026'
"
BREAD GALLERY REMODELATION.
' li PLENUM NOZZLE "
31" MAX, 17" MIN E, "
70 COOKING SURFACE. 5784 SUNSET DRIVE
„ ,MECHANICAL AUTOMAN SOUTH MIAMI FLORIDA
6 MIN. REMOTE PULL STATION W/ LT-30-R CARTRIDGE OVER ITEM 02 y
60" AFF.(MAXIMUM) CHARBROILER
CONTACT:CESAR&LUISA RINCON`'(305)663-1179
COOKING EQUIP.
JOB /: XXXXX '
REFER t0 M-1 SHEET FOR MOUNTING ANSUL R-102 HOOD FIRE SUPPRESION GUERRERO/GONZALE2
LOCATION OF ANSULEX TANK AUTOMAN
AND REMOTE PULL STATION. 5Y5TEM PIPING ISOMETRIC ENGINEERS, INC.
NTS Michael C. Guerrero, P.E.
Mechonkal Eng. tk. 115235
Rafael L Conza4z, RE
Electrleal Enq. Lk. /11057
4300 S.W. 73rd Avenue, Suite f 107
Miami, Florida 33155
Td. (305) 262-3941, Fax (305) 262-8211
E—mail: GGENGQACCESSPRO."ET
HOOD ELEVATION ---
NTS GUERfj
.�\eA i F s,z° FLOOR PLAN l
V:•�, ����` �, w SCALE: AS SHOWN
DATE: FEB.'01
M 2
DRAWN: DHB