01-0144-029 PLAN NOTES y
NOTE: THE SCOPE OF THE PLUMBING WORK (, INSTALL NEW SINK t COMP.AS SPECIFIED.CW t NW SUPPLIES t 2'SAN. < i
NOTE: ON THiS PROJECT 15 THE REPLACEMENT OF 4 `J VENT AIM EXISTING iN PARTITION. SAMUEL C MATTHEWS
SINKS. THE SANITARY STACKS VENTS 4 HOT A R C H I T E C T
ALL SANITARY PiPE 2' m OR SMALLER AND GOLD WATER SUPPLIES ARE EXISTING-r: IN 7�°`�E�7�i8 WORK INCLUDES TidE INSTALLATION OF 4 NEW SIMCS t
SHALL RUN 0 1/4' SLOPE PER LFT. THE PARTITIONS RHERE NEW SINKS ARE O EXISTIWX
THE CONTRACTOR WILL ea RE6IUIRED To OFF SET TINE
3' AND LARGER -0 1/8' SLOPE PER LFT. NOTED. TWO LOCATIONS NOTED REQUIRE LAACEI�1 L%HOT 4 COLD POTABLE WATER SUPPLIES TO ACCOMIDATE AK 0009733
2 SANITARY CONNECTIONS 4 2' OF NEW CASEWORK t SINK LOCATIONS.
EXISTING VENTS 4 NEW 1/2' WATER SUPPLY LINES. SEE 8546 S.W. 175 PLACE
DOME5TIC WATER PIPING STAIR RISER DIAGRAMS. �
M FLORIDA,"
(305) 595.3149
I. UNDERGROUND: GALVANIZED STEEL PIPE, SCHEDULE 40 SCREWED (ASTM w°3
A120-18) WITH MALLEABLE IRON FITTING GALVANIZED TO MATCH
PIPE, ANSI B163-11, ASTM AISI-41 OR CAST IRON FLANGED
FITTINGS (ANSI 516.1). PIPE SHALL BE PROTECTED WITH COAT OF
BITUMINOUS COMPOUND. COPPER TUBING TYPE K ASTM 888-15, ACCEPTED EXISTING
ALTERNATE. ALL COPPER PIPING BLW.GROUND SHALL BE SLEEVED. ELEVATOR
0
2. ABOVE GROUND: GALVANIZED STEEL PIPE, SCHEDULE 40 SCREWED .s
(ASTM A120-18) WITH MALLEABLE IRON FITTINGS GALVANIZED t0 MATCH DATE:
PIPE. ANSI 5163-11, ASTM A191-41 OR CAST IRON FLANGED FITTINGS ❑ 01-20-01 '
(ANSI 816.1). COPPER WATER TUBING, TYPE L, ASTM 888-15 WITH
WROUGHT COPPER FITTINGS, ANSI 81622-13.
REVISIONS:
3. PIPE HANGERS AND SUPPORTS: PROVIDE ADJUSTABLE HANGERS, INSERTS
BRACKETS, ROLLS, CLAMPS AND SUPPLEMENTARY STEEL AS REQUIRED FOR EXISTING
PROPER SUPPORT OF PIPE LINES. HANGERS SHALL ALLOW FOR EXPANSION ELEV.
AND CONTRACTION OF PiPE LiNES AND COVERING TO RUN CONTINUOUSLY MACHINE
THROUGH HANGERS.
EXISTING ROOM
4. SPACING AND SIZES WAITING
A. HORIZONTAL CARBON STEEL PIPE ROOM
PIPE SIZE ROD DIAMETER MAXIMUM SPACING
UP TO 1-i/4' 3/8' 8'
1-1/214 2' 3/8' to' EXISTING MEDICAL
B. HORIZONTAL COPPER PIPING OFFICE SPACE
PIPE SIZE ROD DIAMETER MAXIMUM SPACING
UP TO 1' 3/8' V
1-1/4' 4 1-1/2' 3/8' 6'
2' 3/8' at
VA VA VA
(DI I U 0 Li
PLUMBING NOTES ENTRY
I. ALL PLUMBING WORK SHALL BE PETWORMED IN ACCORDANCE WITH THE
LATEST EDITION OF THE 'SOUTH FLORIDA BUILDING CODE', CHAPTER
46, LOCAL ORDINANCE AND IN COMPLIANCE WITH 'FLORIDA ENERGY
EFFICIENCY CODE FOR BUILDING CONSTRUCTION. EXISTING
RECEPTION
2. CONTRACTOR TO VERIFY AT SITE LOCATION THE ELEVATION AND SIZE
OF EXISTING WATER AND SEWER MAINS FOR CONNECTION OF NEW
SERVICES BEFORE INSTALLATION OF ANY PIPING.
3. UNDERGROUND METAL PIPING SHALL BE PROTECTED WITH COAT OF
BITUMINOUS
ALLL UN DER3ROUND COPPER PIPING SHALL BE FULLY F SLE RING.
SLEEVED.
EXIS7IN!s 21 CW
t 1' HW IN CL�s.
4. PROVIDE SHUT-OFF AND VACUUM BREAKER TO ALL HOSE 5I555 AND ..
FAUCETS WITH HOSE-END CONNECTION, iYi C'3
O
5. ALL FIXTURES SHALL BE PROTECTED AGAINST WATER HAMMER WITH AIR
CHAMBE O SHOCK O .
R5 R AB5 RBERS M3/FILES - - EN - - I EXISTING.. ZO
2m1
6. PLUMBING FIXTURES SHALL BE 'AMERICAN STANDARD' OR APPROVED 0 STAIR �'-+ o
C-+ W
9
a
EQUAL. ALL FIXTURE TRIM SHALL BE CHROME PLACED.FIXTURES � ® ltg .,!4 �
SHALL 13E PROVIDED WITH SUPPORTS, HANGERS, ETC. 1 ,'y W ,d
-I, WASTE LINES SHALL SLOPE 1 1S' PER FOOT. UNLESS OTHERWISE EXISTING EXISTING EXISTING 1 ----�- STORAGE z
WORK EXISTING EXAM �+
NOTED, AREA TOILET TOILET sm9 W �,
EXAM WORK STATION WORK ARE �, O
4m3 ISTING 3/4'': I
S. PROVIDE FULLY ACCESSIBLE GLEANOUTS ON SANITARY AND ANY WASTE _20271 I HU1 < CW IN °' ; !�!
CLG. fY o
PIPING AT EVERY CHANGE OF DIRECTION AND At BOTTOM OF STACKS EXISTING `rI�1 O o D
� o
CLEAN OUT LOCATION AND SIZES ON HORIZONTAL LINES SHALL BE EXAM ; n►1 mi 1-1
ACCORDING TO CODE, I I I W p•••� A
9. VENT LINES SHALL EXTEND 6' MIN. ABOVE ROOF= AND FLASHED WITH
WAITING — EXIS71NCs 3/d E W
HW <CW M �GORRi E
LEAD OR CONNECTED TO EXISTING VENT LINES. CORRIDOR 2ma cLG. 21
10. ALL FLOOR DRAINS SHALL HAVE TRAP PRIMERS TO PROTECT THE SEAL
OF THE TRAP. ' 1 SK
11. PROVIDE CONTROL VALVES TO ALL MAINS ENTERING THE BUILDING, 2Ra
SIC I 2FU I I
RISERS, BRANCHES, GROUPS OF FIXTURES, AND TO EACH PIECE OF EXISTING
EQUIPMENT. i 2FU i I
EXISTING EXISTING EXISTING 1 LL gK LOUNGE ELECTRICAL
OFFICE EXAM OFFICE ROOM
2FU s�o
0 EXISTING EXAM EXAM EXAM
Li
EXISTING EXISTING EXISTING TREATMENT Zmg zmb 2= 1
E
FV
XAM O O EXAM OFFICE ROOM
PIPING MATERIALS
EXISTING
1. SANITARY WASTE, VENT AND STORM DRAIN:
MECHANICA
BELOW GROUND: `CAST IRON', SERVICE WEIGHT, PIPE, t FITTINGS ; REF,
ACCORDING t0 ASTM A-14 HUB d SPIGOT OR,
ABOVE GROUND: 'CAST IRON',SOIL PIPE, 'HUBLESS', ACCORDING
TO CISPI-301-18, ASTM A-14, WiTH STAINLESS STEEL SHIELD AND
CLAMPS OVER NEOPRENE SEALING SLEEVE.
ALTERNATE: THE PLUMBING CONTRACTOR MAY ELECT, IF APPROVED BY
OWNER, TO USE THE FOLLOWING MATERIAL SPECIFICATION FOR WASTE,
VENT AND STORM DRAIN SYSTEM: POLYVINYL CHLORIDE (PVC) PIPE t
FITTINGS (SCHEDULE 40).MATERIAL SHALL COMPLY WITH 0-1184,
TYPE 1,GRADE 1 COMPOUND. PiPE SHALL COMPLY WITH ASTM D-1185. EXISTING 2' CW 4
\ 1' HW IN CLG.
FITTIINGS SHALL COMPLY WITH ASTM 0-2461 SOCKET TYPE. SOLVENT EXIST.
CEMENT SHALL COMPLY WITH D-2564. �j 3' VTR LUM51NG FLAN
2. CONDENSATE DRAINS FROM AIR CONDITIONING UNiTS: PVC
SCHEDULE 40 PIPE 4 FITTINGS.
3/1& ° _ 1 -0° 5;-Is- EXiSTiNG 2' VENT
3, DOMESTIC WATER ABOVE GROUND: TYPE L COPPER PIPE WITH WROUGHT
COPPER SOLDERED JOINT FITTINGS. TYPE K COPPER BELOW GROUND,FULLY �� P
SLEEVED, PIPE ACCORDING TO ASTM B-42. TUBE ACCORDING TO ASTM B-88. �� ��,• 1 N,
ALTERNATE FOR UNDERGROUND PIPE: CAST IRON WATER PIPE r 4FU
ACCORDING To ANSI A 21.6. STEEL PIPE (SCHEDULE 40, 1 NEW 21 EXIST, I I
�'..
GALVANIZED) ACCORDING t0 ASTM A120-68. I I Be YrR NEW 112114W 4 CW
1/2'1 I/2 POTABLE WATER LINES �.
I EXISTING 2' SANITARY '
4. ALL CONTROL VALVES FOR DOMESTIC WATER SHALL BE CAST BRASS OR
SK I CONNEG'tED t0 �¢' STACK 3! g1��
5-88 BRONZE GATE VALVES. SK i/2 1/1
�' k,
5. PROVIDE DIELECTRIC FITTINGS FOR JOINING DISSIMILAR METALS. 21� Co. Co.21 EXISTINCs 2' VENT
1/1' ° •.���'
,-
�� SIG
NEW 2' LATERAL NEW 1/2' 14W 4 CW
CONNECTED TO 2' STACK �' �_ NEW 2' VENT 1/2 POTABLE WATER LiNES h
°.SIC I A,.
4
2FU I 41:U SK 1/1'1 11/2'
I SK I . PROJECT N0.
12Fu CO. P4 205048
NEW 22 LA'T'ERAL 1/2' 1/2'
CONNECTED t0 2' STACK V2'1
CO. EXISTING 2' SANITARY SHEET
CONNECTED TO 4' STACK i •
1/2 �` P — 1
t OF
SANITARY Ri &ER DIAS, tits ' ' ;
DO(l I. `WATER R15ER DIAGP, nts 1 ►t