00-1329-018 MECHANICAL SPECIFICATIONS FIRE PROTECTION SPECIFICATIONS A DO, A. THIS CONTRACTOR SHALL PROVIDE ALL LABOR AND MATERIAL FOR A A. ALL PIPING AND HEADS SHALL BE INSTALLED PER LATEST EDITION OF NFPA 13. COMPLETE HEATING, VENTILATING AND AIR CONDITIONING SYSTEM AS HEAD SPACING SHALL BE BASED UPON THE ORDINARY HAZARD SCHEDULE. ALL INDICATED ON THE DRAWING AND SPECIFICATIONS, VERIFY ALL CONDITIONS AT SPRINKLER PIPING SHALL BE SCHEDULE 40 BLACK IRON. SCHEDULE 10 PIPING DATE EMIS/ISSUED THE SITE BEFORE SUBMITTING A BID. IS PERMISSIBLE IF ACCEPTABLE TO THE LANDLORD. CONTRACTOR SHALL HYDRAULICALLY CALCULATE SYSTEM AND SUBMIT COPIES OF THE CALCULATIONS NOV. 08, 2000 FOR BIDS, LANDLORD AND ALDO (GC.) B. HVAC WORK SHALL COMPLY WITH THE LATEST EDITION OF THE BUILDING TO THE AUTHORITY HAVING JURISDICTION AND THE LANDLORD. CODES AS WELL AS GOVERNING STATE AND LOCAL CODES. ALL WORK SHALL BE INSTALLED IN STRICT ACCORDANCE WITH THE LANDLORD'S TENANT CRITERIA B. CONTRACTOR SHALL PREPARE SHOP DRAWINGS FOR SUBMITTAL TO THE LOCAL FM DEC. 01, 2000 FOR LANDLORD, BIDS AND STOREFRONT PERMIT AND THE TENANT'S LEASE AGREEMENT. CONTRACTORS SHALL OBTAIN A COPY OFFICE AND THE LANDLORD BEFORE FABRICATION. THE CONTRACTOR SHALL RECEIVE AND COMPLETELY FAMILIARIZE THEMSELVES WITH THESE DOCUMENTS. THEIR APPROVAL BEFORE ANY INSTALLATION CAN BEGIN. DEC. 12, 2000 ALDO (G.C.) & LANDLORD TITION C. CONTRACTOR SHALL PAY FOR ALL REQUIRED PERMITS AND INSPECTIONS AND C. TWO COPIES OF THE APPROVED SHOP DRAWINGS SHALL BE SUBMITTED TO THE T PROVIDE A CERTIFICATE OF INSPECTION UPON COMPLETION. ARCHITECT AND THE LANDLORD PRIOR TO ISSUANCE OF A CERTIFICATE OF JAN. 08, 2001 FOR CONSTRUCTION OCCUPANCY. D. FIVE COPIES OF ALL SHOP DRAWINGS SHALL BE SUBMITTED BY THIS RADIUS ELBOW JAN. 25, 2001 FOR PERMIT ADDENDUM CONTRACTOR. THESE DRAWINGS SHALL BE CLEARLY MARKED INDICATING D. PROVIDE FOR INSPECTION TESTING AND APPROVAL BY THE AUTHORITY HAVING FLOW WHICH ITEMS ARE TO BE SUPPLIED AND SHALL STATE CAPACITIES, SIZES, JURISDICTION AND THE STATE INSPECTION BUREAU AS REQUIRED.REQUIRED INSPECTION LABELS AND GENERAL DESCRIPTION OF ALL EQUIPMENT AND FIXTURES. E. PROVIDE SIGNED CERTIFICATE OF COMPLETION COPIES TO BE GIVEN TO OWNER'S REPRESENTATIVE, INSURANCE REPRESENTATIVE, AND PROJECT OFFICE. L DEPTH OF N DUCT E. THIS CONTRACTOR SHALL GUARANTEE ALL EQUIPMENT AND MATERIAL F. ALL WORK SHALL BE COMPLETED IN ACCORDANCE WITH LOCAL AND STATE BRAN 15 DEG INSTALLED UNDER THIS CONTRACT TO BE FREE FROM DEFECTS FOR A PERIOD CODES WHERE APPLICABLE. OF ONE YEAR FROM THE DATE OF OPENING OF THE STORE. CONTRACTOR SHALL REPAIR OR REPLACE WITHOUT COST TO THE OWNER ANY EQUIPMENT WHICH IS G. SPRINKLER LINES SHALL BE INSTALLED AS HIGH AS POSSIBLE. NO ALARMS OR DEFECTIVE, OR IMPROPERLY INSTALLED. IN ADDITION THIS CONTRACTOR VALUES ALLOWED IN SPRINKLER SYSTEM. TRANSITION SHALL ASSUME FULL RESPONSIBILITY FOR ANY DAMAGE TO THE BUILDING AND TO BRANCH FLOW ITS CONTENTS OR OTHER EQUIPMENT CAUSED BY DEFECTS OR IMPROPER H. SPRINKLER HEADS IN AREAS WITH CEILING SHALL BE CONCEALED TYPE SIZE SQUARE VANED INSTALLATION OF EQUIPMENT OR MATERIALS INSTALLED UNDER THIS SECTION WITH WHITE COVER PLATE. UPRIGHT PENDANT HEADS SHALL BE USED IN ALL ELBOW OF THE SPECIFICATIONS. AREAS WITHOUT A CEILING. SPRINKLER HEAD TEMPERATURE RATINGS SHALL FLOW BE 165F IN SALES AND STOCK AREAS AND 212F IN DISPLAY WINDOWS AND , D TURNING VANES F. FABRICATE AND INSTALL GALVANIZED SHEET METAL DUCTWORK FOR LIGHTING FIXTURE CANOPIES OR AS REQUIRED BY LANDLORD'S INSURANCE VELOCITIES LESS THAN 2000 FEET PER MINUTE AND STATIC PRESSURES OF AGENCY AND LOCAL AUTHORITIES. 30 DEG LESS THAN 2" WATER GAUGE IN ACCORDANCE WITH THE LATEST EDITION OF SMACNA'S LOW VELOCITY DUCT CONSTRUCTION MANUAL. ALL ELBOWS AND 1. SPRINKLER CONTRACTOR SHALL VISIT THE SITE AND VERIFY ALL EXISTING DUCTCH BRANCHES FROM THE MAIN IN ALL SUPPLY AND RETURN DUCTS SHALL BE CONDITIONS WHICH WILL AFFECT THEIR WORK. PROVIDE ALL REQUIRED PIPING FULL DEPTH OF MAIN DUCT PROVIDED WITH TURNING VANES, DUCTWORK SHALL BE CONSTRUCTED, AND OR REVISIONS TO PIPING AS NEEDED FOR A COMPLETE SPRINKLER SYSTEM INSTALLED, SEALED AND INSULATED IN ACCORDANCE WITH THE LATEST WHICH IS APPROVED AND ACCEPTED BY LOCAL AUTHORITIES. EDITION OF THE MECHANICAL CODE. FIBERGLASS DUCTBOARD IS NOT ACCEPTABLE. J. EXISTING SPRINKLER SYSTEM SHALL BE MODIFIED AS REQUIRED TO SERVE THE TRANSITIONS THE NEW LAYOUT SHOWN ON THE DRAWING. SPRINKLER CONTRACTOR SHALL FLOW G, TEST AND ADJUST ALL AIR HANDLING EQUIPMENT TO PROVIDE THE REQUIRED NOTIFY THE MALL MANAGER 72 HOURS BEFORE SPRINKLER SHUTDOWN IS o `'' " AIR VOLUME WITHIN 10% OF DESIGN CONDITIONS. TEST AND ADJUST ALL AIR REQUIRED AND SHALL PAY ALL MALL CHARGES FOR SPRINKLER SHUTDOWN. DEVICES TO THE CFM SHOWN ON THE DRAWINGS. PROVIDE ALL CHANGES N r yid REQUIRED TO OBTAIN CFM QUANTITIES SHOWN ON THE DRAWINGS. TESTING K. SPRINKLER CONTRACTOR SHALL CONNECT TO THE LANDLORD'S EXISTING AND BALANCING SHALL BE BY AN INDEPENDENT TEST AND BALANCING SPRINKLER LINE AND TO CONNECTIONS THAT EXIST IN THE SPACE TO NOTES: .� ' BRANCH DUCT Q. o••r .���r AGENCY IN ACCORDANCE WITH THE PROCEDURES OUTLINED IN THE TESTING ACCOMMODATE THE NEW SPRINKLER LOCATIONS. 1. DETAIL IS APPLICABLE TO SUPPLY AND BALANCING MANUAL AS PUBLISHED BY SMACNA. THE ARCHITECT SHALL . r� SIDE TAP AIR BRANCH DUCT TAKE—OFFS. �,� ',�c3 ��i•'`�' BE PROVIDED WITH THREE CERTIFIED COPIES OF THE AIR BALANCE REPORT L. ALL FIRE PROTECTION SPRINKLER HEADS IN TENANT SPACE MUST BE QUICK BEFORE FINAL PAYMENT WILL BE MADE. PROVIDE THE LANDLORD WITH TWO RESPONSE (OR) TYPE. CERTIFIED COPIES OF THE AIR BALANCE REPORT. �f M. SHOP DRAWINGS AND CALCULATIONS SHALL BE SUBMITTED BY THE CONTRACTOR BRANCH DUCT TAKEOFFS AND TRANSITIONS H. FURNISH AND INSTALL ALL MECHANICAL EQUIPMENT AND OR AIR DEVICES AS FOR THE APPROVAL BY THE OWNER LANDLORD, LANDLORD'S INSURANCE NO SCALE SCHEDULED ON THE DRAWINGS BIDS SHALL BE BASED ON THE EQUIPMENT UNDERWRITER AND THE FIRE RATING INSPECTION BUREAU. e� , �c SPECIFIED AND NO SUBSTITUTIONS WILL BE ACCEPTED. N. TENANT'S FIRE PROTECTION CONTRACTOR SHALL DISCONNECT EXISTING SYSTEM $ � ` I. FURNISH AND INSTALL ALL SYSTEMS OF HVAC CONTROL (TO INCLUDE CONTROL FROM MAIN SYSTEM...PERFORM IS WORK, TEST, RECONNECT TO MAIN SYSTEM...ALL WIRING) TO PROVIDE A COMPLETE SYSTEM. ALL SYSTEMS SHALL BE COMPLETE COST RELATED TO DRAIN DOWN AND FILLS ARE TO BE BORNE BY TENANT'S FIRE AND INSTALLED BY THIS CONTRACTOR. PROTECTION CONTRACTOR. J. PAY FOR ALL PERMITS AND INSPECTIONS AND PROVIDE CERTIFICATES CONTRACTOR'S GENERAL NOTES 1 DEC. 12, 00 AS PER ALDO & LANDLORD COMMENTS OF INSPECTION. K. ALL PENETRATIONS OF FLOOR SLAB SHALL BE SAW CUT, GROUTED, AND SEALED 1 ALL OF THE MECHANICAL WORK IS NOT NECESSARILY SHOWN OR NOTED ON THESE DRAWINGS. THE CONTRACTORS SHALL VISIT THE JOB NO. DATE REVISION WATER PROOF. SITE AND VERIFY ALL EXISTING CONDITIONS RELATED TO THEIR WORK BEFORE D BUT WHICH ARE DEEMED CONTRACTOR MUST VERIFY ALL BIDDING. THOSE ITEMS NOT SHOWN OR NOTE L. THIS CONTRACTOR SHALL PROVIDE ALL LABOR AND MATERIAL FOR A COMPLETE NECESSARY FOR REMOVAL OR RELOCATION D OWNER'S REPRESENTATIVE DETAILS, SPECIFICATIONS AND PLUMBING SYSTEM AS INDICATED ON THE DRAWINGS AND SPECIFIED HEREIN. FIELD SHALL BE PART OF THIS CONTRACT. DIMENSIONS, AND REPORT ANY VERIFY EXISTING CONDITIONS PRIOR TO SUBMITTING BID. DISCREPANCIES TO OWNER M. PLUMBING WORK SHALL COMPLY WITH LOCAL AND STATE CODES AND 2. THE SUBMISSION OF PROPOSALS SHALL BE CONSIDERED EVIDENCE THAT THE BEFORE PROCEEDING WITH WORK THE LEASE AGREEMENT. CONTRACTORS HAVE VISITED THE SITE. NO EXTRA PAYMENTS WILL BE ALLOWED THESE CONTRACTORS CLAIMS FOR EXTRA WORK MADE NECESSARY Adifica N. FURNISH AND INS)TALL STANDARD WEIGHT CAST IRON SOIL PIPE WITH "NO—HUB" BY THEIR FAILURE TO VISIT THE SITE. St-LouicaCase real FITTINGS FOR ALL WASTE AND VENT PIPING ABOVE GRADE AND SERVICE �FdwkinWilam WEIGHT CAST IRON PIPING WITH APPROVED COMPRESSION JOINTS UNDER FLOOR. 4. EACH CONTRACTOR SHALL WARRANTY THEIR WORK FOR 1 YEAR FROM THE t7251.is,M William case St-Louis,MO 63026 OPENING DATE OF THE STORE. T 636 349-1600 0. INTERIOR WATER PIPING ABOVE THE FLOOR SHALL BE TYPE L WITH 95-5 SOLDERED JOINTS. VALVES SHALL BE NIBCO S-590 BALL VALVES OR EQUIVALENT. F 636349-1730 www.acdifica.com WATER PIPING TO 125 LBS. FOR AT LEAST TWO HOURS WITH NO LEAKS 5• ALL CONTRACTORS SHALL COMPLETE THEIR WORK ACCORDING TO STATE AND ww.acdifica.com E N G I N E E R I N G BEFORE COVERING. INSULATE HOT AND COLD PIPING ABOVE THE FLOOR WITH I" OR LOCAL CODES. - - -- -^ THICK FIBERGLASS INSULATION WITH ALL SERVICE JACKET. NO PLASTIC PIPE ALLOWED. 6. CONTRACTOR SHALL REVIEW ALL LANDLORD REQUIREMENTS AND INSTALL ARCHITECTURE + D E S I GIN P. THIS CONTRACTOR SHALL CAP ALL UNUSED PLUMBING LINES ASSOCIATED WITH THE ALL MATERIALS AND EQUIPMENT AS DIRECTED BY THE LANDLORD'S REPRESENTATIVE AND AS REQUIRED BY THE LEASE DOCUMENTS. Montreal-st-Louis d *lfica LEASED SPACE AS REQUIRED BY THE LANDLORD AND LOCAL INSPECTION AUTHORITIES. CONTRACTORS SHALL VERIFY THE REQUIREMENTS BEFORE SUBMITTING THEIR BID. 1lsdifiealnc. 4521 rue Clark Suite 300 Montreal[Qu6bec] Canada 112T 2T3 T 514 844-6611 F 514 844-7646 www.aedirca.com APPENDIX Ar1--SGFIEDU LE,4F'PIPING"SYSTEM MATFIRI kL9 -- - - (b)11) � G�pUPF q` Seib Sub-pprP6pPh 4004►1 O v O b. 4 RQuFARKS: A [itiftCtines 4r►Y- IL Each job must be apj mvW by Plumbing rL y` ° 5 4 OmIciat Barosilir.et Ose p�pt'—ugh 3il5ppn r' ¢ e —_ eaetiron. _ ti�'9�pp C. fkt'AA54, a zt o0 4 Ir D. f4bava ground tan K 4 ° a a d HODGE - a ad tw lacatloar or was shown. Is - 1 g 9 rc I y _ U J64 8 M V9 0 E ST E LA UU R E N T �• QUEBEC, CANADA H4N 263 w 1 °� 906 a 1 a d m LOCAT1014 OR Mic 0 U 1 t� # s �' l ' i ° a a 4 (514) 747-2536 n wale(smfoc x X X x X X1 Ix X D D X-1 x X Z FAX: (514) 747-7993 1610ter 6007 A%V16butioa SVatam In Build X X I a4 X x I I X X D DI I Abbe round Draln,Wesze a Vent in SUIding I x x X1 ixlxlx x x x x X K X X x PROJET/PROJECT: Vmde•gmand Drain,Wame S vent in auifding X x x I X1 Ix x X X X Chemical&Ack!Draln,Waste&vent CIO c ALDO space 154 R'urnvalar Leaders x x x x x x x x x x X X K x X Sawm&$,,mil ovains X X x x x x x x x x x x SHOPS AT SUNSET PLACE aas> Pmy x x C ssk%immii Pot,l Rai B a X. x x x x x x SOUTH MIAMI, Wells X x TITRE TITLE: Lawn Sprinklers S Irrio0on X x x K x �{ SPECIFICATIONS & DETAILS Wplk:Tank TVht Lines x X x X X x x Underground Fire Sling ipe ta x Above Smund ma Slaf4 ipe PROJET N0./PROJECT N0. DESSIN DRAWN: BuIldIn Howe Sewer X X X x K x ASPM-01 -00 S. . ? 00 cordeneale Drains K X X X x 7€ x x x x x ECHELLE/SCALE: VERIFIE/CHECKED: NOTE.See Paragraph 4402.2(c)fcr uncergr4oura plpng and 4elere,ivus fill, 1/41) — 1 1-0)) _ P.C. DATE: PAGE: H:\2—Comm\Aldo\Shops at Sunset Place\ARCHITECTURAL\DESSINS\GENERAL\U612_E1.dwg NOV 01 , 2000 1 M2 PLOT TIME:NOV 01, 2000 [16:25]