00-0824-004 - REVISIONS BY ELECTRICAL. GE :V F:-. R AI- NOTES 1.- ALL CONDUIT RUN EXPOSED, CONCEALED IN MASONRY WALL OR CONCRETE SLAB,' BENEATH SLABS ON GRADE OR RUN UNDERGROUND SHALL BE IN RIGID OR INTERMEDIATE WEIGHT GALVANIZED STEEL CONDUIT, CLECTRICAL OR METALLIC TUBING MAY BE CONCEALED IN INTERIUR HOLLCW WA;.LS AND A3OVE SUSPENDED CEILING. ALL FITTINGS SHALL BE COMPRESSION TYPE 011) WATERTIGHT, POLYVINYL CHLORIDE (PVC) SCF'ECULE 4: U.L. LISTED RACEWAY MAY BE USED IN ALL RUNS UNDERGROUND AND BENEATH GROUND SLAB, PROVIDED SIZE IS SUFFICIENT TO ACCOMODATE GROUND WIRE AND ADAPTERS ARE INSTALLED AT PVC TO METAL TRANSITIONS, WHERE RACEWAYS RISE TROUGH GRADE AND/OR BOTTOM SLABS, 2.- ALL WIRES SHALL BE # 14 AWG COPPER, UNLESS SPECIFICALLY INDICATED OTHERWISE ON DRAWINGS. ALL INSULATION SHALL BE TYPE "THWN', 3,- ALL CONDUITS SHALL BE SECURED FASTENED TO THE BUILDING WITH PIPE STRAPS OR OTHER APPROVED PIPE SUPPORTS. NO WIRE HANGERS ARE ACCEPTED. To FPFP—t LOAD CALCULATIONS 4.- MANUFACTURERS' NAME AND CATALOG NUMBERS ARE USED TO DEFINE THE �,� G•- I , / TRANSF. AREA ---> 1470 Sf. TYPE AND QUALITY OF EQUIPMENT AND MATERIAL, EQUAL ITEMS OR OTHER f AEREAL SERVICE GENERAL LIGHTING & RECEP. (1470 Sf. X 3 VA/Sf.) = 4,410 V.A MANUFACTURES ARE ACCEPTABLE PROVIDED THEY ARE EQUAL OR BETTER IN SMALL APPUANCES (2X1,500 VA! = 3,000 THEIR QUALITY. REFRIGERATOR = 1,200 RANGEIOVEN = 12,000 WASHER = 1,500 S.— ALL WORK SHALL BE DONE IN A NEAT AND WORKMANLIKE MANNER, AND IN DRYER = 5,000 FULL ACCORDANCE WITH NATIONAL ELECTRIC CODE, ALL APPLICABLE STATE WATER HEATER = 4,500 AND LOCAL CODES, AND THE LOCAL UTILITY (FPL) COMPANY REQUIREMENTS. NEW T NEW ELECTRICAL W,0,41 (5000 V.A 065%) = 6,500 V.A • 31,610 VA FPL ELECT O PANEL W.� ..2(5,590 V.A 0 100%)= 5,590 V.A • 6.- CONTRACTOR SHALL VERIFY NAMEPLATE RATINGS OF ALL EQUIPMENT FOR DEMAND LOAD ¢ METER 150 AMPS. • NON CURRENT LOADS CORRECT SIZE OF OVERCURRENT DEVICES AND WIRING BEFORE ROUGH-IN. FIRST 10,000 V.A ®100% = 10,000 VA 7,- WHERE FUS!2LE EQUIPMENT IS SPECIFIED, DELIVER TO THE OWNER'S fwd- MAIN SERVICE REST 040% (31,610-10,000)X40% = 10,162 DISCONECTiVE 65% OF HTR. LOAD I = 8,644 REPRESENTATIVE :� KINIMUM OF ONE (1) SPARE SET OF EACH SIZE, (\/J,C�. {`� 150 cIMP 28,806 VA g,- CIRCUIT NUMBERS SHOWN ON PANEL SCHEDULES ARE FOR IDENTIFICATION LOAD ----> 28,806 VA = 120 AMPS OF BALANCED LOADS. IT SHALL BE THE ELECTRICAL CONTRACTOR'S 1 #5 3 #1 THWN-Cu 240 V RESPONSABILITY TO BALANCE THE PHASE LOAD OF PANEL BOARDS IF THwN cu IN 2' CONDUIT ADDITIONAL LOAD IS ADDED OR IF CIRCUIT ARRANGEMENT DIFFERS FROM PANEL SCHEDULES, CWP / 9.- CONTRACTOR SHALL VERIFY LOCATION OF ALL EQUIPMENT REQUIRING FIN. GRADE NEUTR� ELECTRICAL CONNECTION AND THE EXACT CONNECTION REQUIREMENT OF 0 �- - - EQUIPMENT BEFORE ROUGH-IN, 44 REC£PT./LIGHTING & APPL = 8.462 V.A 1 #6 (2) s/a• X 10'-0' GROUND Roo �� 10.- THE SHORT-CIRCUIT AVAILABILITY AT PANEL BOARDS SHALL BE ^ THWN CU SPACED ® 6'-0• MIN. FIRST 3000 V.A ® 100% = 3,000 LIMITED TO THE INTERRUPTING CAPACITY OF THE LOWEST RATED DEVICE, a REST 0 35% (8,462-3,000) X 35% = 1,911 ° RANGE/OVEN 070% = 1 1,208 W ( DRYER ® 709 = 3,500 11,— CONTRACTOR SHALL LABEL ALL CIRCUIT AT PANEL BOARD. A;_=1 t WASHER 0 100% = 1,500 #5��� 21,119 vA 12,- OUTSIDE RECEPTACLES AT B,"1TiiR�OMS, GARAGE A�'D zo' or+c MIN. 6 FEET FROM KITCHEN SINK SHALL BE GFI. *4 CG .�� - __.- LOAD 21,119 VA = 96 AMPS U N ELECTRICAL RISER DIAGRAM 220 V W N 4- N.T.S. AS PERQREQUIRE BYANE 1010-9 WITH CIRCUITIIMPIEDANCENS PER NEC-110-10 �F d / - LEND OF SYMBOLS 14,- ELECTRICAL OUTLETS (Receptacles and lighting) BELOW BASE FLOOD ELEVATION M M M W .� KITCHEN OR SHALL INSTALLED AT THE HIGHEST PERMITTED ELEVATION AND SHALL BE 3 BATHROOM LIGHT SMOKE DETECTOR INSTALLED ON (Separate) INDEPENDENT CIRCUITS FROM THOSE IN HABITAL AREAS, ouPLFx OUTLET RECEPTACLE - GROUNDING TYPE NO APPLIANCES OR APPLIANCES OUTLETS SHALL BE INSTALLED BELOW p; o O 0 0 125 V, 18' ABOVE FINISH FLOOR BASE FLOOD ELEVAT ON. �J LINE DUPLEX C GROUNDING UL OF SWITCH 125V,, 1 B ABOVE FINISH FLOOR GROUND F T INSULATED. 15.- A/C COMPRESSOR SHALL BE INSTALLED ABOVE BASE FLOOD ELEVATION, w a, 0I SWITCH cEUNC ucHnrlc OUTLET 16,- MAIN CIRCUIT BREAKER PANELS SHALL BE LOCATED ABOVE BASE ISWITCH LEG O JUNCTION BOX FLOOD ELEVATION, o PHASF CONDUCTOR FQ WALL LIGHTING OU=. 17.- COORDINATE WITH FLORIDA POWER k LIGHT TO LOCATE THE 1 = swcL� POLE SWITCH ELECTRICAL METER TO COMPLY WITH FEDERAL EMERGENCY SMOKE DETECTOR CONNECTION 120 V, 44' ABOVE FINISH FLOOR G G° - DETAIL AND NOTE s MANAGEMENT AGENCY REQUIREMENTS, THREE WAY SWITCH G 3W 120 V, 44' ABOVE FINISH FLOOR 18,- ALL "J" BOXES SHALL COMPLY WITH N.E.C. 370.17A SMOKE DETECTOR SHALL BE HARDWIRED (110 VOLT TYPE) TO A NON-SWIT-4ABIF KITCHEN OR ® SMOKE DETECTOR ALARM. BATHROOM LIGHTING CIRCUIT, WITH BATTERY BACK-UP AND SHALL NOT BE _'ONNECTED ONTO THE LOAD SIDE OF GROUND FAULT CIRCUfT INTERRUPTER. ALL SMOKE DETECTORS WITHIN DISCONNECTTVE SWITCH 19.- MAXIMUM NUMBER OF OUTLETS PER CIRCUIT SHALL COMPLY EACH UNIT SHALT. BE INTERCONNECTED. _ _ __._ _ WITH SFBC. I ul C 150 AMPS, MCB, 1,0' 3W, 1201240 VOLTS E L_ E C T R I C A L PANEL FLUSH MOUNTED TYPE I.T.E. CIRCUIT AMPS. BKR.POLE DESCRIPTION WIRE CONDUIT LOAD -S,z :G� t. 1" « � 1 2b 2 LIVING RM OUTLETS #12 SMKE 2 15 1 BATHROOM LIGHT #14 ---- W . U i 3 20 1 REFRIGERATOR #12 1200 lit _ A� 4,_ 4 2ca 1 BEDROOM RECEPT #12 ---- W 5 2 4) 1 KITCHEN Cm 1z I #1 6 15 1 BEDROOM LIGHTS J14 ---- 7 20 1 SMALL APPLIANCES #12 1500 w h1 8 2U 1 BEDROOMcEC-��. #t2 __j ---- 20 1 DISHWASHER #12 U 1200 9 � �� �- ° 12 - ---- a W Q 13 20 1 BATHROOM GFI #12 14,16 30 2 WATER HEATER #10 4500 r O O 75,77 30 2 DRYER #70 5000 16,18 40 2 - Wc6.E , t�Rd�°T" #Ilz 19,21 50 2 RANGE #6 12000 M+y 20,22 °- — 23 24 24 -- -- SPARES ---- ---- rr/ 25 -- -- SPARES ---- ---- 26 -- -- SPARES ---- ---- e7 27 -- -- SPARES ---- ---- `y N 28 -- -- SPARES ---- • 29 -- -- ---- ---- 0 (�/� SPARES 30 - SPARES 31 -- -- SPARES ---- ---- ® � _T SPARES TOTAL DEMAND: 40990 Date 9="* Scale NI F ti Drawn C� �'P C Job Sheet 6F 44 1 r f Of Sheets 24 X 36 PRINTED ON NO.1000H CLEARPRINT m