00-0355-010 rRLOS
FIGUEROA
HEAT PUMP UNIT SCHEDULE
GAUGE CONNECTION LEGEND UNIT NUMBER EXISTING EXISTING „ NEW H VA C DESIGN REQUIRES. YES NO
AHU-8 AHU-9 AHU-13
.\ & VENT WATER WATER T1�ATER
12x12 TYPE COOLED COOLED COOLED DUCT SMOKE DETECTOR
THERMOMETER WELLS (TYP) CWR RECTANGULAR DUCT INSIDE DIMENSIONS
HEV- HEV-
MODEL N0. HS120
8;6 1000-4 1200-4 FIRE DAMPER(S) •
FLEXIBLE ROUND DUCT INSIDE DIMENSIONS SEE SEE SEE
I BALANCING VALVE ISOLATION AREA SERVED
� . PLAN PLAN PLAN
VALVES CWS -� VOLUME DAMPER SMOKE DAMPER(S)
VD TOTAL AIR SUPPLY 011115 3907 3866
❑ O
FIRE RATED ENCLOSURE
7L�. SUPPLY AIR, CEILING MOUNTED REGISTER OUTSIDE AIR 358FM 280 240 ARCHITECTURE
I FIRE RATED ROOF/FLOOR INTERIOR DESIGN
TOTAL STATIC PRESSURE .G.--- --- CEILING ASSEMBLY
RETURN AIR, CEILING MOUNTED REGISTER --- A R 0 0 0 9 8 4 4
EXTERNAL STATIC PRESSURE W. --- 0.90 FIRE STOPPING 4080 MIAMI 0.90 841h AVENUE
FLORIDA 33155
OT THERMOSTAT 3os 2zo 8e9�
A MOTOR HORSEPOWER HP--- --- 1.00 SMOKE CONTROL
\ \ GAUGE CONNECTION COMBINATION FIRE/SMOKE DAMPER
AC UNIT �✓ & DRAIN FD ELECTRICAL CHARACTERISTICS V/ !�1/Hz 480/3/60 480/3/60 4$0/3/60
0/A OUTSIDE AIR `���,
HEATING CAPACITY >350 117,000 206,666
AIR DISTRIBUTION SCHEDULE
DN. DOWN �' � �������3,y{+ i
J UNION OR FLANGES (TYP) 21,6 f "
S/A SUPPLY AIR MCA/MOCP -- -- 30
SYMBOLS SIZE MFGR MODEL SERIES REMARKS
CWS CONDENSING WATER SUPPLY PIPING GRAND TOTAL HEAT BT /'9fP,500 117,000 124,000
O 24x24 TITUS PAS-AA-OBD-6"- NK SUPPLY h" "4 LL
CONDENSER WATER CONNECTION DETAIL CWR CONDENSING WATER RETURN PIPING TOTAL SENSIBLE HEAT BTU HM,750 91,650 91,000
80 80 40 � B 24x24 SEIHO PAS—AA—OBD-8"— NK
N f D
TS MD MANUAL DAMPER ENTERING AIR TEMPERATURE B/ °F WB 67 67 67 SUPPLY � �,.
HEATING ENTERING WATER a
SD SMOKE DETECTOR WATER TEMPURATURE F C 24x24 TITUS PAS—AA—OBD-14"— NK SUPPLY x
WATER FLOW BRIM 34 32.4 D 24x24 TITUS PAS—AA—OBD-16"— NK .�:
SUPPLY
WATER TEMP. ENT./LEAN. 95 95 !!�95
CLASS 1, NORMALLY CLOSED FIRE/SMOKE MAXIMUM COIL PRESSURE DROP FT. H 2 0 7 6 7
DAMPER WITH AIR FOIL BLADES. EQUAL TO O
RUSKIN MODEL No. FSD-60. PROVIDE A EER / COP 10.3 10.3 11.2
120 VOLT CONTROL MOTOR. FIRE RATED ASSEMBLY 3.3 33 4.0
DESIGN MANUFACTURER FHP FHP CLIMATE
MASTER
2 24x12 TITUS
0 MINIMUM ROWS / MAXIMUM FINS PER INCH 3 14 3 14 .3 14 350FL- AA WITH INSECT SCREEN INTAKE
COMPRESSOR LA --- --- 19.6 0 24x24 TITUS 50E- AA RETURN
I
NOTES: NOTES:
1 1/2"x1 1/2"x1/8" GALVANIZED 1. COMPRESSORS SHALL HAVE A 5-YEAR EXTENDED WARRANTY. �'
ANGLE. FASTEN DAMPER TO 2. A SMOKE DETECTOR SHALL BE INSTALLED IN THE S/A DUCT OF UNIT$ IN ACCORDANCE WITH � I J REFER TO PLAN FOR QUANTITY, LOCATION AND AIR THROW PATTERN.
SLEEVE BY WELDING 6" ON CENTER. GALVANIZED SLEEVE NFPA 90A. SMOKE DETECTORS ARE SPECIFIED UNDER ELECTRICl� . �"� F
(ON ALL 4 SIDES) (SEE NOTE) 3. THERMOSTATIC EXPANSION VALVES SHALL HAVE A BROAD MODULATING RANGE. EXTERNAL j
EQUALIZING LINES SHALL BE TAPPED INTO SUCTION LINES DOWNSTREAM OF THE EXPANSION
xi
VALVE SENSING BULBS. OUTSIDE AIR RECAPITULATION
"S" JOINT COLLAR TO 4. UNITS SHALL HAVE 1" THICK FLAT THROWAWAY FILTERS LOCATED IN UNIT MOUNTED FILTER RACK.
DUCT. (TYPICAL TO BOTH 5. INSTALL UNITS ON EXTERNAL SPRING ISOLATORS.
SIDES OF FIRE DAMPER.) 6. UNITS SHALL BE COMPLETE WITH LOW PRESSURE SWITCH, ANTI-SHORT CYCLE TIMER AND NET. SQ. FT. OUTSIDE AIR TOTAL OUTSIDE
ROOM THERMOSTAT WITH AUTOMATIC CHANGEOVER. UNIT NO. AREA SERVED NO. PEOPLE CFM/PERSON AIR/UNIT (CFM) REMARKS
7. UNITS AHU-1 and AHU-5 ARE EXISTING TO REMAIN. MIN. USED
NOTE: EXISTING
1. SLEEVE TO BE 16 GAUGE AHU-8 --- 17 20 340 358 ��yy
THROUGH 36"x24" AND 14 EXISTING N-1
GAUGE ON ALL LARGER SIZES. AHU-9 --- 14 20 280 280 M� a
2. FIRE DAMPER INSTALLATION NEW O
SHALL MEET U.L. REQUIREMENTS. AHU-13 --- 11 20 220 240
® PL,
LOW VELOCITY SUPPLY
F I R E f S M O K E DAMPER DETAIL
AIR DUCT (SEE PLAN VIEW)
N.T.S. MANUAL VOLUME
DAMPER AIR 1 OUTDOOR AIR PROVISIONS FOR VENTILATION SHALL SATISFY THE MINIMUM
FLOW REQUIREMENTS FOR ACCEPTABLE INDOOR AIR QUALITY PER ASHARE 62-1989. ry
SEAL JOINT
WITH DUCT INSULATE FLEXIBLE DUCT 2 THE FULL VOLUME OF OUTSIDE AIR ESTABLISHED IN THIS SCHEDULE SHALL BE
SEALER & SUPPORT AS REQUIRED DELIVERED TO THE SPACE AT ALL TIMES THAT THE BUILDING IS OCCUPATED W
TAPE FOR NO SAG. MAXIMUM
MANUAL DAMPER VOLUME LENGTH 10'-0 r r
SUPPORT CROSS
ANGLE (2 1/2"x2 1/2"x1/4") DRAW
BAND AIR
b�4
FLOW SPIN COLLAR FITTING WITH
O EXTRACTOR & DAMPER W/
* * DOUBLE LOCKING NUTS } QUADRANT OPERATOR TO BE 12 GAGE (MIN) WIRE---"
(TYPICAL) OUTSIDE INSULATION PROVIDE SUPPORT FROM EXISjIIG
INSULATION GUARD WHERE STRUCTURE 1 1/2" MIN. HANGER STRAPS
INSULATED & VAPOR NECESSARY. SUPPORT FROM EXISTING
SPIN COLLAR W/ SEALED COLLAR & DIFFUSER STRUCTURE (26 GAUGE)
1/2" EXPANTION BOLT DAMPER AND BACK PANEL ,.s !i
INTO EXISTING STRUCTURE HANGER ROD EXTRACTOR SEAL JOINT WITH DUCT M�-I
(3/4"- THREADED) SEALER & TAPE ii ^
DIFFUSER
* A.H.0 BELLOW
a I
FIBROUS DUCT
VIBRATION
ISOLATION /
FIBROUS ROUND
AND FLEXIBLE
* A.H.0 BELLOW *� \�� Revisions
SHEET METAL DUCT
SADDLE MIN.
5-0" ON CENTER 6" MIN.
NOTE:
PLACE SUPPORT AT 8'-0"
(2) 1 1/2" x1 1/2" (12go) ON CENTER FOR D�CTS UP
UNISTRUT GALVANIZED FLEXIBLE DUCT CONNECTION DETAIL TO 35" AND 6'-0'� FOR DUCTS NOTE:
DOUBLE LOCK STEEL ANGLE UP TO 59", AS PER SMACNA HANGERS SHALL BE LOCATED AT
NUTS N.T.S. 2"x2"x1/ " DUCT JOINTS OR AS CLOSE AS
TOP HUNG BOTTON HUNG GALVANIZED POSSIBLE.
CHANNEL
ROUND DUCT SUPPORT DETAIL
A. H. U . HANGER DETAILS RECTANGULAR DUCT SUPPOgT DETAIL N.T.S.
N.T.S.
N.T.S.
I
I
j Job No. Sheet No.
Date
09/09/99
Puga and Associates, Inc.
Engineers/Consultants Drawn by
# EB 0005813 GSR/GLM
4970 S.W. 72 Avenue, #107 Appr. by
Miami, Florida 33155 JDP 1 of 3
(305) 661-7700