00-0508-028 :
/
\ /
ELECTRICAL NOTES � - -
1. ALL WIRING TO RUN EXPOSED, CONCEALED IN MASONRY WALLS OR CONCRETE 14. ELECTRICAL CONTRACTOR SHALL VERIFY ALL EQUIPMENT NOT FURNISHED
SLABS, BENEATH SLABS OF GRADE OR RUN UNDERGROUND SHALL BE IN RIGID UNDER THIS SECTION BEFORE ROUGHING-IN.
.._..
GALVANIZED STEEL CONDUIT. OR PVC SCHEDULE 80 IF EXPOSED, OR SCHEDULE
40 IN ALL OTHER SITUATIONS, GALVANIZED STEEL CONDUIT. ELECTRICAL METALLIC 15. SEE EQUIPMENT LAYOUT PLANS FOR LOCATION OF BUILDING EQUIPMENT BEFORE /)
TUBING MAY BE CONCEALED IN INTERIOR HOLLOW WALLS AND ABOVE SUSPENDED ROUGHING-IN. ; --
CEILINGS.
16. ELECTRICAL CONTRACTOR SHALL VERIFY LOCATION OF ALL EQUIPMENT'S
2 . ALL WIRES SHALL BE COPPER UNLESS SPECIFICALLY OTHERWISE INDICATED ON REQUIRING ELECTRICAL CONNECTION BEFORE ROUGHING-IN.
THE DRAWINGS. ALL INSULATION SHALL BE TYPE "THW'. OR "THHN/THWN".
17. CONDUIT RUNS ARE SHOWN SCHEMATICALLY. BUILDING CONDITIONS WILL + I
3 . BOXES SHALL BE PROVIDED FOR ALL OUTLETS. IN GENERAL THESE BOXES SHALL DETERMINE THE ACTUAL CONDUIT RUN.
BE STAMPED OR PRESSED SHEET METAL. BOXES IN HAZARDOUS AREAS SHALL BE
APPROVED FOR THE CONDITIONS INDICATED.
18. ELECTRICAL CONTRACTOR SHALL VERIFY WITH MANUFACTURER THE LOCATION
.\,• a _� & /ice: \ `' t �,.��Lo ,/ j' /'
OF CONNECTION BOX OF EACH EQUIPMENT BEFORE ROUGHING-IN.
4 ALL CONDUITS SHALL BE SECURELY FASTENED TO THE BUILDING WITH PIPE }
STRAPS OR OTHER APPROVED PIPE SUPPORTS. 19. WHERE WIRE SIZES ARE INDICATED ON THE PLANS FOR ANY INDIVIDUAL "
CIRCUITS. THE INDICATED WIRE SIZE SHALL APPLY TO THE COMPLETE
5 MANUFACTURER'S NAMES AND CATALOG NUMBERS ARE USED TO DEFINE THE ;f,
CIRCUIT UNLESS OTHERWISE INDICATED.
PE AND QUALITY OF EQUIPMENT AND MATERIAL. EQUAL ITEMS OF OTHER
f r
MANUFACTURERS ARE ACCEPTABLE WITH THE APPROVAL OF THE ENGINEER. 20. ALL MOTORS STARTERS FOR FANS, PUMPS, BOILERS, AIR CONDITIONING, ETC.;
L BE EQUIPPED WITH OVERLOAD PROTECTION IN EACH PHASE LEG.
" . /.!-:
:. ..
. ALL WORK SHALL BE DONE IN FULL ACCORDANCE WITH THE NATIONAL ..;�,;\�::�- •••,, ,
STARTERS FOR MOTORS RATED AT 50 HP. OR LESS AT 208 v. MAY BE ACROSS THE M t �. :. ..
ELECTRICAL CODE. ALL APPLICABLE STATE AND LOCAL CODES, AND THE LOCAL LINE TYPE, WHERE APPLICABLE STARTERS FOR LARGER MOTORS SHALL BE � //: �- ::��--,�: •, ,,� _.."/
UTILITY COMPANY REQUIREMENTS. COMPLY W SFBC CHAPTER 45 \ l
REDUCED VOLTAGE TYPE PART WINDING, PRIMARY RESISTOR, ETC.) k. +�
7 ALL WORK SHALL BE DONE IN A NEAT AND WORKMANLIKE MANNER.
21. ALL EQUIPMENT FURNISHED WITH Y
CORD, THE CORD SHALL BE SHORTENED AND
INSTALLED WITH CORRECT OUTLET PLUG, JACKS, ETC., AS REQUIRED FOR y..
S SOON AS PRACTICABLE, AND WITHIN THIRTY DAYS AFTER T14E AWARD OF THE COMPLETE INSTALLATION OF EQUIPMENT. ALSO WHEN APPLICABLE RECEPTACLES
CONTRACT, AND BEFORE ANY MATERIALS OR EQUIPMENT ARE RELEASED FOR SHALL BE FURNISHED TO MATCH THE ELECTRICAL EQUIPMENT SERVED BY.
SHIPMENT, THE CONTRACTOR SHALL SUBMIT TO THE ENGINEER FOR APPROVAL A
COMPLETE LIST OF MATERIALS AND EQUIPMENT THAT HE PROPOSES TO FURNISH 22. ALL ELECTRICAL SERVICE EQUIPMENT SHALL BE READILY ACCESSIBLE I
6 = /
AND INSTALL, GIVING MANUFACTURER'S NAMES. TRADE NAMES, CATALOG AND SHALL HAVE CLEAN AND DRY LOCATION AND BE PROTECTED FROM PHYSICAL
UMBERS, ETC. SEVEN COPIES SHALL BE FURNISHED. DAMAGE. ALSO, CLEAN WORKING SPACE SHALL BE PROVIDED AROUND EQUIPMENT •' • 1
(a)
9 WHERE A CONDUIT PASSES THROUGH A BUILDING EXPANSION JOINT OR A AS PER NEC. 110-16 (b).
STRAIGHT RUN EXCEEDS 200 FT. AND APPROVED EXPANSION FITTING WITH 23. JUNCTION AND PULLBOXES SHALL BE SECURELY MOUNTED TO THE BUILDING STRUC.
BONDING JUMPER SHALL BE INSTALLED. WITH SUPPORTING FACILITIES INDEPENDENT OF THE CONDUITS ENTERING OR LEAVING THE
BOXES. BRACKETS, RODS, HANGERS, BOLTS OF OTHER SUITABLE SUPPORTING METHOD 89,1 1 I
10. WHERE FUSIBLE EQUIPMENT IS SPECIFIED,DELIVER TO THE OWNERS MAY BE USED.
REPRESENTATIVE SPARE FUSES IN THE AMOUNT OF 10 % OF EACH SIZE USED ON I / — -
THE JOB WITH A MINIMUM OF 3 FUSES OF EACH SIZE. 24. JUNCTION AND PULLBOXES SHALL BE GALVANIZED CODE-GAUGE SHEET STEEL,
WITH SCREWED ON COVER, NEMA 1, OF SIZES AND SHAPE TO ACCOMMODATE 1 1
E CONTRACTOR SHALL VISIT THE SITE BEFORE SUBMITTING HIS BID IN ORDER WIRING WITHOUT CROWDING AND TO SUIT LOCATION.
r=
T HE MAY BECOME AWARE OF EXISTING CONDITIONS, NO ALLOWANCES WILL
BE MADE FOR ANY EXISTING CONDITION OF WHICH THIS CONTRACTOR WAS NOT 25. ALL JUNCTION AND PULLBOXES SHALL BE ACCESSIBLE ALL THE TIME
AWARE.
26. ALL RACEWAYS ROUTED, INSULATED CONDUCTORS SYSTEM SHALL BE COLOR
12. CIRCUIT NUMBERS SHOWN ARE FOR IDENTIFICATION ONLY. IT SHALL BE THE CODED AS PER NEC. STANDARDS . /
ELECTRICAL CONTRACTOR'S RESPONSIBILITY TO COMPLETE PHASE PANEL BOARD
BALANCE LOAD). 27. PROVIDE J.B. AS REQUIRED BY FIELD CONDITIONS, EVEN IF NOT SHOWN
13. SEE EQUIPMENT LAYOUT PLANS FOR EXACT LOCATION OF ALL MOTORS AND
OTHER EQUIPMENT BEFORE ROUGHING-IN.
A27,29 /
1 / O 0
_ V w
_ w rZ
� LO
�-- _ —
a;'2F., c,r)
CONCRETE POLE 20' LENGTH ABOVE GRADE. U
SEE SITE LIGHTING PLAN. $H M
J
U-
ACCESS OPENING COVER SHALL \ '`' / -% m W
COMPLY WITH THE N.E.C. \ m
410-15 (ACCESSIBILITY) Q 00
J
H.
a A,
Q J
EXTERIOR GRADE NOTE: THIS POLE IS DESIGNED TO WITHSTAND \•; \ , i,' T
OR ASPHALT. .:;:;y....,.;t,;// O
150 MPH. _���:.......,�< : U Ir
.cif
2' MIN.
/
1" PVC CONDUIT
WELL COMPACTED FILL,
TO ATTAIN MINIMUM OF
i
95 X COMPACTION,SEE
STRUCTURAL NOTES FOR `• ' ., r`
6" MIN. MIN. COMPACTION REQ'S. \` '/ ��' .
CONCRETE POLE
d
ENCASED A MINIM. OF 7'-0"
..
\z ;
POLE MOUNTING DETAIL ._..........._._.........
N.T.S.
ui
LL
cp
w
- <
J
0
ui
SITE ELECTRICAL PLAN • ELECTRICAL z w
c • MECHANICAL
• PLUMBING
SCALE. 1"=10'--0" w 0 Q
W r CARLOS M.
a BARRENECHEA Z
y W PRESIDENT Lu D
—p 4936A S.W. 74 CT. '? ).O (n Q
MIAMI, FLA. LID `/J J
[9 33155 I O N
Z Z OFFICE N
ul W (305) 665-7759 Q N31
FAx
(3 05) 665-7758
L.C. No. EBO❑E171 So
�„v) 0 , rl: P.E. No. 0052023
.L.,� Q : U �. 3 • 1 r! EDUARD❑ MARTINEZ
,/ ELECTRICAL ENGINEER
I •�1