00-0646-024 ` REVISION BY FACKAGED ROOFTOP A.C. UNIT SCHEDULE J -- UNIT DESIGNATION RTU-I RTU-2 H VAG DESIGN RE CQU I RE S: YES NO DESIGN MANUFACTURER TRANS TRANE DUCT SMOKE DETECTOR Q MODEL NO. TCX060G100A TCX0365100 NOMINAL TONS 5.0 3.0 FIRE DAMPER(S) 0 (8) EER 12.05 12.60 SMOKE DAMPERS) 0 LOCATION SEE PLAN SEE PLAN TOTAL AIR SUPPLY CFM 2000 1,200 FIRE RATED ENCLOSURE 0 OUTSIDE AIR SUPPLY CFM 160 140 FIRE RATED ROOF/FLOOR EXT. STATIC F RES5. IN. OF Hz0 0.50 0.59 CEILING ASSEMBLY 0 FAN MOTOR HP/FLA 3/4 50 1/3 2A FIRE STOPPING 0 Lu SENSIBLE COOLING CAP. BTU/HR 43,400 25.000 SMOKE CONTROL W_ TOTAL COOLING CAP . BTU/HR 61,500 36,000 0 ENTERING AIR TEMP. (DB/WB) 'F 80 6� 80 6"I FILTER TYPE AND THICKNESS 1 'THROWAWAY 1 'THROWAWAY FILTER SIRE GUT t0 Flt CUT TO PIT � O CQ d, w TOTAL HEATING CAPACITY BTUH 32,765 23,891 O O � � HEATER SIZE KW °-6 1.0 U � c°� c° NOMINAL TOTAL FLA 28.8 112 0 Cd ., a�� tL FAN NOMINAL TOTAL HP/FLA 1/2 AMBIENT AIR TEMP. (DB) 'F 95 95 O MAX. CONDENSING TEMP. •F 125 125 ELECTRICAL REQUIREMENTS VR/Hz 240/1/60 24011160 Qi MCA/MOCP 45 .10 26 �cd OPERATING WEIGHT Iba 500 233 O e REMARKS ROOF CURB FRAME O NOTES: Q rua � l V O I. UNITS SHALL BE FACTORY FABRICATED RICATED ROOF TOP UNITS PROVIDE A FULL FACTORY FABRICATED SOUND ATENUATION ROOF CURB UNLESS OTHERWISE INDICATED. �^ O 2. UNITS SHALL HAVE WEATHERPROOF OUTSIDE AIR INTAKE PROVISIONS SIZED FOR INDICATED AIR QUANTITY COMPLETE WITH MANUAL VOLUME DAMPER AND U ,� p N BIRDSCREEN UNLESS OTHERWISE INDICATED. 0 ,10 � d" 3. UNITS SHALL BE CONSTRUCTED AND INSTALLED TO WITHSTAND A 60 PSF WIND PRESSURE FROM ANY DIRECTION. b 4. UNITS SHALL BE EQUIPPED WITH THROWAWAY ROWAWAY TYPE FILTERS SIRED AND ARRANGED � � co TO HANDLE THE FULL AIR QUANTITY. 5. UNITS SHALL HAVE SINGLE POINT ELECTRICAL CONNECTION. oO '"'<� 6. COMPRESSORS SHALL HAVE 5 YEAR EXTENDED WARRANTY. cl 1. UNITS SHALL BE EQUIPPED WITH ANTI-SHORT CYCLE TIMERS. O� 8. EXTERNAL STATIC PRESSURE DOES NOT INCLUDE FILTERS. cn 9. CONDENSER COILS SHALL BE PROVIDED WITH A PROTECTIVE GUARD. a 10. ALL DUCT CONNECTIONS TO EACH UNIT SHALL BE PROVIDED WITH A 4' FLEXIBLE 00 CONNECTION. 11. UNITS SHALL BE PROVIDED WITH ADEQUATE INSULATION TO PT%!EVENT SURFACE CONDENSATION UNDER ALL CONDITIONS. 12. UNLESS UNITS HAVE A FACTORY INSTALLED INTERNAL CONDENSATE DRAIN TRAP, PROVIDE EXTERNAL DWV 3' DEEP TRAP FULL SIZE OF DRAIN CONNECTION IN ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS. ..._ 13. THE UNITS ENERGY EFFICIENCY RATINGS SHALL COMPLY WITH ALL STATE AND LOCAL REQUIREMENTS. ■ � 14. ROOF OPENINGS SHALL BE NO LARGER THAN NECESSARY TO ACCOMMODATE THE SUPPLY AND RETURN DUCTS INDIVIDUALLY. 15 PROVIDE A PROGRAMABLE, DIGITAL tHER!'10StAt AS RECOMMENDED BY MANUFACTURER U 0 JR I OUTSIDE AIR INTAKE ,per MANUAL DAMPER (n �♦ (D ROOFTOP A/C UNIT ■® O CONDENSATE DRAIN (SEE SCHEDULE) > J (SEE PLUMBING DWG S.) I�I ® Lij LL FASTENER 1/2' BOLTS 0 24' OZ. (TYP) (D L FLASHING 0 e 14' HIGH MANUFACTURER '�' BUILT-UP ROOF­,,,, CURB O �. WOOD CANT OUT6 f 1D E A f RECAPITULATION cn :c PLYWOOD DECK TOTAL OUTSIDE ® Q �- UNIT NO. AREA SERVED NO.PEOPLE ��RSSON AIR/UNIT (CPM) REMARKS � m MIN. USED � � O� O GALVANIZED METAL SUPPORT RIGID INSULATION ?TU-1 ___ 13 20 260 260 --- ANGLE (TYPICAL) FLEXIBLE CONN, i �� 1/2' BOLTS a 24' O.C. (TYP) RTU-2 ___ 20 140 140 --- (TYPICAL) (2) 1/2'10 BOLTS THRU STRUCTURE WITH DOUBLE LOCK NUTS (TYPICAL ON BOTH SIDES) IV WOOD STRUCTURE .,...add...-. DRAW! s/AIR R/AIR NOTES CHECK I OUTDOOR AIR PROVISIONS FOR VENTILATION SHALL SATISFY THE MINIMUM ABC UNIT (ROOFTOP) INSTALLATION DETAIL REQUIREMENTS FOR ACCEPTABLE INDOOR AIR QUALITY PER ASHARE 62-1989. DATE NT°v 2 THE FULL VOLUME OF OUTSIDE AIR ESTABLISHED IN THIS SCHEDULE SHALL BE 1�0 18/99 DELIVER TO THE SPACE AT ALL TIMES THAT THE BUILDING 15 OCCUPIED scA�E 1 /4„ _ 1 ,_0., JOD 110. &MET rfY f1 �� r• t'. .. OF SHEETO