Loading...
09-18-07 Item 11South Miami Mwedeac" CITY OF SOUTH MIAMI 1 I I I I I �� o 27 OFFICE OF THE CITY MANAGER INTER- OFFICE MEMORANDUM 2001 To: The Honorable Mayor Feliu and Members of the City Commission Via: Yvonne S. McKinley, City Manager From: W. Ajibola Balogun, REM, CFEA, Director Public Works & Engineering Department Date: September 18, 2007 Agenda Item No.. Subject: Installation of Emergency Generator at the Gibson - Bethel Community Center Resolution: A RESOLUTION OF= THE MAYOR AND CITY COMMISSION OF THE CITY OF SOUTH MIAMI, FLORIDA, AUTHORIZING THE CITY MANAGER TO EXECUTE A SERVICE WORK ORDER WITH ALL POWER GENERATORS CORP. FOR THE INSTALLATION OF EMERGENCY GENERATOR AT THE GIBSON- BETHEL COMMUNITY CENTER IN AN AMOUNT OF $173,700 AND AUTHORIZING AN ADDITIONAL $16,300 CONTINGENCY FOR UNFORESEEN ISSUES FOR A TOTAL OF $190,000 TO BE CHARGED TO MIAMI -DADE COUNTY OFFICE OF COMMUNITY & ECONOMIC DEVELOPMENT (OCED) ACCOUNT NUMBER 114 - 2020 - 572 -6410 AND ACCOUNT NUMBER 001 - 2100 - 519 -9920; PROVIDING FOR AN EFFECTIVE DATE Request: Authorizing the City Manager to execute Service Work Order with All Power Generators Corp. for the Gibson - Bethel Community Center. Reason /Need: As part of our Fiscal Year 2007 funding from Miami -Dade County Office of Community & Economic Development (OCED), we received $100,000 to install emergency generator at the Gibson - Bethel Community Center. After much review and studies by the following Electrical Contractors, we have decided on installing 275KW diesel generator with 1000 gallon capacity: • All Power Generator Corp. • Benson Electric, Inc. • Generator Power Systems of South Florida, Inc. It is our intent to award the service work order to All Power Generator Corp. by "piggybacking" on their County contract (Bid No.: 8240 - 4/12). Cost: $190,000.00 Funding Source: Miami -Dade County OCED Grant Account No. 114 - 2020 - 572 -6410 will fund $97,500 towards the project, while $92,500 will be funded from account number 001- 2100 -519 -9920. The current account balance for each account is as follows: 114- 2020 -572 -6410 $97,500 0011-21100-1519-9920 $612,900 Page 2 of 2 Comm. Agenda Item No.: Sept. 18, 2007 Backup Documentation: ❑ Proposed Resolution Proposal from All Power Generators Corp. ❑ Copy of Miami-.Dade County Bid & Contract No. 8240 -4/12 Page 2 of 2 RESOLUTION NO.: A RESOLUTION OF THE MAYOR AND CITY COMMISSION OF THE CITY OF SOUTH MIAMI, FLORIDA, AUTHORIZING THE CITY MANAGER TO EXECUTE A SERVICE WORK ORDER WITH ALL POWER GENERATORS CORP. FOR THE INSTALLATION OF EMERGENCY GENERATOR AT THE GIBSON - BETHEL COMMUNITY CENTER IN AN AMOUNT OF $173,700 AND AUTHORIZING AN ADDITIONAL $16,300 CONTINGENCY FOR UNFORESEEN ISSUES FOR A TOTAL OF $190,000 TO BE CHARGED TO MIAMI -DADE COUNTY OFFICE OF COMMUNITY & ECONOMIC DEVELOPMENT (OCED) ACCOUNT NUMBER 114- 2020- 572 -6410 AND ACCOUNT NUMBER 001- 2100 - 519 -9920; PROVIDING FOR AN EFFECTIVE DATE WHEREAS, the Mayor and City commission wishes to provide Emergency Generator at the Gibson - Bethel Community Center, and WHEREAS, the Mayor and City Commission authorize the City Manager to issue a service work order to All Power Generators Corp. for the installation of a 275KW diesel generator at the Gibson - Bethel Community Center in an amount of $190,000. NOW, THEREFORE, BE IT RESOLVED BY THE MAYOR AND CITY COMMISSION OF THE CITY OF SOUTH MIAMI, FLORIDA THAT: Section 1: That the Mayor and City Commission authorize the City Manager to issue a service work order to All Power Generators Corp. for the installation of a 275KW diesel generator at the Gibson - Bethel Community Center in an amount of $190,000. Section 2: That the project's cost shall be charged to OCED Grant Account No. 114- 2020 -572- 6410 and the City matching account number 001 - 2100 -519 -9920 with account balances of $97,500 and $612,900, respectively. Section 3. The attached agreement is made a part of the resolution PASSED AND ADOPTED this ATTEST: CITY CLERK READ AND APPROVED AS TO FORM CITY ATTORNEY Include File Name and Path day of APPROVED: MAYOR COMMISSION VOTE: Mayor Feliu: Vice Mayor Wiscombe: Commissioner Palmer: Commissioner Birts: Commissioner Beckman: Aug. 28, 2007 9 ; 55AM No. 6851 P. 3 ELECTRICAL ACCESSORIES Battery rack and cables Starting battery -- (2)'12 volt - lead acid type Battery charging alternator System battery charger, 24VDC 6 amp, float type GOVERNOR AND ACCESSORIES Electronic /Isochronous governor GENERA'T'OR ACCESSORIES Main line circuit breaker - 3 pole, 500 amps per pole, 80 %° Rated, Installed on generator Voltage regulator +/- 2 % Safeguard breaker CONTROLLER AND ACCESSORIES Kohler DEC 3 +- control console is included with all standard features and accessories Engine fimetions: Battery voltage Coolant Temperature Oil Pressure General Functions: Run Tinge System shutdowns (high water temp, low oil press, over speed, over crank, emergency stop, low coolant level) Systems warnings (pre -high water temp, pre low oil press, low water temp, low Mel. level, not in auto) Generator Functions Generator Amps (LI, L2, L3) +/- 2 °f° Generator frequency 0.5% accuracy Gen.Voltage (line to line, & line to neutral for all phases) +/- 2% Engine Pre -alarm senders to include. Pre -high engine, temperature alarm Pre -low oil pressure alarm Low engine temperature alarm Over voltage protection kit ADDITIONAL ACCESSORIES Vibration isolators - standard between engine /generator and skid base Oil drain extension with valve Skid end caps 1 Set of owners/operators manuals 1 year Kohler Warranty 230ttEOZJD Aug. 28. 2007 9:55AM No. 6851 P. 4 DISTRIBUTOR SITE WORK Engine coil and antifreeze provided at start up service System checkout and start up service after installation is complete System load testing with available facility load Installation L Intercept 1200amp Main Feeder and 125amp Elevator Feeder from utility transformer pad and connect into new 1200 amp and 125 amp service rated outdoor ATS and 250 KW diesel generator with 1000 gallon capacity tank provided by All Power Generators, Corp. 2. Proposal assumes ATS and generator feeders will be installed within 20'of the buildings existing conduit and feeder wire, and the existing feeder conductors are properly sized 3. Electrical connection from the ATS to the generator set for control wiring, jacket heater and battery charging circuit. _ 4. Generator Pad and site prep included 5. Engineering allowance of $8,00.00 included 6. Electrical vault shutdown/ FP &L work with fee allowance of $1800.00 included 7. Permit and Permit Processing fees are excluded. Provided by Customer 8. Patching, painting and restoration of landscaping or finished surfaces by others. 9. Any additional costs for work required by the local building authority or substantial changes in design by the project Professional Engineer, not specified in the above scope of work shall be the responsibility of the owner.(none anticipated) 10. Additions or changes to the above scope of work are billed separate from the initial project agreement. (none anticipated) Combined Scope of work- 1. Install concrete generator maintenance pad adjacent to the existing FP &L transformer on the North property boundary or alternately, in the parking spaces just East of the building in the parking lot outside of the Main Electric Room 2. Coordinate building electrical( shutdown during weekend or night hours 3. Intercept the existing 1200 and 125 amp feeders from the transformer to the main electric room and install the ATSs', specific location to be determined by professional engineering and zoning requirements 4. Place generator on maintenance pad and connect to the ATS 5. Generator sizing is based on demand load history of 143kw provided by City of South Miami with 60 %+ safety and expansion factor 6. Generator is expected to consume 20 gallons per hour during peak usage. Load management will increase the run time to approximately 4 days. 7. Coordination of mechanical systems is essential for proper operation of this system. Time delays on air conditioning or packaged units shall be coordinated to minimize lock rotor current starting. S. Building and Electrical permits are included. Plumbing or Mechanical permits are not normally necessary with type of project and are specifically excluded. 23OREOZJD Aug.28. 2007 9:56AM. No, 6851 P. 5 (2)AUTOMATIC TRANSFER SWITCH 277/480 3oh Service Rated Nema 3f i_ and a 200 277/480 31ph Service Rated Nema 3R PRICE FOR THE ABOVE LISTED ............................... ....................$173,700.00 Price is based on Electricians survey of the site and way change after Engineer work ESTIMATED DELIVERY: ABOVE PRICE IS BASED ON STANDARD LEAD TIME WHICH IS APPROXIMATELY 17 TO 20 WEEKS AFTER RELEASE OF ORDER.. VALIDITY OF PRICE: QUOTATION IS VALID FOR 60 DAYS FROM ABOVE DATE Customer .Acceptance: By approval below, we accept the above bill of material, price and terms and request that the order be released for production. Company Name Approved By (Signature) Approved By (Paint Name) 23OREOZJD 4 Date Title CONTRACT AWARD SHEET MIAMf[aAADE DEPARTwNTOF PROCUREMENT K ANAGENiENT Bid No. 8240 -4/12 Award Sheet Bids and Contracts DIVISION BID NO.: 8240 -4/12 PREVIOUS BID NO.: BPO: ABCW0701073 TITLE: STATIONARY GENERATORS- MAINT/REPAIRS COMMODITY CODE NO.: 285 -39 CURRENT CONTRACT PERIOD: 06/18/2007 through 05/31/2008 Total # of OTRs: 4 MODIFICATION HISTORY Bid No. 8240 -4/12 Award Sheet DPM Notes APPLICABLE ORDINANCES LIVING WAGE: Yes UAP: Yes IG: Yes OTHER APPLICABLE ORDINANCES: CONTRACT AWARD INFORMATION: No Local Preference No Micro Enterprise No Full Federal Funding No Performance Bond No Small Business Enterprise (SBE) NO PTP Funds No Partial Federal Funding Yes Insurance Miscellaneous: REQUISITION NO.: rgpm0700076 PROCUREMENT AGENT: PRUNA BASIA PHONE: 305 375 -5018 FAY: 305 3754407 EMAIL: BPRUNA(aMIAMIDADE.GOV DEPARTMENT OF PROCUREMENT MANAGEMENT Bids and Contracts DIVISION Page 1 of 3 Bid No. 8240 4/12 Award Sheet VENDOR NAME: ALL POWER GENERATORS CORP STREET: 9840 NW 117TH WAY CITY:MEDLEY ST: FL ZIP:33178 FOB—TERMS: DELIVERY: PAYMENT TERMS: NET30 TOLL PHONE: - VENDOR INFORMATION: CERTIFIED VENDOR ASSIGNED MEASURES Local Vendor: No _ SBE No Set Aside No Bid Pref. No Micro Ent. No Selection Factor No Goal No Other: kkkkkk *kkkkkkk * * * * * * * * * * * ** * * * * * * ** *kkk * *kk * ** *kkk *k * *kk Vendor Record Verified? No * *k* *kkk * * * ** Vendor Contacts: Name Phonel Phone2 Fax Email Address DEREK CID 305- 888 -0059 305- 888 -2090 allpwr @bellsouth.net ITEMSA WARDED Section: Details: 8240 -4/12 Attachments: 1. ITB 2. Tally 3. All Power Generator Bid response 4. BPO AWARD INFORMATION Section BCC Award: DPM Award: No BCC Date: 01/01/1900 DPM Date: 05/22/2007 [tract Amount: S 91,427.50 Additional Items Allowed: Agenda Item No.: Special Conditions: DEPARTMENT OF PROCUREMENT MANAGEMENT Bids and Contracts DIVISION Page 2 of 3 Bid No. 82404/12 Award Sheet DeyaiMmAtId 13utlarmocations FR * * * * ** 91,427.50 End of Deyartment Allocations Section DEPARTMENT OF PROCUREMENT MANAGEMENT Bids and Contracts DIVISION Page 3 of 3