Loading...
00-0332-036 W 0..o...I D.. :.. E O ma L c0 N M.YI OW • v O M � y ■� O t.:: �-! LLJ LD U •` LLJ c O a!': O N Q _ o° Ym � Z � . • z° w LL 'v'� O o o.. Q u- GENERAL NOTES U � �Q �~ m 1. ALL PIPING,HANGERS,SUPPORT METHODS AND SPRINKLER HEADS TO BE ■` 0 3 Q INSTALLED IN STRICT ACCORDANCE WITH N.F.PA 13, AND ALL LOCAL a CODES AND ORDINANCES. _ ui ....... ............ -.• 2. SPARE SPRINKLER HEADS AND WRENCHES SHALL BE PROVIDED IN = � ti z a ACCORDANCE WITH N.F.PA 13. 91000 W Q 3. ALL RATED WALLS AN FLOORS TO BE PROPERLY SLEEVED AND SEALED = c� WITH APPROVED FIRE/SMOKE STOP MATERIAL. W a 4. HYDRAULIC DATA PLACE CARD TO BE PLACED ON SYSTEM RISER. m W z"' Co 5. ALL SPRINKLER HEADS IN ELEVATOR MACHINE ROOMS,ELECTRICAL ROOMS , o AND MECHANICAL ROOMS SHALL BE PROVIDED WITH HEAD GUARDS. -� �f 6. PROVIDE INSPECTOR'S TEST CONNECTION AND DRAIN AS PER N.F.PA 13 �; LL, 1' 1" REQUIREMENTS. o W .: 7. TEMPERATURE CLASSIFICATION FOR ALL SPRINKLER HEADS SHALL BE . ORDINARY UNLESS NOTED OTHERWISE ...:::.: UPRIGHT 1 1/4" INDM'f1NG VALVE SPRINKLER B. DESIGN CRITERIA: 1 1/2 IN VAiIE BOX S AT TOP DESIGN CRITERIA SHALL BE BASED ON N.F.PA 13, ORDINARY W/ T4 HAZARD GR. 1. .15 GPM PER SO. FT., 130 SQ. FT. MAX COVERAGE '' 1• PER HEAD. 1500 SQ. FT. REMOTE ARE . 1 PARKING E. MECHANICAL ROOMS 1 .. ..........................:. DESIGN CRITERIA SHALL BE BASED ON N.F.PA 13 LIGHT HAZARD, .10 GPM PER SO. FT., 225 SQ. FT. MAX COVERAGE UNE OF HYDRAULIC REMOTE AREA, 2' 1" ' OFRSTNRS HEMS AT TOP { UT�HER 1500� )Q. FT. REMOTE AREA. MINIMUM 1500 SQ. FT. ORD.HAZARD GR. II, .20 GPM/ SQ. FT. 1' 1 DESIGN CRITERIA SHALL BE BASED ON N.F.PA 13, ORDINARY 1' 1 1/4' 1" HAZARD GR. it .20 GPM PER SO. FT., 130 SQ. FT. MAX COVERAGE PER HEAD, 1500 SQ. FT. REMOTE AREA (3RD do 4TH FLR.) :............... ...............................::::::.:::.::::::.:..::.,.. ............................:::::::.:::::::::::::.,::..............................::,.................,::.::.......':;. ..................................... ::::::::::::::::::....,: ....................:..::::.....................................€................................ . ;;:;::.:;;;;;;;;;:;:;.::........ ::...............................::......................::..............................................: ..................................::::::: .........................................................................:.:.....................:<...............................:;:...................................... 9. ALL VALVES CONTROLLING WATER SUPPLY SHALL BE PROVIDED WITH 2 1/2" A SUPERVISORY (TAMPER) SWITCH.000RDINATE LOCATION OF ALL FLOW AND TAMPER SWITCHES WITH ELECTRICAL CONTRACTOR. tot tos ttt I 10ALL PIPING ABOVE GROUND SHALL BE UGHTWALL THREADABLE STEEL PIPE FOR 2" AND SMALLER, ROLL AND GROOVED SCHEDULE 10 STEEL PIPE .> I FOR PIPING 2 1/2" AND LARGER. AWED XL AND ALLIED SCH. 10 OR APPROVED EQUAL FITTINGS FOR PIPING 2" AND SMALLER SHALL BE MALLEABLE IRON. 1 1 1 1 1" 1• 1• 1• 1• 150 PSI BANDED.THREADED.BLACK.ANSI B 16.3. FITTINGS FOR PIPING 2 1�2" AND LARGER SHALL BE MECHANICAL COUPLING I� I I SYSTEM AS MANUFACTURED BY VICTAUUC CORP.OR GRINNE "GRUVLOCK". LL CORP. toy ttz I UNDERGROUND PIPING SHALL BE DUCTILE CAST IRON, BELL AND SPIGOT U > c-- AWWA C111 AND C151.FITTINGS SHALL BE MECHANICAL JOINT CAST IRON, AWWA C110 AND C111,AND FLANGED FITTINGS AWWA C110. FOR STRAIGHT RUNS OF PIPE: "ON" PUSH ON TYPE JOINT. 4-1 -+-� 1 1/4' 1 1/4' 1 1/4' 1 1/4" 1 1/4' 1 1/4' 1 1/4' 1 1/4' 1 1/4' 1 1/4" 1 ALL FITTINGS SHALL BE FROM SAME MANUFACTURER. •• � � � � 11.PRESSURE TEST AND FLUSH THE SYSTEM IN ACCORDANCE WITH N.F.PA - I I 13 REQUIREMENTS.Q ENTS. SUBMIT N.F.PA 13 FORMS 85A AND 85B. � 103 toe 113 •� Q� 0 12.PROVIDE AUXILIARY DRAIN CONNECTION FOR ALL TRAPPED PIPING SECTIONS IN ACCORDANCE WITH N.F.PA 13.PROVIDE FLUSHING CONNECTIONS AS REQUIRED. m 1 1/4 /4 1 1/4" 1 1/4" 1 1/4" 1 1/4' Zt 1 1/4" 1 1/4' 1 1/4' 1 1/4' 1 1/4" REMOVEABLE FITTINGS SHALL BE PROVIDED AT ENO OF CROSSMAINS. E 24 4" z3 O 4" 4" 4" 4` 4` 13ALL FIRE PROTECTION EQUIPMENT AND DEVICES SHALL BE U.L. LISTED AND U MUTUAL (FM) APPROVED. • / / / 1 1/4 1 1/4 1 1/4 4. 1 1/4 1 1/4 1 1/4 1 1/4 14.GATE VALVES 2 AND SMALLER SHALL BE O.S.&Y. THREADED BRONZE. (� RISING STEM.WEDGE DISC,175 WWP.GATE VALVES 2 1/2" AND LARGER SHALL BE - O I I O.S.&Y. FLANGED IBBM RISING STEM,SOLID WEDGE DI SC 175 WWP. ALL GATE • - VALVES SHALL BE U.L. LISTED AND F.M. APPROVED. _ 2• BUTTERFLY VALVES WITH OR WITHOUT INTEGRAL SUPERVISORY SWITCH MAY >: too toa t t4 4" RISER I'll BE USED WHERE PERMITTED BY N.F.PA 13. Z „ 15.CHECK MOUNTED.175 2 1/20 AND LARGER SHALL BE FLANGED IBBM SWING TYPE,BRONZE WWP C 1/4 :2D .175 LASS.U.L. LISTED AND F.M.F M APPROVED `) 1" 1" 1" 1" 1■ 1r 1w 1■ 16 .IT TAMPER SWITCH, r- - - ... G ? ? SUPERVISORY SWITCHES SHALL BE 120 V . . . . OLT CLOSED CIRCUIT U.L LISTED AND F.M. APPROVED.FLOW SWITCHES SHALL BE PADDLE TYPE,SIN LE O O I I 4" FLOOR ROL POLE DOUBLE THROW WITH ADJUSTMENT FOR SENSITIVITY TO FLOW WITH TIME > : "'' AS DELAY, U.L LISTED AND F.M. APPROVED.POTTER-ROEMER OR APPROVED EQUAL. . 1 ..... 105 1t0 I 17. THREADS AT FIRE DEPARTMENT CONNECTIONS SHALL CONFORM WITH LOCAL FIRE HR 1 1/4" 1 1/2' 1 1/2' - ' DEPARTMENT STANDARDS PROVIDE METAL COVER AT INLETS 18.THE WORK THAT IS TO BE DONE UNDER THIS CONTRACT INCLUDES THE FURNISHING I OF ALL LABOR.MATERWS AND EQUIPMENT ,PERMITS.FEES.INSPECTIONS.TESTS, s _ OF FIRE PROTECTION SYSTEM ...�J .:.... ' ' HEREIN. INSURANCE.ETC. REQUIRED FOR THE CO SHOWN ON THE DRAWINGS AND LISTED :..:::::::::::.::::::::................................::::;.::::::.::::::::.................................. - _ ......................... .:.... . .................. ... SPRINKLER HEADS AT TOP ... ........ .::.:.:. ...::.:. ....... . ........ ..... ......... 19 DRAWINGS NOT SHOW EVERY .THE WINGS ARE GENERALLY DWGRAMMATIC.THEY DO N BEND.OFFSET OR OTHER FITTINGS WHICH MAY BE REQUIRED FOR THE INSTALLATION OF STAIRS IN THE SPACE ALLOCATED, OR FOR COORDINATION WITH OTHER TRADES. ..... :....... .... ......_.. .. ... ..... VERIFY ALL SPACE CONDITIONS AND DIMENSIONS MENSIONS AT JOBSITE PRIOR TO ............................. . FABRICATION OF PIPING AND INSTALLATION OF EQUIPMENT AND MATERIALS. 20. ALL WORK SHALL BE IN ACCORDANCE WITH N.F.PA 13, N.F.PA 24, N.F.PA 25. N.F.PA 101. SOUTH FLORIDA BUILDING CODE (CHAPTER 38) AND IN CONFORMANCE WITH ALL LOCAL CODES AND ORDINANCES. 21. PROVIDE IDENTIFICATION FOR PIPING WITH COLOR BANDS, LEGEND FLOW ARROWS IN ACCORDANCE WITH A.N.S.I. A13.1. ALL VALVES SHALL BE PROVIDED WITH ENGRAVED ANODIZED ALUMINUM VALVE TAGS. PROVIDE ENGRAVED NAMEPLATE FOR ALL CONTROL VALVES. INSPECTOR'S TEST, MAIN DRAIN, AUXILIARY DATA CARD, AUXILIARY DRAINS. 11 /27/01 FOURTH FLOOR FIRE PROTECTION P 4 A N 22. ALL WORK SHALL BE PERFORMED BY STATE LICENSED AND CERTIFIED PERSONNEL IN Revisions ACCORDANCE WITH FLORIDA ADMINISTRATIVE CODE 4A-46 do 4A-48. SUBMIT TO OWNER'S REPRESENTATIVE AS BUILT DRAWINGS, OWNER'S MANUALS, SCALE: 1/8"=1'-O° MAINTENANCE MANUALS. Project 9933alem FPw5 Sheet 5 of 8 4 s rn v C) v • e f'