00-0832-001 C9LMQC 24G3ML HQ)U M
1 All electrical work shall be in accordance with the National Electrical Code and all
w� applicable local codes.
h
p'V �O C CE ❑ 2 Coordinate electrical service with Florida Power and Light.
� Q O �/ ❑❑KER NOE
A13
A15
O
Electrical A 8 3 installation design of this plan is incompliance as set.forth by State of
O Florida statutes model energy efficiency codes.
20
vi O A14 4 the contractor will examine the job site and determine for himself prior to submission
of bid, existing conditions;submission of bid will be taken to mean that he is familiar
g 10'-9' 10'-9' with the site and the work involved and that his final figure represents the lowest
N � C A7 S fixed sum for which he would be willing to undertake the job.
�3'
3 NL'� A9111 A6,8 "
5 All electrical work shall be performed by a licensed electrical contractor. It will be his
Z A14 - _ _ _ _ _ - _ _ 15 responsibility to secure and pay for any and all permits, certificates of inspection, etc.
6 A z 4 A 2 6 A 3 8 A 4 0 4 6 Substitute materials, equipment or methods shall not be made without approval of the
A10 A5 engineer. If the use of a substitute requires any change in work,the necessity for
such change shall be brought to the attention of the engineer, and if approved, shall
M be made at no cost to the owner.
A41 A42 _ r� y
A4 �`- ' � � 7 Clean up such trash and debris generated by the work and leave completed work in a
"``-- Q clean, undamaged, and finished condition ready to receive without further preparation,
unless so specified in other sections, any abutting or adjacent work to be performed
H.S. by others.
A23 r t
25 A 4
g Materials, appliances, devices and equipment shall meet with the requirements of
Underwriter's Laboratories and shall be new and the latest standard products of
". A 4 manufacturers regularly engaged in the production of the item, unless otherwise
A10 / A18 A19 30' indicated. Like item shall be the product of a single manufacturer.
_ g Architectural plans and details shall be referred to for exact location of all equipment;
A4 U, consult with architect and/or owner if any discrepancies are found. Using the scale
on the drawings shall be unacceptable.
-
10 All conductors shall be copper; insulation on conductors sizes through#6 AWG shall
be THHN and THW above#6 AWG, unless otherwise noted. Conductors sizes through
_..
01 #12 AWG shall be either stranded or solid, stranded only for#10 AWG and larger
sizes.
IV
�� ♦� ♦ .
11 Use of PVC, EMT, IMC and other raceways shall be as permitted by the authority
\ r having jurisdiction,
0 ` ci + O
® ' �' y 12 Installation of wall switches shall be as permitted on the basis of one switch per ar
space. p p 9 9
l - 13 Electrical contractor shall be responsible to install thermostats, starters,control
e
TH,
�"► devices, etc.,furnished by the mechanical contractor for the HVAC system, as shown
I + -C],
on control and power diagram for each device.
14 It shall be the electrical contractor's responsibility to verify the load rating of all
devices prior to ordering electrical equipment. Load information on drawing is based
on information provided by_Architect/owner to engineer at the time of the design.
A 17 A 16 16 16 15 Avoid interference and conflict with other trades by proper coordination and timely
communication.
�aa
' PLAN
L
J;.. r_._�.. ..
P'S;.
P/A_.H[RL� Q (EXISTING)
NEW PANEL
LOCATION: WALL MAINS: MLC NEW METER I �
NEW FLUORESCENT FEEDER: 3''p4W 3#3/0 1-1/40 BUS RATING: 225AMP `� , -R��R W A L L I LOAD
LIGHT FIXTURE TO REMAIN MOUNTING: FLUSH VOLTAGE: 120/208 VOLTS ``
FPL
IR POLES
TYPE WIRE KVA COND DESCRIPTION ICIR POLESTYPEWIRE KVA COND DESCRIPTION
EXISTING FLORECENT LIGHTS 1 1 20 12 1.0 1/2 DINE. AREA LGT. 1 2 1 120 12 1.0 1/2 DISPLAY AREA LGT.
3 1 20 12 0.5 1/2 DISPLAY LGT. 4 1 20 12 0.5 1/2 EXIT LGT.
(� DUPLEX OUTLET 5 1 20 12 0.5 1/2 COOLER FAN 6 1 30 10 3.0 1/2 ALK IN COOLER CON,
7 1 20 12 0.5 1/2 HOOD LGT. 8 O
SURFACE MTD. INCANO. LT. 9 2 20 12 2.0 1/2 FREEZER CON. 10 1 20 12 0.8 1/2 KITCHEN LGT. PANEL A
11 12 1 20 12 0.3 1/2 REST. RM. LGT. A
225 AMPS.
13 1 20 12 1.0 1/2 MICO. OVEN 14 1 20 12 1.5 1/2 HOOD VEN.
® EXIT LT. 15 1 20 12 1.0 1/2 TOAS TEV. 16 1 20 12 0.5 1/2 PUBLIC AREA RECPT. 110/208 VOLT
3PH
17 1 20 12 0.5 1/2 RECEPT 18 1 20 12 1.5 1/2 KITCHEN COOLER
MAIN g
EMERGENCY BATTERY BACK-UP LT. 19 1 20 12 1.5 1/2 KITCHEN COOLER 20 SPARE g �>✓>z �� car ��CU� I�I MI -
21 1 20 10 2.0 1/2 ICE MACHINE 22 SPARE F + ANII
225 AM? (��� Af��'
®
TOILET EXHAUST FAN 23 2 40 3 3.5 3/4 DISH WASHER 24 1 20 12 1.5 1/2 DISPLAY COOLER _, A MENT
25 26 1 1 120 12 1.5 1/2 DISPLAY COOLER BY 27 1 20 12 1.5 1/2 COFFEE MACHINE 28 1 20 12 1.5 1/2 SUSHI BAR _ I t°l�t� s tg :'7 DATE
FIRE EXTINGUISHER
29 2 50 13 4.5 3/4 OLD 3 TON A/C 30 2 50 8 8 3/4 EW 5 TON #4 f 14 r ~
31 32 1 r
® 30A 240V RECEPTACLE 4 #3/0 1'-#4- 4 #3101,4_4 '
33 2 50 8 8.5 314 NEW 5 TON A/C 34 1 20 12 1.0 1/2 WASH MACHINE '• ��;st'= "° d�'Zaj
t
35 36 1 20 12 1.0 1/2 COOLER I FI'L L"i�,�i
j)k s
37 1 20 12 1.0 1/2 TEA WARMER 38 1 20 12 1.0 1/2 COOLER � - 0�
39 1 20 12 1.0 1/2 1 NISK 140 1 1 120 12 1.0 1/2 SUSHI BAR w_ -
41 1 20 11'Z 1.0 1/2 1 BRIAM MARIN 142 1 1 120 12 1.0 1/2 1 BRIAM MARIN
LOAD CALCULATION
Total Load:57.1 KVA
FEEDER: 160 AMP 16CX120% = i92< 2254
ELECTRICAL RISER DIAGRAM