00-0332-098 q6'
I
L LLJ Q) N M
`� no o �lu o � a'T
PACKAGED ROOFTOP A.C. UNIT SCHEDULE * w o a`�o °°
AIR COOLED SPLIT A/C UNIT SCHEDULE OUTSIDE AIR CALCULATIONS (AS PER ASHRAE d2-89 m � v`z ` I
UNIT DESIGNATION RTU-1 RTU-2 RTU-3 z � _o
AREA SERVED
3RD FLOOR 3RD FLOOR 3RD FLOOR UNIT DESIGNATION AC-1 AC-2 AC-3 AC-4 AC-5 AC-6 AC-7 �" 3 y�'� �-
NW SW EAST OFFICE OFFICE OFFICE OFFICE OFFICE 2ND FLOOR TOILET & UNIT NO. AREA AREA S/1000 P 0. OF CFM/ CFM Q2 CFM CFM ® -�` - °m i 'n z �^
SQ. FT. Q PERSONS PERSON REQUIRED PROVIDED q
LOCATION SEE PLAN SEE PLAN SEE PLAN AREA SERVED 201 202 203 204 205 206 CORRIDOR „ a x N .° Mop Q
OPERATING WEIGHT LBS. 579 663 858 _ �Q scz �-
ELECTRICAL SERVICE AVAILABLE 08-3- 0 208-3-60 _2T8_-3-6 OPERATING WEIGHT LBS. 92 109 109 109 109 81 81 AC-1 OFFICE 815 7 20 - 115 125 ci � �' d wo
YES YES DESIGN MANUFACTURER RtiEEM RHEEM RtIEEM RHEEM RHEEM RHEEM RHEEM AC-2 o N a
TOTAL Al F 1700 2300 3100 MODEL NUMBER RBEA-17 RBEA-21 RBEA-21 RBHJ-21 RBHJ-21 RBEA-14 RBEA-14 OFFICE 1032 7 - 20 - 145 150 4 m�
OUISIDE AIR 325 360 600 EVAP. COIL MODEL NO. RCGA-37A1 RCGA-48A1 RCGA-48A1 RCGJ36A2 RCGJ36A2 RCGA-24A2 RCBA-2453 N ~ ; NJ
EXTERNAL SIATIC PRESSURE IN, QF H20 50 .50 .70 AC-3 OFFICE 1074 7 - 20 - 151 175 C � w `�
-------- TOTAL AIR CFM 900 1400 1600 1300 1110 750 400 ■� o J
FAN SPEED RPM 3 5-5.3 1-5.9 2-7.5 VENT AIR CFM 125 150 175 125 125 100 100 AC-4 OFFICE 864 7 20 - 122 125 o M
o MAXIMUM MOTOR SPEED R.P.M. N/A N A N A EXTERNAL STATIC PRESSURE IN. OF H2O .40 .40 .40 .40 .40 .40 .25 � °
a z FAN MOTOR HP NON OVERLOAD F.L.A. 1/4-2.0 1/3-2.8 1/3-2.8 1 2-5.0 1/2-5.0 1/8-1.4 1/8-1.4 AC-5 OFFICE 830 7 - 20 - 117 125 Q- z z
ELECTRICAL SERVICE 208-1-60 208-1-60 208-1-60 208-1-60 208-1-60 208-1-60 208-1-60 "®' w
AC-6 OFFICE 708 7 - 20 - 100 100 o L
TOTAL COOLING CAPACITY, B.T.U.H. 55,600 67,700 99,100 SMOKE DETECTORS - c � =,y
TOTAL SENSIBLE CAPACITY, B.T.U.H. 3$900 50 700 69 100 0 FACE VELOCITY FPM - - - AC-7 TICORRIDOR - 300 300 100 � � �
ENTERING Al R TEMP. DB WB �� 77.6/66.6 76.8/65.6 78.3/66.9 Z - - I N
LEAVING AIR TEMP. DB WB o GRAND TOTAL CAPACITY BTU HR 29,800 41,000 46,500 35,800 35,800 23,600 17,200 OFFICE 1498 7
TOTAL HEATING CAPACITY, KW 9.0 6.75 13.5 v TOTAL SENSIBLE CAPACITY BTU HR 21,400 29,300 32,000 26,000 26,000 16,600 12,200 RTU-1 _ - 20 - 309 325 �� 0 j o 0
NO OF HEATING STEPS 2 1 1 - t" a w
ENTERING AIR TEMP 'F DB B 76.8 65.6 76.5 65.1 76.1 64.6 76.1 64.7 76.71/65.2 76-9/65.7 79.1 67.7 OFFICE 1859 7 _ 20 - `" g o`J'
_ ELEC. ELEC. ELEC. LEAVING AIR TEMP 'F DW WB - - - _ _ _ _ RTU-2 TOILETS _ - - 100 360 360 K°; a CL
ELECTRICAL SERVICE 208-3-60 208-3-60 208-3-60 a TYPE AND THICKNESS DISP/1" DISP/1" DI SP/1" DISP/1" DISP/1" DISP/1" DISP/1" RTU-3 OFFICE 2745 7 - 20 - 584 600 m o
or_
w TYPE THICKNESS DISP DISP 2 DISP w QUANTITY AND SIZE AS REQUIRED AS REQUIRED AS REQUIRED AS REQUIRED AS REQUIRED AS REQUIRED AS REQUIRED TOILETS - - 200 z
t FACE VELOCITY FPM MAXIMUM DESIGN - - - FACE VELOCITY FPM MAX
QUANTITY AN SIZE AS REQUIRED AS REQUIRED AS REQUIRED REF. PIPE SIZE SUCT 1-10. 3/4-5/16 1-1/8-3/8 1-1/8-3/8 7/8-3/8 7 8-3 8 3/4-5/16 5 8-1 4
1 1 2 COIL TYPE ELEC ELEC ELEC ELEC ELEC ELEC ELEC NOTES:
CAPACITY REDUCTION 100-0 100-0 100-0
ELECTRICAL SERVICE AVAILABLE 208-3-60 208-3-60 208-3-60 ,� HEAT CAPACITY KW 3.6 3.7 5.3 3.7 3.6 3.6 3.6
18.6/118 21.81L1 8 1 118fA = -" 1 1 ALL CFM AMOUNTS COUNTS ARE AS PER ASHRAE 62-19$9.
N0, OF STEPS 1 1 1 1 1 1
AMBIENT AIR TEMPERATURE F 95 95 95 UNIT DESIGNATION CU-1 CU-2 CU-3 CU-4 CU-5 CU-6 CU-7
Q CFM PER URINAL OR WATER CLOSET
z NUMBER OF FANS 1 1 1
o NO. OF FANS AND F.LA. 1-1.3 1-2.0 1-2.0 1-1.3 1-1.3 1-.9 1-.9
z ELECTRICAL SERVICE AVAILABLE 208-3-60 208-3-60 208-3-60 AMBIENT AIR TEMP F DB 95 95 95 95 95 95 95 O REMAINING TOILET ROOM CFM REQUIRED IS TRANSFERED FROM ADJACENT OFFICE AREAS.
8 F. A. 2.2 2.0 5.5 ~ N0. OF COMPRESSORS 1 1 1 1 1 1 1
DESIGN MANUFACTURER TRANE TRANE TRANEz
ROOEE NUM TCDO60C TC0074 TCD102C COMPRESSOR RPM MAX 3500 3500 3500 3500 3500 3500 3500
TE V7E R - 10.0 10.0 - 9.2 - o°N CAPACITY REDUCTION 100-0 100-0 100-0 100-0 100-0 100-0 100-0
HOT GAS BYPASS - - - ",z COMPRESSOR F.L.A RLA 13-5/72.5 12.5/88 12.9/91 10.3177 10.3 77 10-9/54 ____83T47
w HOT GAS REHEAT - - - a z ELECTRICAL SERVICE 208-1-60 208-3-60 208-3-60 208-3-60 208-3-60 208-1-60 208-1-60
ANTI SHORT CYCLE TIMER YES YES YES
TIME DELAY SEQUENCE START MULTIPLE COMP.) I YES OPERATING WEIGHT LBS. 188 193 255 188 188 155 135
a OUTSIDE AIR INTAKE W1 MANUAL DAMPER YES YES YES DESIGN MANUFACTURER MODEL NO. RAMB030JAZ RAMB042CAZ RAMB048CAZ RAM13036CAZ RAMB036CAZ RAMB024JAZ RAKA018JAZ
SINGLE POINT ELECTRICAL CONNECTION YES YES YES EER/SEER -/12.40 -/12.40 -/12.40 -/12.80 7/12.80 -/12-4 -/10.0
NOTES: NOTES:
1. RTU-1,2,3 & 4 TO BE PROVIDED WITH PRE-FAB ROOF CURB,14" HIGH MIN. 1. AIR HANDLING UNITS SHALL BE PROVIDED WITH SINGLE POINT POWER CONNECTION
SINGLE POINT POWER CONNECTION, ANTI-SHORT CYCLE TIMER, 0/A 2. REFRIGERANT LINE SIZES SHALL BE AS RECOMMENDED BY UNIT MANUFACTURER
INTAKE W/ MANUAL DAMPER & BIRDSCREEN, TIME DELAY SEQUENCE START. FOR ACTUAL DEVELOPED LENGTH OF REFRIGERANT PIPE RUN, AND SHALL BE SUBMITTED
TO ENGINEER FOR REVIEW.
VENTILATION FAN SCHEDULE
UNIT DESIGNATION EF-1 EF-2 EF-3 EF-4 EF 5 EF-6 ` AIR DISTRIBUTION SCHEDULE AIR CONDITIONING LEGEND > �-
ELEV. CH. A SYM USE TYPE ACCESSORIES MFR & MODEL NO � Q �
AREA SERVED SEE PLAN SEE PLAN SEE PLAN SEE PLAN BASEMENT SUPPLY CEILING ROUND NECK, 24X24 TITUS S Y M B 0 L W D E S C R I P T I O N
R00 VENTILATION A
OPERATING WEIGHT LBS. 15 25 13 36 1 AIR DIFFUSER PANEL, O.B.D. TDCA-AA AHU AIR HANDLING UNIT .� � _
260 U
SUPPLY PERF. CLG. 24X24 PANEL, ROUND TITUS BTM. BOTTOM (n
LOCATION SEE PLAN SEE PLAN SEE PLAN SEE PLAN SEE LAN SEE PLAN AIR DIFFUSER NECK, O.B.D. PCS-AA COND. CONDENSATE M �--
FAN TYPE CLG. MNTD. CLG. MNTD. CLG. MNTD. IN-LINE CLG. M TD. WALL-CENT "C- RETURN RETURN 1/2 X 1/2 X 1/2 GRID, TITUS C.U. CONDENSING UNIT ,
AIR GRILLE 2024 LAY-IN 50F CONC. CONCRETE
TOTAL AIR CFM 100 220 50 600 259 4000 RET/EXH. EXHAUST/RETURN SURFACE MOUNT, TITUS CFM CUBIC FEET PER MINUTE 0
DRIVE TYPE DIRECT DIRECT DIRECT DIRECT DIR CT DIRECT AIR REGISTER O.B.D. 4 FL E.F. EXHAUST FAN m E
FAN WHEEL TYPE CENTRIF. CENTRIF. CENTRIF. CENTRIF. CEN-RIF, CENTRIF. SUPPLY CEILING ROUND NECK, PLASTER TITUS F.L.A. FULL LOAD AMPS Q) W
FAN TIP SPEED,RPM MAX 2513 2113 1406 2189 299 5 3316 AIR DIFFUSER MOUNTING FRAME TDCA-AA F.P.M. FEET PER MINUTE U Q�
FAN SPEED,RPM 1500 1538 956 1325 150110 517 1/2 X 1/2 X 1/2 RETURN RETURN GRID, H.P. HORSEPOWER `'- > 0
4 -
' TOTAL STATIC PRESSURE,IN. OF I120 .25 .125 .125 .250 .12 .25 'F" SIZE AS INDICATED ON TITUS
AIR GRILLE 50F H.R. HOUR O
u- FAN MOTOR HP NON OVERLOAD 63 WATTS 109 WATTS 14 WATTS 1 4 1 1 1 2 Pte' IN. INCH O C)
FAN MOTOR STARTER TYPE - - - - - - SUPPLY VAV CEILING 2024 PANEL ACUTHERM
STARTER FURNISHED BY - - - - - - AIR DIFFUSER RELIEF RINGS TF-HC K•W. KILOWATT
ELECTRICAL SERVICE AVAILABLE 120-1-60 120-1-60 120-1-60 120-1-60 120-1-60 120-1-60 LBS. POUNDS z
SUPPLY VAV CEILING ACUTHERM MAX. MAXIMUM
MASONRY OPENING REQUIRED - - - - - VERIFY �� AIR DIFFUSER RELIEF RINGS TN-C MVD MANUAL VOLUME DAMPER (OPPOSED BLADE) T
DESIGN MANUFACTURER COOK COOK COOK COOK COOK COOK N 0. NUMBER 0 D
NOTE: O
MODEL NUMBER GC-140 GC-340 GC-120 GN-720 GC 180 245W56 0/A OUTSIDE AIR
- 1. AIR DISTRIBUTION SHALL BE OF EXTRUDED ALUM. CONSTRUCTION. 0
SERVICE SWITCH YES YES YES YES ES YES 2. PROVIDE INSULATED BACKING FOR SUPPLY AIR DIFFUSERS TO PREVEVT CONDENSATION, RPM. REVOLUTIONS PER MINUTE
SMOKE DETECTORS - - - - R/A RETURN AIR
w FIRE DAMPER - - - REF. REFRIGERANT
_ � CONSTRUCTION STEEL STEEL STEEL STEEL STEEL ALUMINUM
MULTIBLADE BACKDRAFT DAMPER YES YES YES YES ES YES RTU. ROOFTOP UNIT -
BIRDSCREEN - - - - YES S SUPPLY AIR
SOLID STATE SPEED CONTROL - YES YES - YES TEMP. TEMPERATURE
AIR DISTRIBUTION DESIGNATION
TAT CONTROL - e - - - ES - HVAC DESIGN REQUIRES: YES NO / QT ' THERMOSTAT
FACTORY FABRICATED CURB MODEL N0. - - _ - - - -
SONES 3.1 �4.0 1,2 3.5 5. 7.7
-------- DUCT SMOKE DETECTOR I>< SUPPLY OR OUTSIDE AIR DUCT SECTION
NOTES: FIRE DAMPER(S) EXHAUST OR RETURN AIR DUCT SECTION
1. ALL FANS SHALL BE AMCA CERTIFIED. SMOKE DAMPER(S) -'� OPPOSED BLADE MANUAL VOLUME DAMPER
2. EF-1,3 SHALL BE PROVIDED WITH TIME DELAY SWITCH & DELUXE ALUMINUM GRILLE. -• SIDEWALL REGISTER WITH AIRFLOW ARROW
FIRE RATED ENCLOSURE �'� L `� CEILING DIFFUSER WITH AIR FLOW ARROW
3. EF-1,3 SHALL BE INTERLOCKED W/LIGHT SWITCH. FIRE RATED ROOF/FLOOR IA.Q. SOUND LINING
CEILING ASSEMBLY
ELBOW UP (SUPPLY OR OUTSIDE AIR)
FIRE STOPPING �,., ELBOW DOWN (SUPPLY OR OUTSIDE AIR) 3.Z 8.2
SMOKE CONTROL �--�� ELBOW UP (RETURN OR EXHAUST AIR)
' ELBOW DOWN (RETURN OR EXHAUST AIR) Revisions
9(7 ELBOW W/TURNING VANES A BL5-03-00 DG. PT. COMMENT
VWN" FLEXIBLE DUCT (INSULATED R-6 MIN.)
S ' DUCT MOUNTED SMOKE DETECTOR
�-� UNDER CUT
Project
9933alem
Mol
M CHAI�IICAL MOTES AND SCHEDULES Sheet 1 of 7
r ,
IL fit r
E ;�=
., . .�_.
Cl
0
Seal (AR 1 6320`
7 .T ! .