II
. . . . . . . . . . . . . . . . .
3/8'016) METAL SCREWS AT 18' O.C.• r �
— ROOF MOUNTED HVAC EQUIPMENT MOTOR MOTOR COVER
DUCT HOUSING AND BASE WITH PHOTOELECTRIC LENGTH AS REQUIRED TO INSURE
DETECTOR. 120/24VOLTS. TRANSFORMER LOCATED IN FULL DEPTH NAILER PENETRATION.
DETECTOR HOUSING PROVIDE SPACERS AS REHIRED TO ~ ALUMINUM FAN ALUMINUM : Howard Snoweiss
AVAILABLE POWER INPUTS ACCOMMODATE ALTERNATE LOCATION WHEEL DISCHARGE COVER Design Group
1 2 12 13 14
3 14 ( FAN CURB "wr=44
I _ 3/8' BOLTS 305-0 -9131
J NOTES 2X4 W000 NAILER 1/4' NEOPRENE RUBBER GASKET (2) PER SIDE ROOF 906-311-9191
r
CONTINUOUS AROUND PERIMETER
t 24V. 120 --- �} --- --
I VAC I 1. PROVIDE CONDUIT AND WRING IN INTERCONNECT (METAL STUDS WHERE - --s
ALL DUCT DETECTORS FOR MULTIPLE UNITS. IF REQ'D BY LOCAL A.H.J.) - MIN. 1-1/2'. 3 LB RIGID BACKDRAFT AR JOIST
I 220(240 I ANY ONE IS SET OFF ALL WILL ACTIVATE UNIT INSULATION WITH NEOPRENE DAMPER r ' ' ' ' ' ' ' ' ' ' ' ' ' ' ' ' ' r
VA • _:= COATING ON EXPOSED SURFACE EXHAUST DUCT
SHUTDOWN. FASTNERS. 16 O.0
I ALARM AUXILIARY CONTACTS I = FlRESTAT
FOR FAN SHUTDOWN, ETC. 2. ELECTRICAL CONTRACTOR SHALL COORDINATE COUNTER FLASHING
15 16 17 18 19 20 A/C SHUT DOWN WITH MECHANICAL CONTRACTOR. GALVANIZED METAL CURB
COORDINATE I I EXACT ET
SWITCHES AND HORN, WITH THE OWNER AND/OR __ (18 GA. MIN.)
N BASE FLASHING EXHAUST FAN DETAIL
I N.C. C. N.O. N.C. C. N.O. ( ARCHITECT. Nor_
To
FIBER CANT STRIP SECURE CURB TO ROOF WITH scALe 8122.122995
3. THE DEVICE HAS THE CAPABILITY OF BEING SET IN BITUMEN STAINLESS STEEL BOLTS
CONNECTED TO A FIRE ALARM SYSTEM IF REQUIRED. SEE NOTE f10 FOR SIZE AND NO.
ALARM AUXILIARY CONTACTS SHOWN IN ( __: (WELD CURB TO TOP CHORD
STANDBY. CONTACTS TRANSFER DURING 4. 120V CONTROL CIRCUIT REQUIRED. SEE SPECIFICATIONS LIGHT WEIGHT CONCR BUILD UP ROOFING _= AS ALTERNATE METHOD) ALLUMINUM AF
I ALARM AS INDICATED BY THE ARROWS. I FOR ADDITIONAL POWER SUPPLY INFORMATION. (SEE ARCH.) FLUE CAP
.y7yj,,Sx,.' '.`.kc.`. 'YYJM.R• "�`Rx. r',t.. S':*.-•.. ."•'i.t..� y\Vi .Y..e;...+• —_
ALARM INITIATION CONTACTS 5. FOR WIRING OF AUXILIARY DEVICES, REFER TO I I I + "_
1/2" CONDUIT. (NUMBER OF WIRES I I MANUFACTURER'S INSTALLATION INSTRUCTIONS _: SEALANT AS REQ�O .
ACCORDING TO MANUFACTURER) OR CONTACT MANUFACTURER. ^� TO MAKE SYATERTIGHT DOUBLE WALL METAL
80-4�°—�9 ROOF RIGID INSULATI i^�� i/^�� i,^�� i,^�� i^�� TALL CONE FLASHING
FLUE PIPE
IN.O. TROUBLE CONTACTS CLOSED IN STANDBY AND ALARM. (SEE ARCH.) VENT STORM COLLAR W/
CONTACTS OPEN WHILE DETECTOR HEAD OR POWER IS =' INTEGRAL METAL FLANGE
2 (ALARM I 5 (+) ALARM SIGNAL I REMOVED, AND DURING RESET. OPEN CONTACTS - MOP IN WITH ROOFING
EXTINGUISH OPTIONAL APA451 GREEN 'POWER" LED TO r', f`^ UP OVER TALL CONE r n
COMMON 6 INDICATE TROUBLE CONDITION TO PANEL. J01ST WEB - -- ,�''t,r --- _ _ , , --- �,' — --� -- — JOIST TOP CHORD ROOF
V/
RED i (-) AUX POWER I WASHER AND NUT
(FIELD ( 7 (+) AUX POWER I BOLT THRU ROOF SLEEVE ROOF
W/(4) 3/8'0 BOLTED CONSTRUCTION
INSTALLED CONNECTION AS REQUIRED.
-:► JUMPER 1
I GRN N I -Z-}- TROUBLE I ; q
3 POWER 11 CONTACTS TOLFLUE GP PE I& TO NEAREST ,
JOISTS W/STEEL ANGLES
R00 TOP UNIT OTALLATION NOT 8
DH400ACDC DUCT DETECTOR NOTES: 1. SIZE OF OPENING IN ROOF DECK TO BE AS SMALL
APA451 SYSTEM SENSOR' 1. DUCT TRANSITION FROM RTU TO DUCT SIZE SHOWN ON MECH. FLOOR PLAN SHALL BE MADE BETWEEN RTU & TOP OF ROOF WITHIN CURB. AS POSSIBLE. COORDINATE W/STRUCTURAL DWGS. ,
AUDIBLE PIEZO A{ERT MATH ALARM AND
POWER �TROUBLEE LEDS. F?R STAND ALONE 2. SIZE OF OPENING IN ROOF DECK TO BE AS SMALL AS POSSIBLE• 6' MAX. LARGER THAN DUCT SIZE SHOWN. COORDINATE W/STRUCTURAL PLANS. (1' LARGER THAN FLUE DIAMETER MAXIMUM)
APPUCA ONS 0 Y. APA4 1 RECOMMENDED
NORMALLY OCCUPIED AREA OF PREMISES. 3. INSTALL PER MANUFACTURER'S RECOMMENDATION AND INSTALLATION MANUAL 2. FOR ROOF CONSTRUCTION REFER TO H. o'
Tt N LOCATED IN A 4. ALL (RING BY E .
STATION ELECTRICAL CONTRACTOR. .
NORMALLY OCCUPIED AREA .
5. SHIM CURB AS REQUIRED TO PROVIDE HORIZONTAL INSTALLATION OF UNIT WITHIN PRESCRIBED TOLLERANCES A
6. CONTRACTOR SHALL COORDINATE LOCATION OF ROOF CURB WITH STRUCTURE PRIOR TO INSTALLATION. U 2 A FLASHING
I
F NOT To SCALE elss•12299s ; 0 '
7. ROOF CURB BY AIR CONDITIONER MANUFACTURER. PROVIDE ADDITIONAL BRACING AND SUPPORT.
(+� ALARM slcNAl (+) s ALARM ALARM SIGNAL ALARM (+) � , AS REQUIRED FOR ROOF CURB INSTALLATION TO WITHSTAND WIND LOAD PER LOCAL. CODES.
i 8. CURB TO BE HEAVY GAUGE GALVANIZED STEEL CONSTRUCTION AS RECOMMENDED BY MANUFACTURER. ALL FASTERERS SHALL BE
AUX POWER (-) ° AUX POWER (-) ° - QX POWER STAINLESS STEEL OR CHROMIUM PLATED FOR CORROSION PROTECTION :
_ raw
RESET (_)HSr py�, p�, 9. INSTALL CURB TO PROVIDE EQUIPMENT ELEVATION MIN. 12' ABOVE FINISHED ROOF.
_ I _ -+-�
TEST (-) ` n 1 10. FOR A/C UNIT ROOFCURB, PROVIDE 3/8' THRU BOLTS WITH MIN. LENGTH AS DETERMINED BY FIELD CONDITIONS TO ;
DUCT DETECTOR PA400 OPTIONAL) DUCT DETECTOR REMOTE Pop TIONAL) —
oH400acOC REMOTE O� INSURE PROPER ATTACHMENT TO STRUCTURE. PROVIDE ANCHORING AT 18' O.C. OR AS RECOMMENDED BY STRUCTURAL ENGINE ANNUNCI DUCT DETECTOR RTS451/RTS451KEY O
REMOTE STATION LOCATED NEXT OH400ACDC (OPTIONAL) REMOTE
TO THERMOSTAT LED. ALARM INDICATOR TO BE MOUNTED TEST STATION
ON CEILING DIRECTLY BENEATH SMOKE
DETECTOR KEYED REMOTE TEST STATION
LOCATED NEXT TO THERMOSTAT.
OPTIONAL ACCESSORIES (HIRING DIAGRAM
X
HVAC EQUIPMENT
DUCT SMOKE DETECTOR WIPING DETAIL
RV®F CURB DETAIL � N
(WITHOUT A CONTROL PANEL( NOT TO SCALE
NOT To SCALE
SUPPORT STRAP (SUPPORT FROM ;
LOCKING QUADRANT GALV. STEEL ROD OR STRUCTURE) ROOF TOP UNIT
DISCONNECT SWITCH
TO BE EXPOSED STRAP SUPPORTS PER
FLEXIBLE DUCT W 11" SMACNA STANDARDS FACTORY PLENUM WITH INTERNAL BAFFLES
THK. INSULATION & SUPPORT BRACE (16' ON CENTER) '
VAPOR BARRIER- FIBER GALSS OUCTBOARD
MAX. RUN TO BE 8'-0" - WITH R-6 1-1/2" THICKNESS. R/A DUCTWORK S/A DUCTWORK .
NYLON DRAWBAND AND 12' MIN. ;
SPIN-IN TAP FITTING WITH MASTIC AT EACH CONNECTION SHIM CURB AS
TIE TO AIR SCOOP & DAMPER REID TO LEVEL UNIT CURB WIDTH
- � . . . . . . . . . . . . . . . . .
CONTROL CIRCUIT
SUPPORTS TO THERMOSTAT
STRUCTURAL SQUARE TO ;
— _ ROOF OPENING POWER CIRCUIT
I ROUND DUCT TO SERVING PANEL ;
I 2" WIDE METAL BAND ADAPTER CLAMP NOTES ;
j
SUPPORT - \ I SPIN-IN TAP I. DUCT TRANSITION FROM RTU TO DUCT SIZE SHOWN ON MECH. FLOOR PLAN
\ I CEILING SHALL BE MADE BETWEEN RTU & TOP OF ROOF WITHIN CURB.
BOARD I —
/ — GYPSUM BO 2. SIZE OF OPENING IN ROOF DECK TO BE AS SMALL AS POSSIBLE. .
' CEILING / __' 'a ML-39 LINEAR SUPPLY COORDINATE W/STRUCT. DINGS (6' MIN. LARGER THAN DUCT SIZE SHOWN)
-_- �
________-_, ---- ----- -- NOTES: 1. REFER TO ARCH. FOR FRAMING 3. INSTALL PER MANUFACTURER'S RECOMMENDATION AND INSTALLATION
---
� MANUAL . . . .
SQUARE TO 4. ALL WIRING BY ELECTRICAL CONTRACTOR. James Patrick O'Sha hnessy ;
1-1/2" X 1-1/2" X 1/8" GALV. aagg
State of Florida drehitect
ROUND ANGLE OR STRAP PER SMACNA Lim AR 0011651
ADAPTER (� �( M o ;State of Florida interior Designer:
NYLON DRAWBAND AND LOUVERED FACE CEILING DIFFUSER QC CTION AT LINEAR S PoPLY CONNECTION1 TO RTU Howard D. 000031 ss
MASTIC AT EACH CONNECTION
eur12299s Design Croup ,
Coral• 1a. 3W 46
• '
906-46I-9191
TEE HANGING ELBOW,
SUSPENDED TYPE LOUVERED FACE CEILING DIFFUSER
CEILING SYSTEM WITH 2' X 2' LAY-IN ALUM. PANEL
TURNING VANES
HANG ALL DUCT PER SMACNA STANDARDS CORNER ANGLE
CHANNEL : . . . .sue. . . .
TURNING VANES '
TYPICAL DIFFUSER DETAIL ' ' ' ' W ' ' ' '
SPUTTER
DAMPER ;
NOT TO SCALE BLADE
Prime Professional
CHANNEL STRAP & SADDLE . . • . • . . • • . . . . • . .
r
SPUTTER DAMPER CONTROL . . • . • . . . . . . . . . • . .
ROO W/ LOCK
YLA.MU CONSULTING PROJECT #: JU40-or5 r
PROJECT 5UTIAGEIt BRAD HROt1,i
02-28-00
0 0 DETNU�53 HVAC DUCE' DETAILS . . . .DAIS M C� H Q N O CC Q L NOT TO SCALE 441 Clint Moore Rd Baca Raton, . 33 $7 .
� )?bonz �dt�45�$�bt;F'j,1�•$4>G.v�sIb23 :
tD$�t3tt(t`Dg+3 3i1ITt]Id, r
NTS
M7 - 1
-