00-0646-001 =REVISI SION BY FACKAGED ROOFTOP A.C. UNIT SCHEDULE ^^^^ UNIT DESIGNATION RTU-1 RTU-2 H VAC D E S I C * IRE QU I RE S YES � O DESIGN MANUFACTURER TRANS TRANE DUCT SMOKE DETECTOR 0 MODEL. NO. TCX042F100 TCX0365100 v NOMINAL TONS 3B 3.0 FIRE DAMPER(S) O (S)EER 10.0 12b0 SMOKE OAMPER(S) © LOCATION SEE PLAN SEE PLAN / TOTAL AIR SUPPLY Cpm 1,400 1;00 FIRE RATED ENCLOSURE Q OUTSIDE AIR SUPPLY CFM 160 140 FIRE RATED ROOF/FLOOR EXT_ STATIC PRESS. IN. OF H2O 0b0 0.59 CEILING ASSEMBLY © FAN MOTOR HP/FLA 1/3 2Z 1/3 ?.4 FIRE STOPPING ~ © � SENSIBLE COOLING CAP_ BTU/HR 29,500 25,000 SMOKE CONTROL © O TOTAL COOLING CAP . BTU/HR 42,000 36,000 • O � � Q ENTERING AIR TEMP. (DB/WB) 'F 80 67 80 (Y FILTER TYPE AND THICKNESS I 'THROWAWAY 1 'THROWAWAY � � FILTER SIZE CUT TO FIT CUT TO Flt Q tu TOTAL HEATING CAPACITY BTUH 32,165 23,891 HEATER SIZE KW 9b 1.0 U I M M NOMINAL TOTAL FLA 18B 112 0 � � ' � ai k FAN NOMINAL TOTAL HP/FLA r-1 1� lb 1/6 Ib 4-) b AMBIENT AIR TEMP. (DB) •F 95 95 MAX. CONDENSING TEMP. •F 125 125 O '[ � a ELECTRICAL REQUIREMENTS V/O/Hz 240/1/60 240/1/60 .--� MCA/MOCP 28 45 26 40 OPERATING WEIGHT Ibs 850 233 U REMARKS ROOF CURB FRAME co U NOTES: o C_5 1. UNITS SHALL BE FACTORY FABRICATED ROOF TOP UNITS PROVIDE A FULL FACTORY o N M FABRICATED SOUND ATENUATION ROOF CURB UNLESS OTHERWISE INDICATED. M� �i � � 2. UNITS SHALL HAVE WEATHERPROOF OUTSIDE AIR INTAKE PROVISIONS SIZED FOR INDICATED AIR QUANTITY COMPLETE WITH MANUAL VOLUME DAMPER AND N � o BIRDSCREEN UNLESS OTHERWISE INDICATED. d 0 3. UNITS SHALL BE CONSTRUCTED AND INSTALLED TO WITHSTAND A 60 PSF WIND -p PRESSURE FROM ANY DIRECTION. O b 4 � o 4_ UNITS SHALL BE EQUIPPED WITH THROWAWAY TYPE FILTERS SIZED AND ARRANGED U A TO HANDLE THE FULL AIR QUANTITY. 5. UNITS SHALL HAVE SINGLE POINT ELECTRICAL CONNECTION. 6 O. COMPRESSORS SHALL HAVE 5 YEAR EXTENDED WARRANTY. o 1. UNITS SHALL BE EQUIPPED WITH ANTI-SHORT CYCLE TIMERS. ti ca S. EXTERNAL STATIC PRESSURE DOES NOT INCLUDE FILTERS. co 0 9. CONDENSER COILS SHALL BE PROVIDED WITH A PROTECTIVE GUARD. m u 10. ALL DUCT CONNECTIONS TO EACH UNIT SHALL BE PROVIDED WITH A 4' FLEXIBLE CONNECTION. 11. UNITS SHALL BE PROVIDED WITH ADEQUATE INSULATION TO PREVENT SURFACE CONDENSATION UNDER ALL CONDITIONS. 12. UNLESS UNITS HAVE A FACTORY INSTALLED INTERNAL CONDENSATE DRAIN TRAP, -- PROVIDE EXTERNAL DWV 3' DEEP TRAP FULL SIZE OF DRAIN CONNECTION IN ACCORDANCE WITH THE MANUFACTURER'S INSTRUCTIONS. 13. THE UNITS ENERGY EFFICIENCY RATINGS SHALL COMPLY WITH ALL STATE AND LOCAL REQUIREMENTS. 14. ROOF OPENINGS SHALL BE NO LARGER THAN NECESSARY TO ACCOMMODATE THE SUPPLY AND RETURN DUCTS INDIVIDUALLY. 15 PROVIDE A PROGRAMABLE, DIGITAL THERMOSTAT AS RECOMMENDED BY MANUFACTURER V I OUTSIDE AIR INTAKE MANUAL DAMPER ROOFTOP A/C UNIT La o CONDENSATE DRAIN (SEE SCHEDULE) i' (SEE PLUMBING DWGSa J -�� 0 L- � � FASTENER —\_ ip i 1 1/2' BOLTS o 24' O:C. (TYP) (D L FLASHING 14' HIGH MANUFACTURER �, BUILT-UP ROOF—\ ROOF CURB ���� f � � AIR �� f WOOD CANT R RECAPITULATION AT f Oil -� (� g y Yyy PLYWOOD DECK NET.SQ.FT. OUTSIDE AIR TOTAL OUTSIDE ® 0 UNIT NO. AREA SERVED NO.PEOPLE �M/PE SON AIRUNIT (CFM) REMARKS O MIN. USED GALVANIZED METAL SUPPORT _ ___ /� RIGID INSULATION RTU-1 --- 13 20 260 260 --- a N 0 ANGLE (TYPICAL) FLEXIBLE CONN, i �� 1/2' BOLTS a 24' DEG. lTYP) ,� RTU-2 --- 1 20 140 140 (TYPICAL) (2) 1/2'0 BOLTS THRU STRUCTURE --- WITH DOUBLE LOCK NUTS (TYPICAL ON BOTH SIDES) jWOOD STRUCTURE DRAG-4 _AIR R/AIR NOTES c�caeD I* I -�• I I * f I 1 OUTDOOR AIR PROVISIONS FOR VENTILATION SHALL SATISFY THE MINIMUM A/C UNIT (ROOFTOP) IIV5 I ALl.._ATIOI�l DETAIL REQUIREMENTS FOR ACCEPTABLE INDOOR AIR QUALITY PER ASHARE 62-I9S9. N.T.S 2 THE FULL VOLUME OF OUTSIDE AIR ESTABLISHED IN THIS SCHEDULE SHALL BE 10/18/99 DATE DELIVER TO THE SPACE AT ALL TIMES THAT THE BUILDING IS OCCUPIED acA�e 1 /4 " = 1 '-0" JOB 120. UHZET ei 4 ....... ENEETO