00-1157-001 FIRE ALARM PANEL BATTERY CALCULATIONS ITEM DESCRIPTI❑N STANDBY QTY TOTAL ALARM QTY TOTAL CURRENT STANDBY CURRENT tALARM PER UNIT CURRENT PER UNIT CURRENT (AMPS) PER ITEM (AMPS) j(AMPS) (AMPS) 1 SILENT KNIGHT 5204 0.120 X 1 = 0,120 0.400 x 1 = 0,400 2 SMOKE DETEC""ORS 70 uA X 1 = 0.00007 .060 X 1 = 0.060 APARTMENT APARTMENT = = APARTMENT APARTMENT 3 REMOTE ANNUNCIATOR 0,060 x 1 0.060 0.120 x 1 0.120 4 STR/HORNS NS-241575W -- X - _ -- -- X - _ -- �3 I 5 MINI HORNS 90dBA MIZ -- X 18 = -- 0.012 x 18 = 0,216 6 STROBE/HORNS NS-2411OW __ X 6 = -- 0.195 X 6 = 1.170 -- _ -- -- - ' 7 STROBE 15 CD RS-2415W -- X X - -- /� g 4 2 11 _ -- -- -- _ -- v FMHI — — — — — — — — — — — — — — — — — — — — — T -"/— — :o° — — — — — — — — — — — — — 8 DIALER X -- X— MMH FMHI 9 t t o cd H 110 cd ..� 10 95 dBA H F ..t 26 �3 � 27 7 _,. 10 28 110 cd - - - - - ❑F H 95 50 — — — — — — — — — dBA TOTAL SYSTEM TOTAL SYSTEM ' — — — — — — — — — — — — — STANDBY CURRENT (AMPS) 0.18007 ALARM CURRENT (At4PS) 1.966 MH MF MH MH RA M 12 8 6 5 1 REQUIRED OPERATING TIME OF SECONDARY POWER SOURCE FROM NFPA 72 1-5.2,5 STANDBY 1 24 HOURS ALARM i 5 MINUTE x 1/60 = 0.0833 HOURS v v REQUIRED TOTAL SYSTEM REQUIRED REQUIRED TOTAL SYSTEM REQUIRED LAUNDRY FAP STANDBY STANDBY STANDBY ALARM ALARM ALARM TIME CURRENT CAPACITY TIME CURRENT CAPACITY O 25 (HOURS) (AMPS) (AMP-HOURS) (HOURS) (AMPS) (AMP-HOURS) METER ROOM 24 X 0,18007 = 4.322 0.0833 x 1.966 = 0.164 APARTMENT APARTMENT APARTMENT APARTMENT APARTMENT REQUIRED REQUIRED REQUIRED DERATING MINIMUM STANDBY ALARM AMPERE HOUR FACTOR @ AMP-HOUR CAPACITY CAPACITY BATTERY 1.2 BATTERY (AMP-HOURS) (AMP-HOURS) REQUIRED 4.322 + 0.164 = 4.486 x 1.2 = 5.384 s r LEGEND SYMBOL DESCRIPTI❑N FIRE ALARM CONTROL PANEL 4- FLOO R PLAN =� A SILENT KNIGHT 5204 FOUR ZONES, 24 HOURS EMERG. BATTERY BACK UP POWER SUPPLY FIRST F L O O R MANUAL FIRE ALARM PULL STATION, FIRELITE BG-12 FIRE ALARM HORN/STROBE LIGHT WHEELOCK a EH M❑D # NS- 2430W, 2411OW (WHEELOCK) with High dBA setting (95 dBA) DRAW IN ALARM as shown in the Batteries Backup Calculations Chart FIRE ALARM MINI HORN WHEELOCK IMH RS-24-MIZ 90 dBA WHEELOCK IDRAW IN ALARM 0.012A I t� SMOKE DETECTOR ESL (SENTROL) MODEL 429CT STANDBY uA 70, DRAW IN ALARM 0,060 A APARTMENT APARTMENT APARTMENT =� APARTM ENT - RA REMOTE ANNUNCIATOR lei t 6 23 � 21 1 ,� 14 MH MH THE FOLLO 1,'ING LIFE SAFI ' F1kTUREl, Ito od n s F H tto d IALL BE PROVIDED AT "isSE OF OCCLIPANC'y; 95 dBA'ic' Fwd- 995 1 g rL" �95 8A �� A�-T 22 3 ❑F dBA jr",c� 29 1 Q �c� ���-;r� �r� 2�.� ' 4s � P 6A C_ L 6x MH w �-/ 24 20 18 17 13 SEQUENCE ❑F OPERATION: `rtnv fa a - 1.- IN NORMAL ❑PEP.^TIEIN THE DISPLAY IS BLANK 2.- UPON ACTIVATION OF ANY MANUAL DEVICE (PULL STATI❑N) A DIGITAL NUMBER SHALL SHOW THE ZONE IN ALARM, A LOCAL AUDIBLE SIGNAL SHALL SOUND AND A RED L,E.D, SIGNALING COMMON ALARM SHALL LIGHT AND WILL ACTIVATE GENERAL ALARM THRU THE BUILDING. 3,- IF ANY MANUAL OR AUTOMATIC DEVICE IS DISCONECTED THE APPROPIATE APARTMENT YELLOW L.E.D. SIGNALING TROUBLE WILL LIGHT. APARTMENT APARTMENT APARTMENT APARTMENT ELECTRICAL SYSTEM — GENERAL NOTES 1.- AUDIBLE, VISUAL DEVICE CIRCUITS MUST BE RUN IN SEPARATE CONDUIT 2,- NO A,C, WIRING MAY BE RUN IN ANY CONDUIT WITH ANY D,C, INPUT OR OUTPUT CIRCUIT FROM PANEL. 3.- WIRING SHALL BE TYPE TFN, RUN IN METALIC CONDUIT AS SHOWN ON DRAWING, SHALL COMPLY WITH ART,760 OF N.E.C. AND N.F.P.A.72A AND SHALL BE SIZED AS SHOWN; DETECTI❑N #18 MIN„414 MAX,/ ALARM AND RELEASING DEVICES #16 MIN„#14 MAX,/ POWER WIRING SHALL BE #12 AND COMPLY WITH ART. 310 OF THE N.E.C. 4,- ALL CONDUIT TO BE MINIMUM 1/2' EMT 5,- ALL EQUIPMENT IS 'U,L,' LISTED FOR FIRE SERVICE AND SHALL BE COMPATIBLE. E..- PARALLEL BRANCHING OF AUDIBLE OR INITIATING CIRCUITS (T-TAPPING) IS NOT ALLOWED. 7.- FIRE ALARM CONTROL PANEL IS POWER LIMITED 8,- SYSTEM SHALL BE ELECTRICALLY SUPERVISED WITH TROUBLE ALARM. Cam° 9,- ALL GREENFIELD CONNECTIONS TO BE 1/2' MINIMUM nr 10- FACP TO BE POWERED THROUGH DEDICATED BREAKER FLOOR PLAN if BY SECOND FLOOR ZL SIRE ALARM SYSTEM- _ _ - w�,T�jAi`� ^:�:� :':�,�t�,v� _ DATE � SCALE; 1/8'= 1'-0” 1st. FLOOR 1 2 3 4 5 6 7 8 9 10 11 12 M OUTPUT 1.5 Amp 2 #16 TFN 3 STR/HORN NS-2411OW DRAW= 3 X 0.195 =0.585 rl�i�' r`e.cY57 t 'f'0�� MH MH H MH MH H-4-4-44—” 4.7K EOL 9 MINI HORN 90 dBA DRAW= 9 X 0.012 =0.108 INSTI U ED III ACCO-Ri 1 (;i. ,,V'`- SK-5204 BELL # 1 0 112' M.C. DRAW =0.693 ^• NORTH 24 HAS. BATT, 2nd FLOOR 13 14 15 16 17 18 is 20 21 22 23 24 ,J❑B VALUE LESS THAN _G V(I I ��y5j INC I I -- FIRE OUTPUT 1.5 Amp 2 #16 TFN 3 STR/HORN NS-24110W DRAW= 3 X 0.195 =0.585 BACK-UP MH MH H MH MH MH H MH M H MH MH 4.7K EOL 9 MINI HORN 90 dBA DRAW= 9 X 0.012 =0.108 $ 55,000,00 1 � S W 41 st. ST. ALARM BELL # 2 01/2- M.C. DRAW =0.693 Q ___ PANEL 1st FLOOR 25 26 27 28 2 #16 TFN TOTAL DRAW =1.386 ECA 0012192 13016 S.W. 128TH STREET S F F F 0 1/2' M.C. 4,7K E.O.L. ZONE # 1 (1) S , (3) F Miami, Florida 3 318 6 2nd, FLOOR 119 n° 'nt 2 #16 TFN 4,7K E.O.L. ZONE # 2 (3) S Ph;C305) 971-2944 Fax1C305) 255-8860 +' 0 1/2' M.C. � AREA = 9322 S Q F r SPARE I ��f"M l� N I I I I SPARE 4.7K E.O.L. ZONE # 3 I , I N P� /-\P/-\ 5 `--J ---' 4.7K E.O.L. ZONE # 4 V) Two SUPERVISED, CLASS B, STYLE B CEILINGS ARE FLAT 6470 SW 41st, STREET MIAMI, FL, 33155 M.C. = Metatic Condult FIRE ZONES 120 VAC AND LESS THAN SCALEI //— /— // DRAWN BY) J.F. POWER THROUGH A DEDICATED CIRCUIT 10' HIGH 1/8 -1 0 SITE PLAN D 09-OS-2000 REVISEDI 09 Cj,M, N.T.S. SILENT KNI ❑ H F 5204 CONTROL PANEL WIRIN ❑ DIAGRAM FIRE ALARM AND DETECTI❑N SYSTEM DRAWING No. FIRE ALARM SYSTEM WILT_ LOCAL � LTC. # EC-A0012192 D`; 1