01-0144-011 1 ) 1
SAMUEL G MATTHEWS
A R C H I T E C T
AR 0009733
NOTE: NO NEW ELECTRICAL CIRCUITS ARE ;
REQUIRED. CONTRACTOR 15 TO CONNECT NEW
8545 SW M PLACE
OR RELOCATED RECEPTACLES TO EXISTING ' ' ' ' MIAMI, FLORIDA
1201208V 20 AMP CIRCUITS AS INDICATED ON (305) 595.3149
G�1�1�}�'A� ELECTRICAL 1�10`��5 � PLANS.
I- THE CONTRACTOR SHALL FURNISH AND INSTALL ALL MINOR ITEMS WN NOTE. NO NEW FIRE ALARM DEVICES ARE ICN ARE OBVIOUSLY REQUIRED. EXISTING HORN STROI:3ES AND
AND REASONABLY NECESSARY TO COMPLETE THE INSTALLATION. SMOKE DETECTORS ARE INDICATED ON
2. BIDDERS SHALL VISIT THE SITE AND FAMILIARIZE THEMSELVES WITH ALL CONDITIONS PLANS. MAIN PANEL IS LOCATED ON THE
SURROUNDING THE WORK. EXISTING FIRST FLOOR L08BY.
STAIR DATE:
3. THE CONTRACTOR IS REFERRED TO THE ARCHITECTURAL, STRUCTURAL AND MECHANICAL 01-20-01
PLANS AND SPECIFICATIONS. SUCH PLANS AND SPECIFICATIONS ARE TO BE CONSIDERED
PART OF THE ELECTRICAL CONTRACT DOCUMENTS. REVISIONS:
4. DRAWINGS ARE DIAGRAMMATIC AND INTENDED TO SHOW APPROXIMATE LOCATIONS AND 03-19-01
ARRANGEMENTS ONLY. EXISTING
5. ALL MATERIALS SHALL BE NEW, OF TYPES AND MAKES CALLED FOR, OR APPROVED EQUAL. ELEVATOR
h. CONTRACTOR SHALL SUBMIT REQUEST FOR SUBSTITUTION IN WRITING TO THE ENGINEER (�
I. CONTRACTOR SHALL TOUCH UP OR REFINISH THE FACTORY FINISH OF EQUIPMENT MARRED C� �❑ ❑
DURING SHIPMENT OR INSTALLATION. (D
8. THE ELECTRICAL INSTALLATION SHALL MEET THE APPROVAL OF THE GOVERNING
AUTHORITIES AND THE OWNER'S REPRESENTATIVES BEFORE ACCEPTANCE. EXISTING
S. THE CONTRACTOR SHALL BE A LICENSED MASTER ELECTRICIAN. ELEV.
MACHINE
10. THE ENTIRE INSTALLATION SHALL BE PERFORMED IN A FIRST-CLASS WORKMANLIKE EXISTING ROOM
MANNER WAITING
11. THE ELECTRICAL CONTRACTOR SHALL PROVIDE TEMPORARY POWER AND LIGHTING AS ROOM
REQUIRED FOR ALL TRADES. O E
12. ELECTRICAL WORK SHALL NOT INTERFERE WITH CLEARANCES REQUIRED FOR GENERAL F EXISTING-,: MEDICAL
AND MECHANICAL CONSTRUCTION. SHOULD ELECTRICAL WORG BE INSTALLED WHICH OFFICE SPACE
INTERFERES WITH THE WORK OF THE OTHER CONTRACTORS, SUCH WORK SHALL BE CHANGED
At NO ADDITIONAL COST t0 THE OWNER
13. AT THE COMPLETION OF THE WORK, THIS CONTRACTOR SHALL REMOVE ALL RUBBISH
CAUSED BY HIS WORK AND SHALL THOROUGHLY CLEAN ALL ELECTRICAL EQUIPMENT.
VA
VA VA
14. ALL WORK SHALL BE GUARANTEED FREE FROM DEFECTS FOR A PERIOD OF ONE YEAR (D
FROM DATE OF FINAL ACCEPTANCE.
15. ALL ITEMS OF ELECTRICAL EQUIPMENT ASSOCIATED WITH THE CONTROL OF ELECTRICAL
APPARATUS SHALL BE IDENTIFIED. O E ENTRY
D
1(o_ NOMINAL MOUNTING HEIGHT OF DEVICES IN EXPOSED CONCRETE BLOCK, OR BRICK WALLS
SHALL ALL OCCUR WITHIN A STRUCTURAL COURSE. A MINIMUM AMOUNT OF BLOCK, OR
BRICK WALLS SHALL BE CUT.
11. ALL ELECTRICAL EQUIPMENT SHALL BE COMMERCIAL GRADE AND UL APPROVED UNLESS ExIStINrs
SPECIFIED OTHERWISE. ® O�•
E
18. WIRING; DEVICES SHALL SE SPECIFICATION GRADE. MINIMUM SIZE OF OUTLET BOXES ffh E �+ Q ►-�
SHALL BE 4' TRADE_ Op O Z A
o z
6 a
19. ALL CONDUCTORS SHALL BE COPPER, UNLESS OTHERWISE NOTED, 00V, X10 AND SMALLER, c) Z a
TYPE t1 HN/THWN, 08 AND LARGER, TYPE THWN, 012 MINIMUM EXCEPT CONTROL WIRING. I
E O r�.Yt
Z
0. L WIRING MUST BE IN CONDUIT. A PULL WIRE OR CORD SHALL BE INSTALLED IN ALL
EMPTY CONDUITS.
21. FLEXIBLE CONDUIT SHALL BE USED FOR CONNECTIONS TO VIBRATING EQUIPMENT. EXISTING E NTERVITw R F
'SEALTITE' WHERE USED OUTDOORS. BUSINESS TO MAT MCs
IST ` O c c
OFFICE ENTRY EXISTING t„
22. RISES SHALL BE BUSSMAN 'FUSTRON' DUAL-ELEMENT, TIME DELAY, OR EQUAL, OR AS
STAIR
CALLED FOR ON DRAWINGS. NEW w A
DISPLAY O Z
CABIAET EXISTING ❑ E 3m z
23. PROVIDE TYPEWRITTEN INDEX CARDS FOR ALL PANELS. EXISTING EXISTING ❑
£ TOILET TOILET ❑ EXISTING `' EXAM OTO PHOTO �y
24. PROVIDE ALL ELECTRICAL PANELS, CONTROLLER DISCONNECT SWITCHES AND TIME EXISTING EC-32 PREP W
CLOCKS WITH PLASTIC EMBOSSED LABELS. STAFF L2 2 �s-3� 2 20� ROOM
Fl 25. THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFICATION OF CEILING CONSTRUCTION EXISTING LOUNGE STO.
BEFORE ORDERING OR INSTALLING LIGHT FIXTURES. EXAM
26. THE CONTRACTOR SHALL BE RESPONSIBLE FOR PROPERLY BALANCING ALL BRANCH E O
E
D CORRIDOR OD E
CIRCUITS BETWEEN THE PHASES OF THE SYSTEM REGARDLESS OF CIRCUITING INDICATED. E � E Extsrn�Qaxt=L Ls
21• MOTOR STARTERS AND CONTROLS FURNISHED BY MECHANICAL CONTRACTORS, INSTALLED F O E CORRIDOR E F Ell 3P 40*&s 2
AND WIRED (INCLUDING CONTROL WIRING) BY ELECTRICAL GONtR.ACTOR
a 411 W01T4 LOAD
EXISTMCs PANEL H4
28. PROVIDE COMPLETE FIRE ALARM SYSTEM AS INDICATED AND IN ACCORDANCE WITH ALL �_ , sl�. o ���.t,t�V
REQUIREMENTS OF THE LOCAL FIRE MARSHAL. t I TW LOAD
Ec-s
EC-8
29. PROVIDE RACEWAY SYSTEMS AND PULL WIRES FOR TELEPHONE SYSTEM AS SHOWN. EXISTING L4 a !=c-9 Ec_9 XISTING ELECTRICAL
RICAL
OFFICE D EXISTING EXISTING -b Lz ILE Roots ROOM
30. 20 AMP CIRCUITS FROM 100 FT. TO 200 FT. ONE-WAY, USE 010 WIRE, OVER 200 FT. USE •8 WIRE. O EXAM OFFICE
0 r_
EXAM �.g • EG-b EXAM EG-8
EXAM
31. ALL EQUIPMENT AND SYSTEMS SHALL BE DEMONSTRATED TO BE FUNCTIONING EXISTING EXISTING-: EXISTING-� �REATNMNT 4ms ��' 4ma
SATISFACTORILY PRIOR t0 FINAL ACCEPTANCE. EXAM ❑ ❑ EXAM OFFICE ROOM i2-3z
-b LE4G-6
32. MAINTAIN THE FIRE RATING OF ALL PARTITION WALLS THROUGH WHICH CONDUIT PASS AND .b
JUNCTION BOXES ARE INSTALLED. L2 1.2
2:9 d A
EXISTING
MECHANICA
.1111111 r•Y. ..
` L1
�L
J
POWER PLAN - w
L)
I �
PROJECT NO.
205048
SHEET
• E - 1
OF
2