F I R E P R 0 T E C T 1 0 N N 0 T E S
1. ALL WORK SHALL CONFORM WITH THE SOUTH FLORIDA BUILDING CODE, NFPA, NEC, AND 18. THE DESIGN OF THE SYSTEM AND SPACING OF THE SPRINKLER HEADS SHALL CONFORM
ALL OTHER APPLICABLE FEDERAL, STATE AND LOCAL REGULATIONS AND ORDINANCES. TO THE FOLLOWING:
2. CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS, FEES, TAXES, INSPECTIONS, RESTAURANT SEATING AREA: Q
TESTS, PERFORMANCE BONDS, FINES AND OTHER ITEMS AS REQUIRED FOR THE LIGHT HAZARD OCCUPANCY CLASSIFICATION.
INSTALLATION OF THE COMPLETE FIRE PROTECTION SYSTEMS, AND SHALL BE DENSITY OF APPLICATION: 0.10 GPM/SF.
RESPONSIBLE FOR OBTAINING HIS OWN PERMIT. MOST HYDRAULICALLY REMOTE AREA: 1,500 SF.
MAXIMUM SPRINKLER COVERAGE: 225 SF. (�
3. CONTRACTOR SHALL PROVIDE ALL REQUIRED INSURANCE FOR PROTECTION AGAINST HOSE ALLOWANCE: 100 GPM. W
PUBLIC LIABILITY AND PROPERTY DAMAGE FOR THE DURATION OF THE WORK. O
4. EXCEPT WHERE LONGER WARRANTIES ARE SPECIFIED FOR SPECIFIC EQUIPMENT, RESTAURANT SERVICE AREA: I E
CONTRACTOR SHALL WARRANT ALL WORK TO BE FREE OF DEFECTS IN WORKMANSHIP ORDINARY HAZARD GROUP 1 OCCUPANCY CLASSIFICATION. U (D 0
AND MATERIALS FOR A PERIOD OF ONE YEAR AFTER FINAL WRITTEN ACCEPTANCE OF c0 v
DENSITY OF APPLICATION: 0.15 GPM/SF. LU L
THE PROJECT BY THE OWNER. -+-� Lz
MOST HYDRAULICALLY REMOTE AREA: 1 ,500 SF. U) D n LO
MAXIMUM SPRINKLER COVERAGE: 130 SF. cf) O 00
5. PROVIDE ALL NECESSARY INSTRUCTIONS TO THE OWNER IN THE OPERATION OF THE U) U Q '� 0
MECHANICAL SYSTEMS BEFORE FINAL ACCEPTANCE. HOSE ALLOWANCE: 100 GPM. Q > 0, Q
Fr ° I�
6. PROVIDE EQUIPMENT MAINTENANCE AND INSTRUCTION MANUALS. 19. SPRINKLER HEADS IN AREAS WITH FINISHED CEILINGS SHALL BE FLUSH CONCEALED LL_
TYPE VIKING SILHOUETTE MODEL A-1 QUICK RESPONSE (OR APPROVED EQUAL). Lo 00 o-
7. SUBMIT SHOP DRAWINGS AND HYDRAULIC CALCULATIONS TO THE ENGINEER FOR z Q � 0
APPROVAL OF ALL EQUIPMENT, MATERIALS, LAYOUTS AND CALCULATIONS PRIOR TO ORIFICE SIZE ?' , 155 DEGREE F TEMPERATURE CLASSIFICATION, UNLESS INDICATED .- � � 0 0
OTHERWISE OR NEAR THE KITCHEN VENTILATOR. COVER PLATE COLOR TO BE
COMMENCEMENT OF WORK. OBTAIN APPROVAL OF THE AUTHORITIES HAVING
JURISDICTION BEFORE COMMENCING ANY WORK. PREPARE HYDRAULIC CALCULATIONS. SELECTED BY OWNER. WHERE CEILING TILES ARE PROVIDED, THE SPRINKLER HEAD
SHALL BE LOCATED IN THE CENTER OF THE TILES (UNLESS INDICATED OTHERWISE ON � Duo o �., �
8. ALL CONTROL WIRING IS INCLUDED UNDER THE ELECTRICAL WORK. WIRING SHALL BE THE DRAWINGS). O U `n cn o I
,�
AS PER THE ELECTRICAL SPECIFICATIONS. FIRE PROTECTION SUB-CONTRACTOR TO 0 LU
FURNISH ALL FLOW SWITCHES, TAMPER SWITCHES, ETC. 20. SPRINKLER HEADS IN AREAS WITHOUT CEILINGS SHALL BE PENDENT TYPE, VIKING U J
LU
MICROFAST MODEL M QUICK RESPONSE (OR APPROVED EQUAL). ORIFICE SIZE ?", 155 �-
9. PROVIDE ALL NECESSARY OFFSETS IN PIPING TO CLEAR BUILDING STRUCTURE, DEGREE F TEMPERATURE CLASSIFICATION, UNLESS INDICATED OTHERWISE. NATURAL U
DUCTWORK, LIGHT FIXTURES, DIFFUSERS, ETC. AS SHOWN ON THE DRAWINGS AND AS BRASS FINISH. PROVIDE FREEZE PROOF SPRINKLER DROPS FOR THE FREEZER W
REQUIRED BY FIELD CONDITIONS. PROVIDE PIPE DRAINS AT LOW POINTS AS REQUIRED. ENCLOSURES. Q
10. PROVIDE ALL NEW MATERIALS OF AMERICAN MANUFACTURE, BEARING THE U.L. LABEL 21. SPRINKLER HEADS FOR SIDEWALL APPLICATIONS SHALL BE CHROME PLATED STANDARD _
AS APPLICABLE. PROVIDE SUPPLEMENTAL MATERIALS NOT SPECIFICALLY NOTED OR EXTENDED COVERAGE, DEPENDING ON THE APPLICATION. PROVIDE HEAT U
HEREIN, BUT REQUIRED TO COMPLETE THE INSTALLATION IN ACCORDANCE WITH THE REFLECTORS AND/OR GUARDS AS REQUIRED. VIKING MICROFAST QUICK RESPONSE
INTENT OF THE CONTRACT DRAWINGS, AT NO ADDITIONAL COST TO THE OWNER. SIDEWALL SPRINKLERS (OR APPROVED EQUAL).
11. FURNISH ALL NECESSARY ACCESS PANELS TO CONTROL VALVES, ETC., TO THE 22. ALL VALVES SHALL BE UL AND FM APPROVED. SHUT-OFF VALVES, CHECK VALVES, ETC.,
GENERAL CONTRACTOR, FOR INSTALLATION UNDER THE GENERAL TRADES. SHALL BE MANUFACTURED BY CRANE, STOCKHAM, KENNEDY, MUELLER, OR APPROVED
EQUAL.
12. ALL WORK SHALL BE FIELD CHECKED BEFORE INSTALLATION AND COORDINATED WITH
ALL OTHER TRADES. THE CONTRACT DRAWINGS ARE DIAGRAMMATIC AND INTENDED TO 23. PROVIDE ADJUSTABLE RETARDING FLOW SWITCHES, CHECK VALVES, FLOW
DEPICT APPROXIMATE EQUIPMENT LOCATIONS AND ARRANGEMENTS, NOT TO SHOW INDICATORS, ETC., FOR ALL SPRINKLER CONNECTIONS TO THE SPRINKLER RISERS
ANY MINOR DETAILS. PLANS SHALL NOT BE SCALED: OBTAIN DIMENSIONS AT THE SITE. (EXISTING STANDPIPES).
THE ACCURACY AND/OR VERACITY OF THE BUILDING BACKGROUND SHOWN ON
DRAWINGS IS NOT GUARANTEED: ACTUAL CONDITIONS MAY DIFFER FROM THOSE 24. ALL SPRINKLER SHUT-OFF VALVES, INCLUDING FLOW SWITCHES, SHALL BE SUPERVISED
SHOWN ON PLANS. BY THE FIRE ALARM SYSTEM AND PROVIDED WITH TAMPER SWITCHES AS APPLICABLE
WIRING IS INCLUDED UNDER THE ELECTRICAL WORK: COORDINATE WITH THE
13. PROVIDE A FULL COVERAGE WET PIPE FIRE SPRINKLER SYSTEM IN ACCORDANCE WITH ELECTRICAL TRADE.
ALL APPLICABLE NFPA STANDARDS AND SPECIFICALLY WITH STANDARDS No. 10, 13, 14,
20, 24 AND 101, STATE/LOCAL CODES, LOCAL REGULATIONS AND ORDINANCES, AND THE 25. FIRE EXTINGUISHERS AND EXTINGUISHER CABINETS ARE INCLUDED UNDER THE -j >=
OWNER'S INSURANCE UNDERWRITER. ALL SPRINKLER SHALL BE THE QUICK RESPONSE GENERAL TRADE SECTIONS OF THE SPECIFICATIONS. _j I- = o
2
TYPE. PROVIDE RESIDENTIAL TYPE SPRINKLER WHERE APPLICABLE AND IN � Z = 0
ACCORDANCE WITH THE HYDRAULIC CALCULATIONS. PROVIDE SPARE SPRINKLERS IN 26 THE WORK UNDER THIS CONTRACT DOES NOT INCLUDE UNDERGROUND PIPING, Q o
WALL MOUNTED BOX PER NFPA-13. BACKFLOW PREVENTERS, POST INDICATOR VALVE, SIAMESE CONNECTIONS, w L_ Q
STANDPIPES (SPRINKLER RISERS), HOSE VALVES, ROOF MANIFOLDS, OR SPRINKLER x
14. FIRE SPRINKLER CONTRACTOR SHALL VERIFY ALL SPACE CONDITIONS AND DIMENSIONS PIPING FOR THE THIRD FLOOR, WHICH IS INCLUDED UNDER THE BASE BUILDING W 0 Q
AT JOB SITE PRIOR TO FABRICATION AND INSTALLATION OF MATERIALS AND CONSTRUCTION CONTRACT. U < Ld
EQUIPMENT. Q
15. COORDINATE WORK WITH OTHER TRADES. o� ~00 0
16. CONTRACTOR SHALL SIZE AND INSTALL ALL PIPING AS REQUIRED AND IN ACCORDANCE [ `f r , • 0-)L
In
WITH NFPA STDS. 13 AND 24. ALL WORK AND TESTING SHALL CONFORM WITH NFPA `r
STDS 13 AND 24. NOTE: THE WORK UNDER THIS CONTRACT
CONSISTS ON MODIFYING THE EXISTING
17. ABOVE GROUND PIPING SHALL BE BLACK STEEL OR GALVANIZED, SCHEDULE 40 OR THIN SPRINKLER SYSTEM LAYOUTS FOR THE
WALL AS APPROVED BY THE AUTHORITIES HAVING JURISDICTION. PIPING JOINTS MAY GROUND FLOOR AND THE SECOND FLOOR, r✓t ;= ;{t !-.' ' �Ir'{°= f'"',:`; c h. ='.�
BE WELDED OR THREADED; APPROVED MECHANICAL COUPLINGS WILL BE ACCEPTABLE. AND PROVIDING ADDITIONAL WORK AS
1s UN's1,.;. _, ;, _ ;Vp,. r.,,71.. _
ALL MATERIALS AND EQUIPMENT SHALL BE UL LISTED AND FM APPROVED FOR THE REQUIRED IN THESE TWO FLOORS TO
SERVICE INTENDED. CONNECT NEW PIPING TO EXISTING PIPING AS SHOWN ON CONFORM TO THE NEW TENANT
DRAWINGS OR AS REQUIRED BY FIELD CONDITIONS. IMPROVEMENTS UNDER THIS CONTRACT.
UNDERGROUND PIPING, SPRINKLER RISERS,
ETC. ARE EXISTING AND HAVE BEEN PROVIDED
UNDER THE BASE BUILDING CONSTRUCTION
CONTRACT.
DATE: 10.18.00
JOB NO: 001032
d
DWN BY: EZ
CHK BY: JML f
or z:w
A PA REVISION: "