Loading...
00-0833-018 f e MECHANICAL SPECIFICATIONS 1. 0 GENERAL 7 03 NEW CEILING DIFFUSERS WITH A 12' X 12' FACE SHALL BE PERFORATED FACE, 13, 03 PR❑VIDE INSULATING SADDLES FOR INSULATED LINES AT EACH PIPE SUPPGRT 1. 01 PR❑VIDE COMPLETE, PROPERLY FUNCTIONING SYSTEMS CURVED BLADE, 1, 2, 3 OR 4-WAY DEFLECTORS 'WITH A FRAME AS REQUIRED TO THE INSULATION SADDLE SHALL BE 16 GAUGE GALVANIZED STEEL INSTALLED 1. 02 DRAWINGS ARE DIAGRAMMATIC PRODUCE ACCURATE SHOP DRAWINGS AND PROVIDE SUIT THE CEILING TYPE. DIFFUSERS SHALL HAVE AN 8' X 8' SQUARE NECK BETWEEN HANGER AND INSULATION AND SHALL BE TWICE AS LONG AS OUTSIDE MINOR COMPONENTS REQUIRED TO OBTAIN COMPLETE AND PROPER SYSTEMS, DIFFUSERS SHALL BE PROVIDED COMPLETE WITH OPPOSED BLADE DAMPERS SUCH DIAMETER OF INSULATI❑N 1. 03 MANUFACTURER' S NAMES ESTABLISH TYPE, CLASS AND QUALITY AS TITUS MODEL AG-95-AA. THE CEILING DIFFUSERS SHALL BE SUCH AS TITUS 14, 0 CONTROLS 1. 04 COORDINATE ALL WORK WITH OTHER TRADES MODEL PCS-AA. 14. 01 GENERAL, PROVIDE ELECTRIC, ELECTRONIC OR COMBINATION CONTROLS FOR 11 05 ALL COMPONENTS SHALL BE STANDARD CATALOGED PRODUCTS OF APPROVED U. S. 7. 04 PR❑VIDE AIR VOLUME EXTRACTORS AT ALL RECTANGULAR BRANCH DUCT TAKE- NEW EQUIPMENT. MANUFACTURERS, SUBSTANTIATED BY PUBLISHED DATA; SHALL ESSENTIALLY OFFS AIR VOLUME EXTRACTORS SHALL BE CAPABLE OF PROVIDING A COMPLETE 14, C2 ROOM THERMOSTAT SHALL HAVE INTERNAL SETTINGS, PLAIN CASING AND DUPLICATE EQUIPMENT AND MATERIALS THAT HAVE BEEN IN SATISFACTORY USE SHUT-OFF AND SHALL BE EQUIPPED WITH A MANUAL OPERATOR WITH GRADULATED ADJUSTABLE DIFFERENTIAL, FOR A PERIOD OF TWO YEARS, AND SHALL BE NEW AND FREE FROM DEFECTS DIAL TYPE INDICATOR AND LOCKING OUT MOUNTED IN AN ACCESSIBLE 14, 02 ALL TRANSFORMERS AND CONTROL DEVICES FOR ELECTRIC AND ELECTRONIC 11 06 WHERE CONTACT OF DISSIMILAR MATERIALS MAY CAUSE CORROSION OR LOCATION. AIR EXTRACTORS SHALL BE FACTORY FABRICATED AND ASSEMBLED, CONTROLS SHALL BE PROVIDED. ELECTROLYTIC ACTION, SEPARATE MATERIALS BY MEANS OF SYNTHETIC RUBBER EXTRACTORS SHALL BE TITUS MODEL AG-45 WHERE LENGTH OF EXTRACTOR 14. 03 ALL WIRING REQUIRED FOR ELECTRIC AND ELECTRONIC CONTROL SYSTEMS SHALL International OR PLASTIC GASKETS, GROMMETS AND ISOLATION FITTINGS, AS REQUIRED EXCEEDS 12' , PROVIDE A TITUS XY-02644-1 ROLLER SUPPORT BE FURNISHED AND INSTALLED UNDER THE SECTION, ELECTRICAL WORK THIS 1 07 CODES AND STANDARDS, ALL WORK SHALL CONFORM TO THE REQUIREMENTS OF 8, 0 WATER COOLED HEAT PUMP CONTRACTOR SHALL PROVIDE COMPLETE DIAGRAMS AND INSTRUCTIONS AS Design Partnership THE FOLLOWING STANDARDS AND CODES AS MODIFIED BY LOCAL ORDINANCES, 8 01 UNIT SHALL BE FACTORY ASSEMBLED; ARRANGEMENT, TYPE AND CAPACITY OF REQUIRED FOR INSTALLATION UNDER THAT SECTION A, NFPA 90A - AIR CONDITIONING AND VENTILATION SYSTEMS EACH COMPONENT SHALL BE AS SHOWN AND SCHEDULED ON THE DRAWINGS, UNIT 15 0 CONTROL SYSTEM OPERATION Incorporated B. SOUTH FLORIDA BUILDING CODE. SHALL BE COMPLETE WITH CENTRIFUGAL FANS, OPEN SQUIRREL CAGE FAN 15 01 WATER COOLED HEAT PUMP UNIT, C. UNDERWRITERS' LABORATORIES MOTOR, HERMETIC COMPRESSOR, MAGNETIC STARTERS, COAXIAL TUBE A, NEW AIR CONDITIONING SYSTEM SHALL BE CONTROLLED FROM FULLY D. SMACNA CONDENSER, EXTENDED SURFACE COOLING COIL WITH COPPER TUBES AND AUTOMATIC PROGRAMMABLE THERMOSTAT LOCATED AS SHOWN, E. ASHRAE ALUMINUM FINS AND 1' THICK THROWAWAY FILTERS B ON CALL FOR COOLING FROM THE ROOM THERMOSTAT, THE COMPRESSOR 30 W, NTashta Drive F. NFPA 13 - INSTALLATION OF SPRINKLER SYSTEMS 8. 02 ALL COMPONENTS OF UNITS SHALL BE ENCLOSED IN A SUITABLE APPARATUS SHALL BE ENERGIZED, Key Bisca�rle, F1 331 I9 2 0 SPECIAL CONDITIONS CASING CONSTRUCTED OF STEEL PANELS WITH STEEL ANGLE FRAMING OR C SYSTEM SHALL CHANGE FROM COOLING TO HEATING AUTOMATICALLY WITH A 2. 01 ALL PROPOSALS TO PERFORM WORK UNDER THIS SPECIFICATION SHALL BE BASED BRACING WITH PROPERLY LOCATED ACCESS DOORS FOR INSPECTION AND 2 DEGREE DEADBAND IN BETWEEN ON CALL FOR HEATING FROM THE ROOM Tel: 305.360.8338, Fax� 305.3618339 ON A THOROUGH INVESTIGATION OF ACTUAL CONDITIONS AT THE JOBSITE, AND MAINTENANCE, CASINGS SHALL BE LINED THROUGHOUT WITH FIRE-RETARDANT THERMOSTAT, THE ELECTRIC REVERSING VALVE SHALL BE ENERGIZED E-mail: IDPmiaCaao1,com SHALL INCLUDE ALL WORK REQUIRED TO INTR❑DUCE SYSTEM COMPONENTS INTO SYNTHETIC RUBBER-COATED GLASS FIBER INSULATION, COATED SIDE OF 16 0 FILTERS EXISTING STRUCTURES, AND TO CONNECT TO OR MODIFY EXISTING SYSTEM AS INSULATION SHALL BE THE EXPOSED SIDE. 16 01 PROVIDE ONE SET OF THROWAWAY FILTERS TO BE USED DURING CONSTRUCTION,--- -- NECESSITATED BY THE INSTALLATION, ALL SUCH WORK SHALL BE PERFORMED 8 03 COOLING COILS SHALL BE PROVIDED WITH AN ADEQUATELY INSULATED STEEL FILTERS SHALL BE VISCOUS IMPINGEMENT TYPE, WITH GLASS FIBER MEDIA AND o I� L E Date WITHOUT ADDITIONS TO THE CONTRACT COST . `"' DRAIN PAN. DRAIN PAN SURFACES SHALL BE TWO GAGES HEAVIER THAN THE DISPOSABLE FRAMES; THICKNESS OF MEDIA SHALL BE 1' AS STANDARD FOR THE - 2, 02 WHERE INDICATED EXISTING SYSTEM COMPONENTS SHALL BE CAREFULLY REMOVED UNIT CASING UNIT MANUFACTURER OR RELOCATED, EACH RESULTING OPENING IN THE BUILDING STRUCTURE SHALL 8. 04 ALL STEEL SURFACES SHALL BE PROVIDED WITH AN APPROVED CORROSION 16 C2 NEW FILTERS ARE TO BE INSTALLED IN THE UNITS PRIOR TO FINAL TEST AND - BE PROPERLY PATCHED AND FINISHED WITH THE SAME MATERIALS AS THOSE RESISTANT COATING, BALANCING THESE FILTERS SHALL ALSO BE THROWAWAY TYPE AS SPECIFIED ADJACENT TO THE OPENING 8, 05 THE ENTIRE UNIT, INCLUDING THE FILTER SECTION SHALL BE INSULATED ABOVE, PROVIDE ONE ADDITIONAL COMPLETE SPARE SET OF FILTERS TO BE 3 0 SHOP DRAWINGS ADEQUATELY TO PREVENT EXTERIOR CONDENSATION. USED AFTER TEST AND BALANCE 3 01 SUBMIT COPIES OF THE FOLLOWING SHOP DRAWINGS, 81 06 WATER COOLED CONDENSERS SHALL BE COAXIAL TUBE DESIGN, CONDENSERS 17. 0 VIBRATION ISOLATORS A, DETAILED INFORMATION FOR ALL EQUIPMENT, DAMPERS, ROOF VENTS, AIR SHALL HAVE A PRESSURE RELIEF VALVE AND LIQUID LINE VALVE, CONDENSERS 17. 01 VERTICAL WATER COOLED HEAT PUMP SHALL BE INSTALLED ON RUBBER DISTRIBUTION DEVICES AND AUXILIARIES SHALL BE EQUIPPED WITH A LIQUID SUBCOOLER AND SHALL BE DESIGNED FOR ISOLATION PADS SUCH AS MODEL RV-1 AS MANUFACTURED BY THE AMBER/BOOTH ---- B DETAILED LAYOUTS OF EACH EQUIPMENT AREA, SHOWING ALL EQUIPMENT, 300 PSIG REFRIGERANT SIDE PRESSURE AND 150 PSIG WATER SIDE PRESSURE, COMPANY OF HOUSTON, TEXAS, PIPING AND DUCTWORK, EACH REFRIGERANT CIRCUIT SHALL HAVE A SEPARATE CONDENSER 18 0 GUARANTEE C COMPLETE COMPOSITE DIAGRAMS, DESCRIPTIONS AND SEQUENCE OF 8. 07 COMPRESSORS SHALL BE HERMETIC TYPE AND SHALL HAVE CRANKCASE HEATERS 18 01 ALL EQUIPMENT SHALL BE GUARANTEED TO HAVE THE SPECIFIED CAPACITIES _ OPERATION FOR CONTROL SYSTEMS IN THEIR ENTIRETY, SHOWING THE 8. 08 MOTOR-COMPRESSORS SHALL HAVE A 5 YEAR EXTENDED WARRANTY, AND TO OPERATE WITHOUT OBJECTIONABLE NOISE OR VIBRATION UNDER SPECIFIC EQUIPMENT FURNISHED, 8, 09 THERMOSTATIC EXPANSION VALVE SHALL HAVE A BROAD MODULATING RANGE INSTALLED CONDITIONS. D COMPLETE DETAILS OF ALL HANGERS, SUPPORTS AND VIBRATION EXTERNAL EQUALIZING LINES SHALL BE TAPPED INTO SUCTION LINE 1B. C2 PROVIDE A WRITTEN WARRANTY COVERING ALL EQUIPMENT, MATERIALS AND ISOLATORS. DOWNSTREAM OF THE EXPANSION VALVE SENSING BULB WORKMANSHIP FOR A PERIOD OF ONE YEAR FROM THE DATE OF FINAL 3. 02 SHOP DRAWINGS SHALL INCLUDE CAPACITIES, OPERATING PRESSURES AND 91 0 CONDENSER WATER PIPING ACCEPTANCE OF BENEFICIAL USE BY THE OWNER, WHICHEVER IS EARLIER; THIS TEMPERATURES, SERVICE RATINGS, SOUND POWER LEVELS, PHYSICAL 91 01 PIPE AND FITTINGS, ALL CONDENSER WATER PIPING SHALL BE TYPE L HARD SHALL INCLUDE AN AGREEMENT TO REPLACE ALL DEFECTIVE EQUIPMENT OR STRUCTURE, WEIGHTS, AND DIMENSIONS AS REQUIRED, ALL PERFORMANCE DATA DRAWN COPPER TUBING WITH CAST BRONZE FITTINGS AND SOLDER JOINTS MATERIALS AND REPAIR ALL DEFECTIVE WORKMANSHIP DURING THE WARRANTY AND DIMENSIONS SHALL BE CERTIFIED BY THE MANUFACTURER WITH AUTHORIZED FURNISH AND INSTALL DIELECTRIC COUPLINGS OR UNIONS AT ALL CONNECTIONS PERIOD WITHOUT COST TO THE OWNER.------- _ __ _ FACTORY SIGNATURE. BETWEEN DISSIMILAR METALS ALL ELBOWS THROUGHOUT PIPING SYSTEM SHALL 18, 03 THE FIVE-YEAR FACTORY WARRANTY ON EACH MOTOR-COMPRESSOR SHALL BE CLIENT .APP R0�'�L 3, 03 NO EQUIPMENT OR MATERIALS SHALL BE PURCHASED OR INSTALLED PRIOR TO BE LONG RADIUS TYPE, FILLED OUT IN THE OWNER' S NAME AND GIVEN TO THE OWNER PRIOR TO FINAL FINAL APPROVAL OF SHOP DRAWINGS 9, 02 GATE, GLOBE AND ANGLE VALVES, ALL GATE, GLOBE AND ANGLE VALVES SHALL ACCEPTANCE OF WORK PERFORMED UNDER THIS SECTION I have reviewed these plans and l=ave 'peen 4 0 TESTING AND BALANCING BE DESIGNED FOR A WORKING PRESSURE OF 175 PSI WOG. VALVES 2-1/2' AND Qiven the opportunit to ask questions abo it 4 that 01 SUBJECT THE COMPLETED SYSTEM AND ALL COMPONENTS THEREOF TO OPERATING LARGER SHALL BE IRON BODY, BRASS-TRIMMED, WITH BOLTED BONNET AND them pr to issue These plans that a m to our recuirements. I understand nv TESTS, AS SPECIFIED HEREIN, AND AS REQUIRED TO DEMONSTRATE FLANGED ENDS; 2' AND SMALLER SHALL BE ALL BRASS, WITH SOLID WEDGE modificatlions to these plans will be an ACCEPTABILITY OF SYSTEMS, TESTS SHALL BE PERFORMED BY AN APPROVED DISCS, GLOBE AND ANGLE VALVES SHALL HAVE PLUG TYPE DISCS AND additional service `cith potential impact on AGENCY AND AT THE CONTRACTOR' S EXPENSE RENEWABLE SEATS ALL VALVES SHALL BE DESIGNED TO ENABLE RE-PACKING construction cost and scheduling. 4 02 RECORD AND TABULATE ALL DATA NECESSARY TO DEMONSTRATE THE CAPACITY OF UNDER PRESSURE WHEN WIDE OPEN. ACCEPTED as IS EACH NEW SYSTEM COMPONENT UNDER ACTUAL OPERATING CONDITIONS DATA 9, 03 BALANCING VALVES, ALL BALANCING VALVES SHALL BE DESIGNED FOR A — :ACCEPTED as NOTED FOR EACH ITEM OF EQUIPMENT SHALL BE RECORDED SIMULTANEOUSLY WITH DATA WORKING PRESSURE OF 250 PSI WOG MINIMUM VALVES SHALL BE FURNISHED FROM ALL ASSOCIATED EQUIPMENT, TOGETHER WITH COINCIDENT OUTSIDE AIR WITH AN ADJUSTABLE OPEN-POSITION STOP VALVES 2-1/2' AND LARGER Signature, Date: DRY BULB AND WET BULB TEMPERATURES DATA SHALL INCLUDE, SHALL HAVE FLANGED ENDS; 2' AND SMALLER SHALL HAVE SCREWED ENDS A, SUPPLY, RETURN AND OUTSIDE AIR QUANTITIES FOR NEW AIR VALVES SHALL BE TOUR & ANDERSSON MODELS STAD OR STAF, - _------- _ CONDITIONING UNIT. 9, 04 FURNISH AND INSTALL DIELECTRIC COUPLINGS OR UNIONS AT ALL CONNECTIONS -- B AIR VOLUMES AND VELOCITIES FOR NEW AIR CONDITIONING UNIT FAN, BETWEEN DISSIMILAR METALS COOLING COIL AND AIR CLEANING ASSEMBLY. 9. 05 AIR VENTS, PR❑VIDE APPROVED AIR VENTS AT ALL HIGH POINTS IN all drawings and written ma-en: l here.n, as instr invents C ENTERING AND LEAVING AIR DRY BULB AND WET BULB TEMPERATURES FOR CONDENSER WATER SYSTEM; VENTS SHALL BE AUTOMATIC TYPE UNLESS of service. shall remain. t~e property of ln.erna Tonal NEW COOLING COIL, OTHERWISE INDICATED, AUTOMAT I C AIR VENTS SHALL BE ALL-BRASS, WITH 3esi_n Partnership, Inc. (IDFI and shall not Je reproduced D. ENTERING AND LEAVING WATER TEMPERATURE AND PRESSURE FOR NEW SELF-CLOSING FLOAT-OPERATED VALVE, DESIGNED FOR 150 PSI WWP, MANUAL w coped, '_n whole or in par , without the expressed titi�ritten consent of IDP and may not be used or WATER COOLED CONDENSER, AIR VENTS SHALL BE BRASS PLUG COCKS, DESIGNED FOR A WORKING PRESSURE referenced nor anv other project n'formaticn contained E AIR VOLUMES AND VELOCITIES AT EACH INLET AND OUTLET, OF 125 PSI WOG, PROVIDE EACH AUTOMATIC AIR VENT WITH A 1/4' OD SOFT herein represents proprietary informat'on of International F MEASURED VOLTAGE AND CURRENT INPUT FOR NEW MOTOR COPPER TUBING BLOW-OFF CONNECTION EXTENDED TO NEAREST FLOOR DRAIN OR Design Partnership and/or its CIIea and shell not be 4, 04 SUBMIT TEST DATA FORMAT FOR APPROVAL PRIOR TO BEGINNING OF TESTS, COIL DRAIN PAN. disclosed tc others Those who use these coc is-ients UPON COMPLETION OF TESTING AND BALANCING PROCEDURES, SUBMIT FOUR ( 4) 91 06 INSTALLATION, ALL HORIZONTAL PIPING SHALL BE RUN LEVEL OR PITCHED UP do so in confidence. COPIES OF ALL TEST DATA FOR RECORD AND APPROVAL, TOWARD THE AIR VENT CONNECTIONS, ALL SIZE REDUCTIONS IN HORIZONTAL 5. 0 IDENTIFICATION AND RECORD DRAWINGS PIPING SHALL BE MADE WITH ECCENTRIC REDUCING FITTINGS, KEEPING THE — _- 5 01 IDENTIFY ALL EQUIPMENT, SWITCHES, STARTERS AND CONTROLS BY MEANS OF TOP OF THE PIPING AT THE SAME LEVEL ON EITHER SIDE OF THE REDUCER, :architect of Record: ENGRAVED VINYL PLASTIC NAMEPLATES. PROVIDE COMPLETE CONTROL DIAGRAMS 9, 07 TESTING, AFTER ALL PIPING HAS BEEN INSTALLED, BUT BEFORE PIPING IS Charles Nivers WITH OUTLINE OPERATING INSTRUCTIONS, PROPERLY CODED TO IDENTIFICATION OR CONCEALED, SYSTEM SHALL BE TESTED HYDROSTATICALLY AT A PRESSURE OF PLATES 150 PSIG FOR A PERIOD OF 4 HOURS, IF ANY LEAKS ARE DETECTED, THE 5 02 PROVIDE A COMPLETE SET OF RECORD DRAWINGS, SHOWING THE EXACT IN- DEFECTIVE PIPE, FITTINGS OR JOINTS SHALL BE REMOVED AND REPLACED, Mate of Florida STALLED LOCATION OF EACH COMPONENT OF THE AIR CONDITIONING SYSTEMS, PEENING OR CAULKING OF LEAKS WILL NOT BE PERMITTED AFTER REPAIRS Reg:stration t MANUFACTURER' S NAMES AND DESIGNATIONS FOR ALL NEW MAJOR ITEMS OF ARE COMPLETED, THE HYDROSTATIC TEST SHALL BE REPEATED AS REQUIRED TO AR0014546 EQUIPMENT, AND FINAL AIR QUANTITIES, OPERATING PRESSURES AND DEMONSTRATE THE ACCEPTABILITY OF EACH SYSTEM TO THE ENGINEER, TEMPERATURES 9 08 FINAL CONNECTIONS TO UNITS SHALL BE MADE WITH 200 PSIG, 2 FOOT LONG, 61 0 DUCTWORK BRAIDED, STAINLESS STEEL, FIRE RATED HOSES COMPLETE WITH ADAPTORS 6. 01 ALL SUPPLY AIR AND RETURN AIR DUCTWORK SHALL BE CONSTRUCTED OF 1' 10 0 ROOF VENT THICK FIBROUS GLASS DUCT BOARD UNLESS OTHERWISE INDICATED, 10 01 VENT SHALL BE TESTED AND RATED IN ACCORDANCE WITH THE REQUIREMENTS OF - -- — CONSTRUCTION AND INSTALLATION SHALL COMPLY WITH SMACNA FIBROUS GLASS AMCA, HOUSING SHALL BE OF PROPER DESIGN, SUFFICIENT STRENGTH AND DUCT CONSTRUCTION STANDARDS, RIGIDITY TO OPERATE UNDER INSTALLED CONDITIONS WITHOUT LEAKAGE, 6. 02 ALL OUTSIDE AIR DUCTWORK SHALL BE CONSTRUCTED OF GALVANIZED SHEET 10. 02 VENTILATOR INLET SHALL BE COMPLETELY PROTECTED WITH REMOVABLE BIRD STEEL DUCTWORK SHALL BE FABRICATED IN ACCORDANCE WITH THE 1975 SCREEN ASHRAE HANDBOOK-EQUIPMENT, CHAPTER 1, TABLE 4 AND SMACNA LOW VELOCITY 10. 03 VENTILATOR SHALL BE FACTORY ASSEMBLED UNIT, DUCT CONSTRUCTION STANDARDS, EXCEPT AS OTHERWISE INDICATED HEREIN. 10, 04 VENTILATOR SHALL BE CONSTRUCTED AND INSTALLED TO WITHSTAND A WIND INTERVAL 6 03 PR❑VIDE ALL SQUARE ELBOWS WITH DOUBLE THICKNESS TURNING VANES PRESSURE OF 60 PSF FROM ANY DIRECTION AND TO PREVENT ENTRY OF WATER CONSTRUCT ROUND DUCT ELBOWS OF NOT LESS THAN FIVE ( 5) SECTIONS INTO THE BUILDING UNDER ALL WEATHER CONDITIONS. 6. 04 CONSTRUCT ALL TRANSFORMATIONS IN DUCT SIZE AND SHAPE WITH A MAXIMUM ill 0 CONDENSATE DRAIN PIPING INTERNATIONAL ANGLE OF 15 DEGREES BETWEEN THE DUCT CENTERLINE AND ANY SIDE OF THE 11 01 DRAINAGE PIPING SHALL BE TYPE DWV COPPER TUBING WITH DRAINAGE PATTERN TRANSITION, ALL BRANCHES SHALL ENTER THE MAIN AT LARGE END OF SOLDERED FITTINGS, ALL ELBOWS SHALL BE LONG RADIUS SWEEPS THE TRANSITION OR BEFORE TRANSITION, MINIMUM SIZE OF DRAIN SHALL NOT BE LESS THAN THE SIZE OF THE 6. 05 SEAL ALL JOINTS IN DUCTWORK WITH AN APPROVED FIRE RETARDANT GLASS EQUIPMENT DRAIN OUTLET, SLOPE LINE TO DRAIN AT NOT LESS THAN 1/8' 4th Floor FIBER REINFORCED HIGH VELOCITY DUCT SEALANT UNLESS OTHERWISE PER FOOT, 6262 Sunset Drive INDICATED 11. 02 FURNISH AND INSTALL DIELECTRIC COUPLINGS AT ALL CONNECTIONS BETWEEN 6, 06 PROVIDE ALL VOLUME DAMPERS REQUIRED FOR COMPLETE CONTROL OF AIR DISSIMILAR METALS Miami, Fl 33143 DISTRIBUTION, VOLUME DAMPERS SHALL BE CONSTRUCTED OF 16 GAGE SHEET 12. 0 PIPE HANGERS AND SUPPORTS METAL; DAMPERS UP TO 12 INCHES IN WIDTH MAY BE SINGLE BLADE AND OVER 12, 01 SPACING, 1/2' TO 3/4' - 3, 5 FEET MAXIMUM, 1' TO 1-1/4' - 4, 5 FEET 12 INCHES SHALL BE MULTI-BLADE WITH A MAXIMUM BLADE WIDTH OF 9 MAXIMUM, 1-1/2' TO 2- - 5, 5 FEET MAXIMUM, 2-1/2' AND LARGER - 7, 5 INCHES, SINGLE BLADE DAMPERS SHALL BE PROVIDED WITH 1-1/2 X 1/8 INCH FEET MAXIMUM, GALVANIZED STEEL CHANNEL FRAME EACH DAMPER BLADE SHALL BE SECURELY 12 C2 HANGERS FOR AND SUPPORTS SHALL BE GALVANIZED WROUGHT STEEL CLAMP OR 0 �r.er: Jeff Weiss ATTACHED TO A 1/2 INCH DIAMETER STEEL PIVOT ROD MOUNTED IN BRONZE CLEVIS TYPE, PLACED OUTSIDE THE INSULATION, OR ISOLATED FROM 433 Plaza Real, ti34 275 FRAME INSERTS; EACH ROD SHALL BE EXTENDED TO A LOCKING QUADRANT WITH UNINSULATED PIPE BY MEANS OF RIBBED SYNTHETIC RUBBER ISOLATION PADS Boca Raton, F 3 3 3432 INDICATING DEVICE MOUNTED ON THE SIDE OF THE DUCT 13, 0 INSULATION Contact: Jeff Weiss, (561) 416-4600 6. 07 ALL DUCT PENETRATIONS THROUGH FIRE OR SMOKE RATED WALLS AND FLOORS 13. 01 INSULATION SECTIONS OR SEGMENTS SHALL BE PROPERLY CUT AND FITTED TO SHALL BE SEALED WITH A UL LISTED SYSTEM TO MAINTAIN THE FIRE AND EACH SURFACE, TIGHTLY BUTTED TOGETHER AND SECURED WITH STAINLESS SMOKE INTEGRITY OF THE WALL OF FLOOR. STEEL BANDS OR 14 GAUGE COPPERWELD WIRE ON 9' MAXIMUM CENTERS ALL 04-00 7 0 AIR OUTLETS AND INLETS SEAMS AND JOINTS SHALL BE THOROUGHLY SEALED WITH AN APPROVED FIRE- Date: 7. 01 TEST AND RATE ALL AIR OUTLETS AND INLETS IN ACCORDANCE WITH ADC RETARDANT JOINT SEALER AS RECOMMENDED BY THE INSULATION MANUFACTURER. Pro;ec'. 'o: 605610 EQUIPMENT TEST CODE 1062R4, AND PROVIDE THE PROPER SIZE AND TYPE TO 13 02 CONDENSATE DRAIN LINES AND FITTINGS SHALL BE INSULATED WITH FOAM i Drawn By: `.1B OBTAIN SATISFACTORY DISTRIBUTION OF THE SPECIFIED AIR QUANTITIES PLASTIC PIPE INSULATION SUCH AS AP ARMAFLEX OR AS APPROVED, Checked Bv: 1Ea WITHIN EACH SPACE, CONSTRUCT ALL GRILLES, REGISTERS AND DIFFUSERS CONDENSATE DRAIN LINE INSULATION SHALL BE 1/2' THICK WHERE ENTIRELY OF ALUMINUM WITH PAINTED FINISH UNLESS OTHERWISE INDICATED, POSSIBLE, SLIDE INSULATION ON WITHOUT SPLITTING WHERE THIS IS NOT CADD File 00-05(VECHANICa .j.dw� PROVIDE EACH AIR OUTLET AND INLET WITH A SYNTHETIC SPONGE RUBBER POSSIBLE, USE MANUFACTURER' S RECOMMENDED ADHESIVE TO CEMENT JOINTS GASKET TO FORM A TIGHT SEAL BETWEEN FRAME AND MOUNTING SURFACE TOGETHER, ADDITIONALLY SECURE WITH TAPE OR 14 GAUGE COPPERWELD WIRE Title: 7. 02 ALL CEILING RETURN AIR GRILLES SHALL BE SQUARE GRID TYPE, WITH 1/2 X ON 9' CENTERS FINISH EXPOSED INSULATION WITH TWO COATS OF WHITE 1/2 INCH GRID 1/2 INCH DEEP, FREE AREA SHALL NOT BE LESS THAN 90 LATEX PAINT OR ARMAFLEX FINISH MECHANICAL PERCENT, GRILLES SHALL BE TITUS WITH STYLE 50F CORE OR AS APPROVED jcpi'' �P� o SPECIFICATIONS A A i T NDERSON ILLIAMS CONSULTING ENGINEERS INC. •� •''<; 117 MAJORCA AVE. CORAL GABLES, FLORIDA 33134 ° TELEPHONE (305) 442-8033 AWCE JOB,#: 00-05 I � Uneet Number o_: =-t