GENERAL NOTES
1. COORDINATE NEW DUCTWORK AND EQUIPMENT WITH LIGHTING, PLUMBING,
STRUCTURAL SYSTEMS AND CEILING SYSTEMS,
2. DUCT ACCESS PANELS ADEQUATE FOR SERVICE SHALL BE PROVIDED AT
LEGEND ALL DAMPERS AND CONTROLS
3 CONTRACTOR SHALL COORDINATE LOCATION AND SIZE OF ALL
PENETRATIONS THROUGH WALLS, CEILING AND FLOOR WITH OTHER
ARI AMERICAN REFRIGERATION INSTITUTE O DRAWING REFERENCE NOTE TRADES, ,
CAP. CAPACITY 4, ALL DUCT SIZES SHOWN ARE ACTUAL AIR PATH SIZES
CFM CUBIC FEET PER MINUTE DIAMETER 5. CEILING ACCESS PANELS SHALL BE PROVIDED FOR EQUIPMENT,
CLG. CEILING DAMPERS AND CONTROLS INSTALLED ABOVE OTHERWISE NON- International
COMP. COMPRESSOR THERMOSTAT, ROOM ACCESSIBLE CEILINGS ACCESS PANELS SHALL NOT BE LESS
CNN, CONNECT, CONNECTION
CWR CONDENSER WATER RETURN FLEXIBLE DUCT THAN 20 X 20' . Design P artn e r s hip
CWS CONDENSER WATER SUPPLY NEW DUCTWORK OUTSIDE AIR CALCULATIONS 6. MOUNT ROOM THERMOSTATS 5 FEET ABOVE FL❑OR. t"
DB DRY BULB 7 ALL EQUIPMENT LOCATED OUTSIDE SHALL BE CONSTRUCTED AND
DN DOWN �fla--� GATE VALVE TOTAL GROSS AIR CONDITIONED AREA. , , , , 3346 S, F INSTALLED TO WITHSTAND A WIND PRESSURE OF 60 POUNDS PER Incorporated
SQUARE FOOT FROM ANY DIRECTION
DWG DRAWING
EA EACH MANUAL VOLUME DAMPER GROSS OFFICE AREA , , , , , , , , , , , , , . 2755 S F, 8. DUCTWORK PENETRATIONS OF WALLS SHALL BE SEALED AIR AND
NET OFFICE AREA , , , , , , , , , , , 2066 S. F. WATER TIGHT, hta Drive
EER ENERGY EFFICIENCY RATIO _ 30 W. NfDrive ENT, ENTERING FIRE/SMOKE DAMPER 9, NO EQUIPMENT OR MATERIALS SHALL BE PURCHASED OR INSTALLED
EQUIP EQUIPMENT 2066 S F, /1000 S F X 7 P) 15 PEOPLE PRIOR TO FINAL APPROVAL OF SHOP DRAWINGS Biscayne,Biscane, Fl 331,19
EXT. EXTERNAL 15 PEOPLE X 20 CFM/PX = , , , 300 CFM 10, EXISTING EQUIPMENT, PIPING, DUCTWORK, OUTLETS, CONTROLS, Tel: 30.1'365.8338/ Fax: 308.368.8339
FLA FULL LOAD AMPS ETC. WHERE S❑ NOTED SHALL BE REMOVED OR RELOCATED AS PART -mail: IDPmia aol.com
HP HORSEPOWER TOTAL GROSS LUNCHROOM AREA. , , , 591 S, F. OF THIS CONTRACT.
KW KILOWATTS NET LUNCHROOM AREA. , , , , , , , 443 S F 11 THE CONTRACTOR SHALL PROVIDE A SET OF PRINTS CLEARLY MARKED TO - -
L&S LOUVER AND SCREEN SHOW AS-BUILT CONDITIONS AT THE COMPLETION OF CONSTRUCTION �o. ItiLE Date
MAX. MAXIMUM 443 S, F, /1000 S F, X 70 Px _ 31 PEOPLE 12. FLOOR SLABS ARE POST TENSIONED STRUCTURES. STEEL REINFORCING
MIN, MINIMUM 31 PEOPLE X 20 CFM/Px _ , , , , , 620 CFM SHALL BE LOCATED AND CAREFULLY AVOIDED WHEN CUTTING NEW
MVD MANUAL VOLUME DAMPER OPENINGS
NTS NOT TO SCALE TOTAL REQUIRED OUTSIDE AIR. , , , , , 920 CFM
TOTAL OUTSIDE AIR PROVIDED BY AC-1, AC-2, AC-3
❑/A OUTSIDE AIR &
O/ PRESSURE DROP AC-4. , , , 925 CFM -- -- - - --
PSF POUND PER SQUARE FOOT x IN ACCORDANCE WITH ASHRAE 62-1989
QTY QUANTITY
R/A RETURN AIR
RLA RUNNING LOAD AMPS --- -- ---- -- -
RPM REVOLUTIONS PER MINUTE
S/A SUPPLY AIR
S F. SQUARE FEET
SIP, STATIC PRESSURE
TYP. TYPICAL
V/PH VOLTAGE/PHASE
W/ WITH - -- ----- -- -
WB WET BULB
CLIEtiT APPRO`-AL
I have reviewed these plans and have been
given the oopor,.unity to ask questions about
them prior to issue. These plans conform
to our requirements I understand that any
modifications to these plans will be an
additional service with potential impact on
construction cost and scheduling
ACCEPTED AS I6
ACCEPTED AS NOTED
Signature Date
WATER COOLED HEAT PUMP UNIT SCHEDULE
All d aw'rc, and wri,ten ma+er;al herein, as instrimen s
MASONRY SUPPLY OUTSIDE EXT. MAX. SENS. TOTAL ENT. AIR WATER ENT. WATER STEPS COMP. FAN HEAT of service; shay: remain the property of 'nternational
WALL MARK MAKE MODEL TYPE HP FACE V/PH EER Design Partners'__ip 'nc. (IDP) and small not be reproduced
1' MINIMUM OVERLAP AIR AIR S.P. VEL. BTUH BTUH DB�WB FLOW WATER P.D. OF CAP. RLA FLA BTUH or co Pd, in who'e or in part, wtt_lout the expressed
ON ALL SIDES p
� �. AC-1 CLIMATEMASTER HS060 HORIZONTAL PACKAGE 1700 415 0.7' 1.0 408 45000 60000 80.0 67.0 16.2 GPM 85.0'F 17.0 FT 1 208 3 16.1 5.8 73000 11.2 written consent of IDP and znav not be used or
\� 1/4' M I N I MUM AC-2 CLIMATEMASTER HS096 HORIZONTAL PACKAGE 2800 250 0.7' 1.5 336 67260 92600 80.0/67.0 24.8 GPM 85.0'F 19.3 FT 2 208/3 2: 13.8 EA. 7.5 1 1 1 150 11.0 referenced for an other project r.forrlation ccn ar.ed
\ _ AC-3 CLIMATEMASTER HS060 HORIZONTAL PACKAGE 1735 260 0,6' 1.0 416 45180 60700 180.0/67.0116.2 GPM 85.0'F 17.0 FT 1 208 3 16.1 5.8 73000 11.2 herein represents proprietary into oration of :r.ternat'.onal
Des.gn Partnership and or its '!-.er_t and shall not be
NOTES disclosed to o±hers Those who use these documents
DUCT--' 1, COMPRESSORS SHALL HAVE A 5-YEAR EXTENDED WARRANTY. do so in confidence.
2 A SMOKE DETECTOR SHALL BE INSTALLED IN THE S/A DUCT OF UNITS IN ACCORDANCE WITH NFPA 9CA SMOKE DETECTORS ARE SPECIFIED UNDER ELECTRICAL,
3 THERMOSTATIC EXPANSION VALVES SHALL HAVE A BROAD MODULATING RANGE, EXTERNAL EQUALIZING LINES SHALL BE TAPPED INTO SUCTION LINES DOWNSTREAM OF THE EXPANSION VALVE SENSING
BULBS, --- - - - - - -
� DAMPER FRAME 4. HORIZONTAL UNITS SHALL HAVE 1' THICK FLAT THROWAWAY FILTERS LOCATED IN FILTER BACK GRILLES, Architect of Record:
5. INSTALL UNITS ON EXTERNAL SPRING ISOLATORS Charles Nlyers
6, UNITS SHALL BE COMPLETE WITH LOW PRESSURE SWITCH, ANTI-SHORT CYCLE TIMER AND ROOM THERMOSTAT WITH AUTOMATIC CHANGEOVER,
OVERCENTER LOCK--,\\ State of Florida
'� � S-JOINT AR0014-46
/( SLEEVE TO DUCT)
DUCTS
' '-MOUNTING ANGLES
6' MIN, 11 -//?
16' MAX.
INTERVAL
FIRE/SMOKE DAMPER INSTALLATION DETAIL
NTS INTERNATIONAL
4th Floor
6262 Sunset Drive
Miami, Fl 33143
HVAC DESIGN REQUIREMENTS
CONDENSATE DRAIN PAN GAUGE CONNECTION HVAC DESIGN REQUIRES: YES N
& VENT DUCT SMOKE DETECTOR X Owr_er� eff �;eiss
FIRE DAMPERS X 433 _ _aaa Real, uite 27
THERMOMETER WELLS C TYR� -CWR SMOKE DAMPERS X
Boca Raton, FL 333
x FIRE RATED ENCLOSURE X
Contact: Jeff ti�eiss (061) 416-4600
ISOLATION FIRE RATED ROOF/FLOOR X
BALANCING VALVE �
/AxB � � VALVES '�CWS CEILING ASSEMBLY -
f AIR VOLUME UNION
(A+C)xB EXTRACTOR �- �,_ BRANCH DUCT OR SMOKE CONTROL X X 04-00
�SIDEWALL OUTLET COLLAR Date:
MVD ,- PERFORATED CLEANOU�
Project NO: 8086.10
Drawn By, 8JB
Checked 3y: JEa
AIR FLOW SIZE AND DEPTH OF TRAP �� CADD File 00-015(MECH VCAL) dwg
i r MVD AS RECOMMENDED BY UNIT---,,,,, - --- - -
� MANUFACTURER � AC UNIT � GAUGE - - -- -
DxB" & DRAIN
�DISTRIBUTION DUCT
Title.
J UNION OR FLANGES (TYP)
CxB AT 1/ TO DRAIN SCHEDULE DETAILS
AT 1/8' /FT. �� ,
TYPICAL DUCT TEE DETAIL TYPICAL DUCT TAKEOFF DETAIL A/C CONDENSATE DRAIN DETAIL CONDENSER WATER CONNECTION DETAIL LEGEND & NOTES
NTS NTS NTS A "
NTS �PriGCN+P�1;eZ� f
. ' �' v `f
A
fi NDERSON
ILLIAMS CONSULTING ENGINEERS INC. °
F. ' 117 MAJORCA AVE. CORAL CABLES, FLORIDA 33134
TELEPHONE (305) 442-8033
AWCE JOB#: 00-05
1