00-1294-001
I I ' A B C D E F G H I J K L M N 0 N.T.S. B A MECHANICAL SPECIFICATIONS 2.7 DUCTWORK: PROVIDED IN ACCORDANCE WITH LATEST EDITION OF SMACNA "LOW VELOCITY DUCT CONSTRUCTION STANDARDS", ASHRAE, ASTM, NFPA, AND APPLICABLE PROVISIONS OF THE co. PLUG PART 1 - GENERAL MECHANICAL CODE. A. GALVANIZED SHEET METAL: SUPPLY AND RETURN DUCTWORK, EXHAUST AND OUTSIDE AIR. DUCTWORK ABOVE ROOF SHALL BE WEATHERPROOFED AND PAINTED. INSULATION SHALL BE 1- 1.1 GENERAL: THE GENERAL AND SPECIAL CONDITIONS AND REQUIREMENTS OF THE CONTRACT AND 1/2" THICK RIGID ON INTERIOR, INSTALLED IN AN APPROVED MANNER. TEE AIR CONDITIONING UNIT SCHEDULE SPECIFICATIONS AS WELL AS PLANS AND SPECIFICATIONS OF OTHER DISCIPLINES AND TRADES SHALL B. NON-METALLIC DUCT: WHERE PREVIOUSLY APPROVED BY ARCHITECT/OWNER AND RULING ff�_H_� �..... - AHU APPLY AND BE PART OF THE WORK HEREBY SPECIFIED. THESE SPECIFICATIONS AND THE AUTHORITIES, AIR CONDITIONING UNIT SUPPLY AND RETURN AIR DUCTS MAY BE UL APPROVED A.H.U. UNIT DESIGNATION ACCOMPANYING PLANS ARE INTENDED TO PROVIDE FOR THE COMPLETE FURNISHING AND INSTALLATION 1-1/2" THICK FIBROUS GLASS DUCT BOARD TYPE 475. STAPLE AND TAPE ALL SEAMS AND 2 OF THE MECHANICAL SYSTEMS. "PROVIDE" MEANS "FURNISH AND INSTALL SECTIONS AND APPLY TAPE WITH ROBIN-AIRE HEAT GUN SET AT 400-DEGREE F., INSTALLED 1 ELBOW PER MANUFACTURER'S INSTRUCTIONS. AREA SERVED HOUSE 1.2 COMPLIANCE: WORKMANSHIP, MATERIALS AND INSTALLATION SHALL BE IN STRICT ACCORDANCE WITH C. FLEXIBLE DUCT: FACTORY INSULATED 1-1/2" MINIMUM FLEXIBLE DUCTWORK, CLASS 1 AIR Z ------ THE LATEST EDITION OF NFPA, ASHRAE, ASME, ASPE, ASTM, OSHA, HRS, HEALTH DUCT, UL 181 APPROVED, SIMILAR TO OWENS-CORNING MODEL NO. INL-25, CERTIFIED DESIGN MANUFACTURER AMERICAN AGENCIES, AND OTHER APPLICABLE NATIONAL, STATE, AND LOCAL CODES AND PERTAINING REGULATIONS CERTAFLEX OR APPROVED EQUAL. DUCTWORK SHALL HAVE RESILIENT CORE OF CONTINUOUS UNION CONN. STANDARD INC ESTABLISHED BY RULING AUTHORITIES HAVING JURISDICTION. CONTRACTOR SHALL ALSO MEET INNER AIR BARRIER, JACKETED WITH A REINFORCED VAPOR JACKET. FIRE HAZARD 4" EER/TON 16.1 .0 REQUIREMENTS OF OTHER RECOGNIZED STANDARDS WHERE SUCH REQUIREMENTS ARE MORE STRINGENT CLASSIFICATION SHALL HAVE A FLAME SPREAD OF 25, SMOKE RATING OF 50, IN ACCORDANCE , P A R T N E R S H I P TYPE V TICAL 1 THAN THOSE CITED ABOVE. WITH ASTM C518-70, ASTM E-84, AND UL 723 STANDARDS. 2" LOCATION CLOSET . . 1 OPERATING WEIGHT, LBS 150 1.3 WORKMANSHIP: ALL WORK SHALL BE PERFORMED BY CONTRACTORS LICENSED IN THEIR RESPECTIVE 2.8 DUCTWORK INSTALLATION: DISCIPLINES. WORK SHALL BE DONE IN A FIRST CLASS MANNER, FULLY OPERATIVE, AND TO THE A. DUCTWORK SIZES SHOWN ARE INSIDE DIMENSIONS. MANUFACTURER'S MODEL NUMBER 7A6048A100A ACCEPTANCE OF THE ARCHITECT/ENGINEER. CONTRACTOR SHALL PROVIDE FOR ALL NECESSARY LABOR B. EXHAUST AND OUTSIDE AIR INTAKES SHALL BE GALVANIZED METAL IN ACCORDANCE WITH 116 ALHAMBRA CIRCLE, SUITE J j TOTAL AIR, C.F.M. 1600 AND MATERIALS REQUIRED FOR COMPLETION OF THE WORK INCLUDING BUT NOT LIMITED TO SMACNA STANDARDS, SCREENED WITH A CORROSION-RESISTANT MATERIAL NOT LARGER THAN OUTSIDE AIR, C.F.M. ---- CONNECTIONS TO RELATED WORK SUCH AS CONNECTION TO EXISTING SYSTEMS, EXCAVATIONS AND 1/2" MESH. OUTDOOR AIR INTAKE SHALL BE A MINIMUM OF TEN (10) FEET FROM CORAL GABLES, FLORIDA 33134 Z EXTERNAL STATIC PRESS. IN. OF H2O 0.5 BACKFILLING, DEWATERING OF EXCAVATED TRENCHES. EXHAUSTS, FLUES, PLUMBING VENTS AND OTHER SOURCES OF EXHAUST. `` MOTOR HP NON-OVERLOAD 1 3 C. LONGITUDINAL SEAMS SHALL BE PITTSBURGH LOCK OR APPROVED EQUAL. LATERAL SEAMS E-mail : bapabapdesign.Com z MOTOR SPEED, RPM 1,050 1.4 MATERIALS:RUNDERWRI ER'SCLABORATORYP(UOL)DLABEL AS APPLICABLE. OMATER AMERICAN SHALL UBECACCEPTABLE INAND D. JOINTS ANDSSIEAMS DRIVE SHALLL BEASEALED WITH FOSTER AND 30-02 SHEET UCTI SEALANT APPLIED ABOVE 32 2 Florida Corp AA0002364 2 AHU CONDENSATE DRAIN CONNECTION ELECTRICAL SERVICE 240-1-60 ABOVE STANDARD QUALITY NORMALLY USED FOR THE PURPOSE AS CALLED FOR ON PLANS. DEGREES FAHRENHEIT. PH 305.444.7100 FX 305.444.9803 NTS v FACE VELOC. F.P.M. MAXIMUM DESIGN 500 400 1 SUPPLEMENTAL MATERIALS, PRODUCTS AND COMPONENTS NECESSARY TO COMPLY WITH THE INTENT OF E. DUCTS SHALL BE INDEPENDENTLY SUPPORTED TO PREVENT SAGGING, KINKING AND OTHER V) - DESIGN AIR ACROSS COIL, C.F.M. 0 THE CONTRACT DRAWINGS AND/OR SPECIFICATIONS, BUT NOT NOTED OR SPECIFIED ON THESE SECTIONS, PHYSICAL DAMAGE. WHERE PREVIOUSLY APPROVED BY ENGINEER, USE OF FLEXIBLE DUCTS � " TOTAL CAPACITY, B.T.U.H. 48,500 SHALL BE PROVIDED BY CONTRACTOR AS REQUIRED FOR COMPLETION OF THE WORK AT NO ADDITIONAL SHALL BE RESTRICTED ONLY FOR INDIVIDUAL BRANCH LENGTHS, MAXIMUM 10 FEET LONG. COpw*t © =By Beame ArchdeChral Partnership, PA c� COST TO THE OWNER. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVISIONS AND COORDINATION OF U J TOTAL SENSIBLE B.T.U.H. 32,500 DELIVERY OF MATERIALS. EQUIPMENT MARRED DURING SHIPMENT OR INSTALLATION SHALL BE TOUCHED 2.9 DUCT INSULATION: SUPPLY AIR DUCT SUPPLY AIR PLENUM.SEE FLEX CONN z °o ENTERING AIR TEMP. DB WB° F 80 67 UP AND REFINISHED TO FACTORY FINISH, REPLACED WHERE NOT ACCEPTABLE. A. AIR CONDITIONING DUCTS SHALL BE EXTERNALLY INSULATED WITH R-6 2-INCH BY 1-1/2" LB NARANJO -�- ASSOCIATES W/ O.B.D. (TYP) DWGS. FOR SIZE. ® SUCTION LINE $ U LEAVING AIR TEMP. DB / WB °F ---- FIBROUS GLASS FLEXIBLE BLANKET WITH UL APPROVED FIRE RESISTING ALUMINUM FOIL VAPOR 1.5 PERMITS & INSURANCE: CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS FEES, TAXES, SEAL FACING. p C 0 N S U L T I N G E N G I N E E R S 13 MANUAL O.B.D.(TYP.) COND.C LED LIQUID LINE a w HEAT COIL TYPE ELECTRIC INSPECTIONS, TESTS, FINES AND OTHER ITEMS AS REQUIRED FOR THE INSTALLATION OF COMPLETE B. ROUND DUCTS SHALL BE WRAPPED WITH R-6 2-INCH BY 3/4 LB BLANKET AS NOTED ABOVE. 9300 NW 25TH STREET #209 MIAMI,`] FL 33172 PITS CH w TOTAL HEATING CAPACITY, KW 10 MECHANICAL SYSTEMS AS OUTLINED HEREIN AND SHOWN ON PLANS. PROVIDE ALL REQUIRED JOINTS SHALL BE SEALED WITH FIRE RESISTING MASTIC AND 3-INCH WIDE FOIL BACKED TAPE. C NUMBER OF STEPS 1 INSURANCE FOR PROTECTION AGAINST PUBLIC LIABILITY AND PROPERTY DAMAGE FOR THE DURATION OF TEL: (305)599-9447 FAX: (30,5 99 9427 ELECTRICAL SERVICE 240-1-60 THE WORK. 2.10 AIR CONDITIONING SUPPLY DUCT ELBOWS SHALL BE PROVIDED WITH APPROVED TURNING VANES. ORLANDO NARANJO, PE #3264Q--_- fi� CT�ICAL QUANTITY AND SIZE (1)20X20 RECTANGULAR ELBOWS EQUAL TO OR GREATER THAN 45-DEGREES SHALL HAVE DOUBLE THICKNESS ID# 65-0479171 _- ;�C',•;.;�, ,k'4 W 1.6 EXISTING CONDITIONS: BEFORE BIDDING CONTRACTOR SHALL VISIT THE JOB SITE AND ASCERTAIN ALL TURNING VANES. ROUND ELBOWS INSIDE RADIUS SHALL BE NOT LESS THAN 1.5 TIMES THE WIDTH OF FACE VELOC. FPM, MAXIMUM/DESIGN 500/350 EXISTING CONDITIONS WHICH WILL AFFECT HIS WORK. FAILURE TO DO SO WILL NOT BE ACCEPTED AS 3 � THE DUCT. = ti U. SOLENOID VALVE TYPE THROWAWAY 3 ., y� r TYPICAL AHU. FAN CHARGING A REASON FOR REQUESTING EXTRA PAY WHERE THE EXISTING CONDITIONS RESULT IN EXTRA MATERIAL Q , DOUBLE PORT VALVE DIMENSIONS/INCHES--W/D/H (REF) 23.5X21 X52 OR LABOR. ANY EXISTING CONDITION FOUND BY THE CONTRACTOR WHICH WILL ADVERSELY AFFECT THE 2.11 BRANCH TAKE-OFFS AND SUPPLY AIR REGISTERS SHALL BE PROVIDED WITH INDIVIDUAL ADJUSTABLE AIR 1 FINISHED CEILING & COIL SECTIONS WORK SHALL IMMEDIATELY BE BROUGHT TO THE ATTENTION OF THE ARCHITECT ENGINEER. CORRECTION SPUTTER MANUAL VOLUME BALANCING DAMPERS. ALL ADJUSTING AND CONTROL HARDWARE SHALL BE u. W FRONT ACCESS SIGHT GLASS DRIER CU / : W/FRONT EXP. UNIT DESIGNATION OF ANY DEFECTS SHALL BE COMPLETED WITHOUT ADDITIONAL CHARGE AND SHALL INCLUDE ACCESSIBLE. ) 0'1`,, ��.: PANELS. VALVE W/ 2 REPLACEMENTS OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION WHICH MAY HAVE BEEN •. y ` CONDENSATE DRAIN EXTERNAL s DAMAGED THEREBY. 2.12 PROVIDE CLAMPED FLEXIBLE CONNECTIONS BETWEEN DUCT AND FAN, DUCT AND MOTOR EQUIPMENT, 'j. FRONT CONNECTED C LOCATION GROUND � , • LINE W/TRAP. SEE EQUALIZER DUCT AND COLLARS, AND DUCT AND SIMILAR EQUIPMENT THAT COULD TRANSMIT AND CAUSE VIBRATION ..-• , ; PLMBG DWGS FOR OPERATING WEIGHT, LBS (REF) 320 1.7 UTILITY COMPANIES: BEFORE SUBMITTING BID CONTRACTOR SHALL CHECK WITH WATER, SEWER, GAS, AND NOISE. � ' REFRIG. LINES. SEE r SCHED. FOR SIZES EXACT SIZE AND DX COIL � MANUFACTURER'S MODEL NUMBER TWE04OE13 ELECTRICAL, TELEPHONE, CABLE TV AND OTHER UTILITY COMPANIES SUPPLYING SERVICE TO THIS ,, LOCATION NUMBER OF COMPRESSORS 2 INSTALLATION TO DETERMINE INSTALLATION STANDARDS AND EQUIPMENT REQUIREMENTS AND COSTS TO FILTER RAILS PROVIDED C 2: o 1 BE INCLUDED IN THE BID. EXCEPT WHERE UTILITY REQUIREMENTS CHANGE AFTER SUBMITTAL, NO W/ AHU 1" THROWAWAY NEOPRENE PAD AIR HANDLING UNIT PITCH w N TOTAL CAPACITY REDUCTION 100/501Q EXTRA PAYMENT WILL BE MADE TO THE CONTRACTOR FOR SUCH ITEMS. PART 3 - EXECUTION FILTER REMOVABLE UNDER UNIT o W TOTAL AMPS, FLA LRA 8 103 THRU FRONT ACCESS ANGLE VALVE o � ELECTRICAL SERVICE 240-1-60 1.8 PLANS: DRAWINGS ARE GENERALLY DIAGRAMMATIC, INTENDED TO SHOW APPROXIMATE EQUIPMENT 3.1 TEST & BALANCE: CONTRACTOR SHALL PROVIDE AND PAY FOR AN NEBB OR AABC CERTIFIED RETURN AIR o e LOCATIONS AND ARRANGEMENTS, NOT TO SHOW EVERY MINOR DETAIL. PLANS SHALL NOT BE SCALED INDEPENDENT CONTRACTOR REGULARLY AND EXCLUSIVELY ENGAGED IN THIS WORK TO ADJUST, TEST AND 4 1 1/2" X 1 1/2" X 1 __ OPENING THRU _ TO DETERMINE EXACT LOCATION AND DIMENSIONS. ( o AMBIENT AIR TEMPERATURE, 95 BALANCE ALL SYSTEMS AS SHOWN ON PLANS. TEST SHALL INCLUDE BUT NOT BE LIMITED TO START- 4 STEEL ANGLE METAL BOTTOM OF UNIT Co z NUMBER OF FANS 1 AND TEST SYSTEM OPERATION IN ALL MODES IN CONJUNCTION WITH OTHER DISCIPLINES, CLEANING OF STAND) �., 1.9 INTERFERENCE: CONTRACTOR SHALL COORDINATE HIS WORK WITH THE WORK OF OTHER TRADES SO THAT UNIT INSIDE AND OUT POLISH ALL CHROME AND ENAMEL FINISHES, REFRIGERANT CHANGE AND PROPER FLOOR a °z TOTAL AMPS, FLA 1.9 INTERFERENCES WITH EXISTING CONDITIONS, CONDUITS, PIPING, EQUIPMENT, ARCHITECTURAL, CONTROLS OPERATION, LUBRICATION, ELECTRICAL SYSTEM TESTING FOR RELATED COMPONENTS, AND REFRIGERANT PIPING DIAGRAM ° ELECTRICAL SERVICE 240-1-60 STRUCTURAL MEMBERS WILL BE AVOIDED. BALANCING OF CFM QUANTITIES. AFTER COMPLETION, PROVIDE THREE (3) CERTIFIED COPIES OF DIMENSIONS INCHES--W D H REF 43X37X40 REPORT, INCLUDING WORKSHEET AND SUBSTANTIATING DATA, TO ARCHITECT/OWNER AND ONE (1) CLOSET MOUNTED AIR N.T.S. REFRIGERANT LINES -- SUCTION & LIQUID 1-1/8" & 318" 1 1.10SHOP DRAWINGS: PRIOR TO PLACING AN ORDER AND BEFORE INSTALLATION, SUBMIT FOR REVIEW CERTIFIED COPY TO ENGINEER. HANDLING UNIT DETAIL PROPERLY IDENTIFIED AND BOUND SHOP DRAWINGS AND MANUFACTURERS LITERATURE GIVING SPECIFICATIONS, DETAILS, COMPLIANCE, UL APPROVAL, MATERIALS, FINISHES, ACCESSORIES AND 3.2 VIBRATION ISOLATION: HVAC AND RELATED SYSTEMS COMPONENTS SHALL BE PROVIDED WITH N.T.S. INSTALLATION DIRECTIONS WHERE REQUIRED OF THE EQUIPMENT SPECIFIED. FACTORY CERTIFIED PRINTS VIBRATION ISOLATION DEVICES AS PER MANUFACTURER'S RECOMMENDATIONS. . SHALL BE FURNISHED FOR ALL MAJOR ITEMS OF EQUIPMENT AND SPECIFIED. SUBMISSION OF EQUIPMENT FOR APPROVAL SHALL BE MADE COMPLETE AND ALL AT THE SAME TIME. 3.3. ALL EXTERNAL EQUIPMENT COMPONENTS SHALL BE FACTORY FINISH PAINTED FOR WEATHER PROTECTION AIR DISTRIBUTION SCHEDULE 1.1 1 SUBSTITUTIONS: PRODUCTS AND MATERIALS CALLED OUT BY TRADE NAME AND/OR CATALOG NUMBERS 3.4 CONTRACTOR ACCORDANCE MAKE ALL NECESSARY L EXCAVATIONS, CUTTING AND REPATCHING AS NECESSARY FOR SYMBOL USE TYPE ACCESSORIES MFG. & MODEL REMARK ESTABLISH A STANDARD OF QUALITY, APPEARANCE,RANCE, PERFORMANCE AND DIMENSION. CONTRACTOR SHALL THE PROPER EXECUTION OF THIS WORK. BASE HIS PROPOSAL ON THOSE ITEMS AS THEY SHALL BE CONSIDERED AS A STANDARD BASIS OF SCROLL TYPE STEEL O SUPPLY CEILING OPPOSED TITUS SIZES AS SHOWM BIDDING. REQUESTS FOR SUBSTITUTIONS SHALL BE SUBMITTED IN WRITING TO THE 3.5 VOLUME CONTROL DAMPERS SHALL BE PROVIDED WHERE INDICATED AND SHALL BE EQUIPPED WITH 5 5 4" DIAM, OUTLET WITH HOUSING WITH WHITE AIR DIFFUSER BLADE DAMPER 250-AA ON PLAN. ARCHITECT/ENGINEER, DEMONSTRATING THAT PRODUCT IS OF COMPARABLE AND BASIC DESIGN, LOCKING ADJUSTMENTS, READILY ACCESSIBLE. VINYL BACKDRAFT DAMPER BAKED ENAMEL FINISH O SUPPLY SIDEWALL REGISTER VERT/HOR TITUS SIZES AS SHOWM CONSTRUCTION STANDARDS AND WARRANTIES, DIMENSIONS TO FIT WITHOUT CHANGE, AND DOES NOT AIR WITH DAMPERS DAMPERS ON PLAN. CAUSE EXTRA WORK FOR OTHER TRADES. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVING EQUALITY 3.6 CONTRACTOR SHALL GUARANTEE THAT ALL PIPE AND DUCTWORK SHALL OPERATE FREE OF VIBRATIONS, ELECTRICAL JUNCTION BOX OF SUBSTITUTIONS; ARCHITECT ENGINEER WILL, UNDER NO CIRCUMSTANCES, BE REQUIRED TO PROVE RATTLES, PULSATIONS OR OBJECTIONABLE NOISES. O RETURN RETURN TYPE RETURN AIR TITUS SIZES AS SHOWM SUCH ITEM IS OR IS NOT OF EQUAL QUALITY TO THE SPECIFIED ITEM. ARCHITECT ENGINEER EXPENSES RETURN AIR GRILL BOX PLENUM 50F ON PLAN. / O AIR INCURRED DUE TO CONTRACTORS REQUESTED REVISIONS OR SUBSTITUTIONS SHALL BE PAID BY 3.7 ALL MATERIALS AND EQUIPMENT SHALL BE NEW AND PROVIDED BY THIS CONTRACTOR. EQUIPMENT CONTRACTOR. REMOVAL FROM THE JOB SITE AND/OR DISPOSAL SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR. 0 COORDINATE WITH OWNER BEFORE COMMENCING WORK. 1.12GUARANTEES: AFTER THE SYSTEM IS INSTALLED, THE CONTRACTOR SHALL CONDUCT AN OPERATIVE TEST FOR APPROVAL AND ACCEPTANCE BY THE ARCHITECT/OWNER. ENTIRE MECHANICAL WORK, INCLUDING 3.8 HVAC SYSTEM COMPONENTS AND EQUIPMENT SHALL BE CLEARLY AND PERMANENTLY IDENTIFIED. PARTS AND LABOR, SHALL BE GUARANTEED FOR A PERIOD OF ONE (1) YEAR FROM DATE OF FINAL WITH EQUIPMENT NUMBER, 2" HIGH LETTERS ON SIDES OF THE UNIT AS APPLICABLE AND IN WRITTEN ACCEPTANCE THEREOF AGAINST DEFECTIVE MATERIALS, CONSTRUCTION AND WORKMANSHIP. ACCORDANCE WITH OWNER'S REQUIREMENTS. WHERE APPLICABLE, LONGER GUARANTEES FOR CERTAIN COMPONENTS SHALL APPLY AS REQUIRED AND NOT BE REDUCED IN ANY WAY. CORRECTION OF ANY DEFECTS SHALL BE COMPLETED WITHOUT 3.9 EQUIPMENT SHALL BE SUPPORTED FROM STRUCTURAL MEMBERS. NO WEIGHT SHALL BE',PLACED ON OpOOp ADDITIONAL CHARGE TO THE OWNER AND SHALL INCLUDE REPLACEMENTS AND/OR REPAIR OF ANY OTHER THE ROOFING MATERIALS, INSULATION, CEILING GRID, ROOF DECKING OR SIMILAR COMPONENTS. 6 O PHASE OF THE INSTALLATION WHICH MAY HAVE BEEN DAMAGED THEREBY. DO 3.10 BEFORE COMMENCING WORK CONTRACTOR SHALL COORDINATE WITH OWNER EXTENT OF WORK WITHIN 6 O 00 1.13RECORD DRAWINGS: MAINTAIN A COMPLETE SET OF PRINTS FOR INDICATING ALL CHANGES. USE AND OUTSIDE BUILDING SPACE TO DETERMINE PROVISIONS REQUIRED. COLORED PENS TO MARK CHANGES AT THE TIME OF EXECUTION AND DELIVER THE SET TO 8" DIAM. 9 BLADED ARCHITECT/ENGINEER UPON COMPLETION. CONTRACTOR SHALL STAMP "AS BUILT" ON PRINTS AND PROPELLER FAN PLANS, DATE AND SIGN IN INK. DIRECTLY MOUNTED TO 1000 RPM MOTOR POLYSTYRENE GRILLE PART 2 - PRODUCTS WHITE COLOR, ALIGNED AND TIGHTENED BY 2.1 EQUIPMENT: CONTRACTOR SHALL PROVIDE FOR A COMPLETE HVAC SYSTEM AS SPECIFIED ON PLANS SINGLE CENTER KNOB INCLUDING BUT NOT LIMITED TO HVAC EQUIPMENT OF THE CAPACITIES SHOWN, DUCTWORK AND AIR DISTRIBUTION, FLUID SYSTEMS, REFRIGERANT AND RELATED SYSTEM LINES, TEMPERATURE AND HUMIDITY REMODELING AND DEMOLITION NOTES TYPICAL CEILING EXHAUST FAN CONTROLS, FILTERS, MOTOR STARTERS, RELAYS, CONTACTORS AND ANY OTHER COMPONENTS REQUIRED. PART 1 - GENERAL N.T.S. SUBMIT SHOP DRAWINGS FOR EQUIPMENT NOTED ABOVE AS REQUIRED. A. AIR HANDLING AND CONDENSING UNIT: INSTALLED ON APPROVED BASES WITH VIBRATION 1.1 ALL WORK AND MATERIALS SHALL BE NEW AND PROVIDED BY THIS ISOLATORS, CONDENSATE DRAIN PAN WITH DUAL CONDENSATE DRAINS, AND STRUCTURAL SUPPORT CONTRACTOR UNLESS OTHERWISE NOTED AS EXISTING TO REMAIN OR BE 7 AS NOTED ON PLANS. CONDENSING UNIT SHALL BE MOUNTED ON SUPPORT FRAME RELOCATED. WORK SHALL ALSO INCLUDE THE REMOVAL AND DISPOSAL 7 RECOMMENDED BY MANUFACTURER AND APPROVED BY RULING AUTHORITIES. OF MATERIALS FROM THE SITE AND THOROUGH CLEANING OF THE l .. z.... ....., ......-_.................:r f ........... ........................, _______ B. HVAC EQUIPMENT SHALL PROVIDED WITH NON CYCLING RELAY BIRD SCREEN RAIN HOOD °•'-�� L t r� - ---- - - AND MANUAL OUTSIDE AIR DAMPERS AS REQUIRED. PREMISES UPON COMPLETION OF THE WORK AS DIRECTED BY .................... ---i ARCHITECT/OWNER. : : 2.2 FILTERS: THROWAWAY TYPE LOCATED IN AIR HANDLER OR AT RETURN AIR GRILL UNLESS OTHERWISE 1.2 WORK SHALL INCLUDE PROVISIONS OF ALL MATERIALS, CUTTING, � ,I NOTED. FURNISH ONE (1) SPARE SET TO OWNER. EXTENSIONS, CONNECTIONS, PATCHING, PAINTING, REPAIRING, ADAPTING AND OTHER WORK INCIDENTAL THERETO, TOGETHER WITH SUCH \� 2.3 REFRIGERANT PIPING: "K" COPPER WITH WROUGHT COPPER SOLDER FITTINGS. INSULATE ALL TEMPORARY CONNECTIONS AS MAY BE REQUIRED. REFRIGERANT SUCTION LINES WITHIN BUILDING SPACES WITH 3/4" ARMAFLEX OR APPROVED EQUAL, / UNLESS OTHERWISE NOTED. 1.3 ANY WORK NOT SHOWN OR SPECIFICALLY MENTIONED ON PLANS AND/OR SPECIFICATIONS BUT CONSIDERED NECESSARY FOR COMPLETION OF THE f`�I, ._:%`,'._L) F'l;.� ; I 2.4 CONDENSATE DRAIN: "M" TYPE COPPER; PVC MAY BE USED FOR OTHER THAN AIR PLENUM WORK IN THE PROPER MANNER SHALL BE PROVIDED BY THIS a 1 :'f INSTALLATIONS WHERE ALLOWED BY RULING AUTHORITIES. CONNECT PIPING FROM UNIT THROUGH A 3- CONTRACTOR WITHOUT ADDITIONAL CHARGE. INCH VENTED TRAP TO DRYWELL OR AS NOTED ON DRAWINGS. INSULATE CONDENSATE RUNS WITHIN (4)110 CFM, 6"D FLEXIBLE DUCT, 12X6 SIDEWALL REGISTERS ATTIC AND OTHER NON-CONDITIONED SPACES. 1.4 WHERE PRESENT WORK IS DAMAGED IN THE EXECUTION OF THIS $ H I CONTROL. RUN CONTRACT, OR WHERE OPENINGS ARE LEFT DUE TO THE REMOVAL OF DUCTS WITHIN EXISTING RAFTER SPACING AS SHOWN. FIELD 2.5 THERMOSTATS: HEAT/OFF/COOL AND FAN/AUTO/ON SWITCHES, TYPE AS REQUIRED PER SELECTED PIPES, EQUIPMENT OR APPARATUS, THE SAME SHALL BE REPAIRED OR $ COORDINATE EXACT LOCATION AND TERMINATION DETAIL WITH HVAC EQUIPMENT MANUFACTURER AND FULLY COMPATIBLE WITH HVAC SYSTEM COMPONENTS CLOSED UP TO CORRESPOND IN MATERIAL, QUALITY, SHAPE AND FINISH EXISTING AREA PRESENTLY ARCHITECT/OWNER. USED. MANUFACTURERS SHALL BE HONEYWELL, BARBER-COLEMAN OR APPROVED EQUAL. MOUNT WITH THAT OF SIMILAR AND ADJOINING WORK, UNLESS OTHERWISE FED FROM EXISTING AHU 1 E �. 5 -6 ABOVE FLOOR UNLESS OTHERWISE NOTED. CALLED FOR. WHERE DAMAGE IS UNREPAIRABLE, NEW ITEMS OR FIELD REVISIONS-REVISED TO REMAIN AS IS EQUIPMENT SHALL BE PROVIDED. PROVIDE ALL NECESSARY 11/21/01 MANUF., FLEXIBLE DUCT i I 2.6 AIR DISTRIBUTION ACCESSORIES: TITUS, AIR GUIDE, METAL-AIRE, OR APPROVED EQUAL. DIFFUSERS WATERPROOFING, FIRE STOPPING AND SEALING OF PENETRATIONS LEFT I - - --... - - - -- -- - - - FROM REMOVED T ,... _.___..___.................._..__.._____..._...-........._______.. _.....________.__....__.........____._,___ ti„ -. SHALL BE ELECTROSTATICALLY PAINTED ALUMINUM AND SHALL BE SUPPLIED WITH MATCHING METAL VED EQUIPMENT OR PRODUCED BY THIS WORK. ff - -- ITEM: �'•� 1 � ,„ , r„ «.--,�,: ,,.>w ,3,»r :r, :_1d F , , -, F,,. ,i,„, ': „ MOUNTING BOOTS, COMPLETELY INSULATED. UNLESS OTHERWISE NOTED, SUPPLY REGISTERS SHALL BE REVISION x�:,•f zr a,.-3:,a; . 1.5 INTERRUPTION OF EXISTING SERVICES AND/OR OPERATION OF FACILITIES I = INSTALLED WITH OPPOSITE BLADE DAMPERS. PROVIDE ADDITIONAL CONTROLS, CONNECTORS, PLENUM / BOXES, ROUND TO SQUARE NECK CONNECTORS AND ADDITIONAL COMPONENTS REQUIRED FOR COMPLETE SHALL BE KEPT TO A MINIMUM. CONTRACTOR SHALL FURNISH ALL INSTALLATION. MATERIALS REQUIRED WHENEVER TEMPORARY CONNECTIONS ARE NECESSARY TO MAINTAIN CONTINUITY OF SERVICE. INTERRUPTION OF EXISTING SERVICES, THE INSTALLATION OF TEMPORARY FACILITIES, AND GARCIA R THE WORK OF MAKING FINAL CONNECTIONS TO THE NEW WORK SHALL BE DONE ONLY AT SUCH TIMES PERMITTED AND SCHEDULED IN ADVANCE BY THE ARCHITECT/OWNER WITHOUT ADDITIONAL COST. CARE MUST BE . : : : : 9 RENOVATIONS • - �, - �.;_, 1 I: T 9 11 1 USED N REMOVING SERVICES TO A : : -�e_p-,Y-may, _ 1 OT H MIGHT BE SERVED THROUGH THESE DEMOLISHED SO THAT SERVICES TO HER AREAS WHICH E '___.G �'.;._,''.-�Pv` AREAS WILL NOT BE INTERRUPTED. 235 FM 10"D 235 FM 10"D PART 2 - MECHANICAL • (EXISTING) (EXISTING) 2 1 �iJ;'�i : L;:: :, i� -.-- - ��� 1 EX I ST f` C =` '"7)T' _--------------------------- NEW" CONDITION; WHERE DAMAGE AND/OR OPERATIONAL RESTRICTIONS 1 !VhN1C_": i i //: i I I C ': 1� _, COMPONENTS WITH EQUAL NEW EQUIPMENT. NENT REPLACE SUCH 5870 S 85th _�'Ioom : : CANNOT JUSTIFY REUSE OF EXISTING COMPONENTS, : i! A. EXISTING DUCTWORK TO BE REUSED SHALL BE THOROUGHLY ----------- ------ � -.11 ----- __ --- i ' ' , r�.T°.J ....Y,.....I : . . -------------_----,-- --"- -''--'"' NOTE: ALL FLEXIBLE DUCT CONNECTIONS CLEANED INSIDE AND OUT. REPLACE WHERE MOISTURE t I ' ' I SHALL BE TERMINATED AT PLENUM BOX SIZED FULLY LOUVERED DOOR FOR - :f I CONDENSATION AND/OR PHYSICAL DAMAGE IS DEEMED STREET ,: : � � r. : : TO TAKE FULL SIZE OF ROUND DUCT AND : : ! ` :1 �.L,.L.. ..R.,.,, 'r_itt,, r=-:r�,_a F.: ---..................... UNACCEPTABLE. AC UNIT RETURN AIR ----- ----------------------- --2;o,� ----------- -- ---__-- --_--------------------- -- , : .� . �� MATCH CEILING OR SIDEWALL REGISTER (TYP) I B. DIFFUSERS AND B CLEANED, AND ' , I I.----__...._-_._-------_-------_--_--.-_.. PA NTED AS REQUIRED EBEFORE LBEVNG REEINSTALLED. I ,: _ : - , 0 , ; , ,;, a, ,...____..., _ 1 C. MOTORS AND VENTILATION FANS SHALL BE CLEANED; AIR M . - 'F,_:.] t c, �z, r a, -_-------- --I THERMOSTAT NEXT TO T - -------- --........ 0„D V f..... ��I_ . ... �� cr t \n ;.,---r�r,'t., f OIL, F : : I � ' ' 1 , , ! I - -: CONDITIONING UN LL H SECTION FULLY LOUVERED R/A ..... ' ' P SECTIONS CLEANED, HEATERS A DN COMPRESSORS SHALL i � : -' ,Or �r z, BEECHECKEDTAND REPAIRED AS REQUIRED; FILTERS IN A/C UNIT. _�_DOOR z .aw. �:?\. c .... � FLORIDA'INCLUDING OUTSIDE AIR SYSTEM SHALL BE REPLACED. D I ! I � i , , �;;`;.` ' ' . - M '" U OOR 2.2 I KING AND CORRECTION AS REQUIRED OF THE FOLLOWING Cs�buri.. "'?-:-.p r.,uE,cx.. de.: - --- . Fc-.1T-N f ,r.-�1`r -n]2?:'i '------ ---- _--- - ----- �` --_ --- - _ / / MP - - _....>� ��_•; - _.�l . ------. :.i .... FLEXIBLOE FDUDCTSL R F.i. +r.. .. UC DOOR i -, - 0 j \ C D �! ,I T : _.. A. 11 i! :€ '� 1 O CONDENSINGL ONL. H LUBRICA EDALLG MOVING PARTSTASDEREQUIRED 1 ;i \ AND RECOMMENDED BY MANUFACTURER. CHECK CONDITION OF I I ' ll I _. ..n.,<.. 250 CFM 10"D ` ON, AND REPLACE AS REQUIRED. CHECK L�Ta` =f j F era E?: . ., 12X10 CD- :.mow=' _.a , � _ ,,,. - REFRIGERANT OPERATING PRESSURES; VERIFY PROPER CHARGE ..'w: • I (EXISTING) --- AHU-2 `- - 1 AND CERTIFY THERE ARE NO LEAKS. : : ' ' \,-, x Z ,; -- B O F . :: I __-__ AIR SIDE: CHECK EVAPORATOR SUPERHEAT. CHECK CONDITION _... ... __ _ V,4.--- '' THE EXISTING DUCTWORK EXISTING MAIN TRUNK AND CLEAN AS I.--� �: �, 150 CFM 8 D 1 �/ }, (`., �, x TIf J'. ,_.,% ` ,' �i REQUIRED. VERIFY TEMPERATURE AT THE RETURN AND SUPPLY : f_ ., X ST 1 . . %f'I 10X8 CD 200 CFM 8"D 1 AIR SYSTEMS MEETS DESIGN CRITERIA CHECK OUTSIDE AIR IS I fC 1f__f (E I ING) 6 C 6 D 12X8 CD- BALANCED ACCORDINGLY. REPLACE EXISTING FILTERS AND 1 i !��\./ % �" 6 6 C °,..,...k -- PRJ. MNGR. DRAWING BY S i :_:e'."wa„"!„`_`: ---------------- -....----- " j 'L_i ---'- -�::::...-- ------ n f " '.--------.i.... - .. _i - : , �. ,-. , '\. -:::::::::::::_::................ - - -- - --- - - - : C. CON ROMSND CHECEK VOLTAGE I AAND AMPERAGE TO ALL MOTORS. X ,� . TI;J ( % 4" 0 ST SURE ` `^ _ ^ y - ` 0 1 R 6X3 DRYER EXHAU HEATERS AND RELATED ELECTRICAL COMPONENTS TO AS SHEET TITLE !• ;: %) '/ v \ 1 : CONCEALED WITHIN A SATISFACTORY OPERATION. CHECK OPERATION OF THE ,1. TE:\ f-C )..,.;� it W LL, ; �. „.: I�.\ /` / _,� F.�., TERMINATED AT EXTERIOR WALL CAP - COMPRESSOR CONTACTOR, START CAPACITOR AND RELAYS. . J.,,x <w :,, _ _, - ,�, _ ° °" '`" " r" - -- CONDENSER BEING REMOVED.PAD UNIT WITHIN(4)1/4"D SS INSPECT THERMOSTAT AND OBSERVE ITS OPERATION H a a CHECK _______- .,�a,.<..l,-�n,.t,.a".. - " yt „ ..T�. ..art:F73. t..w�-.[cw nl:« _ __ -------- .E. - -.., -. •r h. . '-%l:. _ - ___. - ----------..-_... -.-_- _____...._..:....-----. :.-- --------------------------- _ 1-W.Y.,<.::,_-- -_-__-- ;:: BOLTS INBEDDED IN 1-1 2" LEAD ANCHORS PER OPERATION OF ALL SAFETY CONTROLS. CHECK ALL WIRING AND ------.... --------------- _ REMOVE I ROVIDE AHU-2 WITH DUCTWORK AS NOTED. AHU - 1 CONNECTIONS INSIDE THE UNIT. -- - F-- "- MANUFACTURERS RECOMMENDATION. REPLACE EXISTING �, E _ ' %' 5 CFM "D CONDENSER REFRIGERANT LINES SIZED PER HVAC SCHEDULE, D OS DOOR SHALL BE FULLY ED OR AI I 0 ° CONDENSATE VERIFY PANS AND DRAIN LINES ARE OPEN AND SCHEDULE S CL ET. I I CD / ____ RUN WITHIN CEILING SPACE, RUN CONCEALED WITHIN INSIDE FREE OF ALGAE, RUST AND SIMILAR OBSTRUCTIONS, AND THAT =' C ATE FINAL DIFFUSER LOCATIONS WITH ARCHITECT/OWNER. RECONNECT ` "�•' ' � - -- DRYWELL IS OPERATING PROPERLY CLEAN OF EXTERIOR WALL, AND BREAK THROUGH WAS 2" ABOVE SYSTEM AS REQUIRED. AHU-2 TO EXISTING CONDENSATE DISCHARTE WITH 3": VENTED TRAP TO - -; ;/ EXTERIOR CONCRETE PAD, TO TIE TO CU-2. NO SECTION OF �. „ .., \ 1 1 2 CD AT 1 8 LF TERMIN _.r , . : - `� \ ATE EXISTING DRYWELL _�. _ - - : -.. --::: :: _ REFRIGERANT LINES SHALL BE EXPOSED. DETAILS, AND D AT .Ae._Dd....... .Ae�.,,r--.3o.... .F r. ,e .. .1.r .i .. -- / r - - --'..... .. ..::_..-' -- -.. ?."�t -C1 ,S�__,c,. �icr Tr,..,w-L^. I- --.�J F�:V (n f e.': - �.�:'Yz i - --- .�. A,.,_......:-gym =_6.:.1-------- -- : ------- y I. i 2 ---- --- -... - -- ----- --t-- - - ' z., ,T. , o - - -- - - - -. - :::.:..:: III-----IIII IIIIII---- ----; I1 7; 5- c - F.: a -F --j- --- - -...--- -- -- - - - - - ,8" - 12 SPECIFICATIONS EF-1: NUTONE MODEL QT-80, 80 CFM, BACKDRAFT DAMPER, 10OW 12OV. TERMINATE 4"D EXHAUST 8X6 KITCHEN HOOD EXHAUST CU-2 MECHANICAL P L A N DUCT AT ROOF CAP 6" ABOVE ROOF TERMINATED AT WALL CAP-�,v SCALE: 1/4 1 01' : 1 ------------------------------------------- JOB NUMBER SHEET NUMBER N 01001 M-1 DATE - I I 8NOV2000 1 OF 1 A R r n F F C, H I ,I K I M N n