00-0646-024 ` REVISION BY
FACKAGED ROOFTOP A.C. UNIT SCHEDULE J --
UNIT DESIGNATION RTU-I RTU-2
H VAG DESIGN RE CQU I RE S: YES NO DESIGN MANUFACTURER TRANS TRANE
DUCT SMOKE DETECTOR
Q MODEL NO. TCX060G100A TCX0365100
NOMINAL TONS 5.0 3.0
FIRE DAMPER(S) 0 (8) EER 12.05 12.60
SMOKE DAMPERS) 0 LOCATION SEE PLAN SEE PLAN
TOTAL AIR SUPPLY CFM 2000 1,200
FIRE RATED ENCLOSURE 0 OUTSIDE AIR SUPPLY CFM 160 140
FIRE RATED ROOF/FLOOR EXT. STATIC F RES5. IN. OF Hz0 0.50 0.59
CEILING ASSEMBLY 0 FAN MOTOR HP/FLA 3/4 50 1/3 2A
FIRE STOPPING 0 Lu SENSIBLE COOLING CAP. BTU/HR 43,400 25.000
SMOKE CONTROL W_ TOTAL COOLING CAP . BTU/HR 61,500 36,000
0 ENTERING AIR TEMP. (DB/WB) 'F 80 6� 80 6"I
FILTER TYPE AND THICKNESS 1 'THROWAWAY 1 'THROWAWAY
FILTER SIRE GUT t0 Flt CUT TO PIT �
O CQ d,
w TOTAL HEATING CAPACITY BTUH 32,765 23,891 O
O � �
HEATER SIZE KW °-6 1.0
U � c°� c°
NOMINAL TOTAL FLA 28.8 112 0 Cd .,
a�� tL
FAN NOMINAL TOTAL HP/FLA 1/2
AMBIENT AIR TEMP. (DB) 'F 95 95 O
MAX. CONDENSING TEMP. •F 125 125
ELECTRICAL REQUIREMENTS VR/Hz 240/1/60 24011160 Qi
MCA/MOCP 45 .10 26 �cd
OPERATING WEIGHT Iba
500 233 O e
REMARKS ROOF CURB FRAME O
NOTES: Q rua
� l
V O
I. UNITS SHALL BE FACTORY FABRICATED RICATED ROOF TOP UNITS PROVIDE A FULL FACTORY
FABRICATED SOUND ATENUATION ROOF CURB UNLESS OTHERWISE INDICATED. �^ O
2. UNITS SHALL HAVE WEATHERPROOF OUTSIDE AIR INTAKE PROVISIONS SIZED FOR
INDICATED AIR QUANTITY COMPLETE WITH MANUAL VOLUME DAMPER AND U ,� p
N
BIRDSCREEN UNLESS OTHERWISE INDICATED. 0 ,10
� d"
3. UNITS SHALL BE CONSTRUCTED AND INSTALLED TO WITHSTAND A 60 PSF WIND
PRESSURE FROM ANY DIRECTION.
b
4. UNITS SHALL BE EQUIPPED WITH THROWAWAY ROWAWAY TYPE FILTERS SIRED AND ARRANGED � � co
TO HANDLE THE FULL AIR QUANTITY.
5. UNITS SHALL HAVE SINGLE POINT ELECTRICAL CONNECTION. oO '"'<�
6. COMPRESSORS SHALL HAVE 5 YEAR EXTENDED WARRANTY.
cl
1. UNITS SHALL BE EQUIPPED WITH ANTI-SHORT CYCLE TIMERS. O�
8. EXTERNAL STATIC PRESSURE DOES NOT INCLUDE FILTERS. cn
9. CONDENSER COILS SHALL BE PROVIDED WITH A PROTECTIVE GUARD.
a
10. ALL DUCT CONNECTIONS TO EACH UNIT SHALL BE PROVIDED WITH A 4' FLEXIBLE 00
CONNECTION.
11. UNITS SHALL BE PROVIDED WITH ADEQUATE INSULATION TO PT%!EVENT SURFACE
CONDENSATION UNDER ALL CONDITIONS.
12. UNLESS UNITS HAVE A FACTORY INSTALLED INTERNAL CONDENSATE DRAIN TRAP,
PROVIDE EXTERNAL DWV 3' DEEP TRAP FULL SIZE OF DRAIN CONNECTION IN
ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS. ..._
13. THE UNITS ENERGY EFFICIENCY RATINGS SHALL COMPLY WITH ALL STATE AND
LOCAL REQUIREMENTS.
■ �
14. ROOF OPENINGS SHALL BE NO LARGER THAN NECESSARY TO ACCOMMODATE THE
SUPPLY AND RETURN DUCTS INDIVIDUALLY.
15 PROVIDE A PROGRAMABLE, DIGITAL tHER!'10StAt AS RECOMMENDED BY
MANUFACTURER
U
0 JR
I OUTSIDE AIR INTAKE ,per
MANUAL DAMPER (n �♦
(D
ROOFTOP
A/C UNIT ■® O
CONDENSATE DRAIN (SEE SCHEDULE) > J
(SEE PLUMBING DWG
S.)
I�I ® Lij LL
FASTENER 1/2' BOLTS 0 24' OZ. (TYP) (D L
FLASHING 0 e
14' HIGH MANUFACTURER '�'
BUILT-UP ROOF,,,, CURB O
�. WOOD CANT OUT6 f 1D E A f RECAPITULATION cn :c
PLYWOOD DECK TOTAL OUTSIDE ® Q �-
UNIT NO. AREA SERVED NO.PEOPLE ��RSSON AIR/UNIT (CPM) REMARKS � m
MIN. USED
� � O�
O
GALVANIZED METAL SUPPORT RIGID INSULATION ?TU-1 ___ 13 20 260 260 ---
ANGLE (TYPICAL)
FLEXIBLE CONN, i �� 1/2' BOLTS a 24' O.C. (TYP) RTU-2 ___ 20 140 140 ---
(TYPICAL) (2) 1/2'10 BOLTS THRU STRUCTURE
WITH DOUBLE LOCK NUTS
(TYPICAL ON BOTH SIDES)
IV WOOD STRUCTURE
.,...add...-.
DRAW!
s/AIR R/AIR NOTES CHECK
I OUTDOOR AIR PROVISIONS FOR VENTILATION SHALL SATISFY THE MINIMUM
ABC UNIT (ROOFTOP) INSTALLATION DETAIL REQUIREMENTS FOR ACCEPTABLE INDOOR AIR QUALITY PER ASHARE 62-1989.
DATE
NT°v 2 THE FULL VOLUME OF OUTSIDE AIR ESTABLISHED IN THIS SCHEDULE SHALL BE 1�0 18/99
DELIVER TO THE SPACE AT ALL TIMES THAT THE BUILDING 15 OCCUPIED
scA�E
1 /4„ _ 1 ,_0.,
JOD 110.
&MET
rfY f1 �� r• t'. ..
OF SHEETO