PLUMBING SPECIFICATIONS
1 WASTE, DRAIN AND VENT PIPING SHALL BE SERVICE WEIGHT CAST IRON, NO HUB 22 BALANCE ALL DUCT SYSTEMS, INCLUDING SUPPLY DIFFUSERS, RETURN
FITTINGS ARE ACCEPTABLE. SCHEDULE 40 GALVANIZED STEEL OR DWV COPPER MECHANICAL SPECIFICATIONS EXHAUST REGISTERS AND TOILET EXHAUST, TEST AND BALANCE
MAY BE USED FOR PIPING 1-112" OR LESS, SHALL BE PERFORMED BY AN INDEPENDENT, APPROVED AND
CERTIFIED AABC OR NEBB CONTRACTOR. SUBMIT TWO COPIES OF
2 POTABLE WATER PIPING, CONDENSATE DRAIN AND RELIEF PIPING SHALL BE TYPE 1 HVAC WORK SHALL BE PERFORMED BY A LICENSED HVAC CONTRACTOR, THE FINAL REPORT TO THE LANDLORD.
OR "M" FHARD DRAWN COPPER WITH WROUGHT COPPER FITTINGS. WHO SHALL BE THOROUGHLY FAMILIAR WITH THE STANDARDS,
REGULATIONS, PROCEDURES, CONDITIONS, MINIMUM BASIC CRITERIA 23 PIPING AND DUCTWORK SHALL BE HUNG FROM JOISTS AND /OR BEAMS.
3 INSULATE HOT AND COLD WATER PIPING WITH 1 THICK OWENS CORNING, FIBERGLASS AND CONSTRUCTION REQUIREMENTS OF THE LANDLORD. APPROVED TYPE DRILLED-IN ANCHOR FASTENERS WILL BE ALLOWED
25 ASJ, JOHNS MANVILLE AP OR APPROVED EQUAL INSTALLED PER MANUFACTURERS FOR INTERMEDIATE SUPPORT INSTALLATIONS INTO CONCRETE ROOF
REQUIREMENTS. INSULATION SHALL BE CONTINUOUS THROUGH WALLS, FLOORS, 2 NOT USED DECK AS APPROVED BY THE LANDLORD.
CEILINGS, ETC. 3 HVAC SYSTEMS INSTALLATION SHALL CONFORM TO LATEST ADOPTED
EDITIONS OF U.B.C., U.M.C., OSHA, AND SAFETY STANDARDS, LOCAL 24 LOCATION OF AIR DISTRIBUTION DEVICES SHALL BE AS INDICATED ON
4 RUN WATER HEATER RELIEF LINE AND CONDENSATE DRAIN LINE DOWN IN WALL AND ORDINANCES AND ALL LOCAL AUTHORITIES HAVING JURISDICTION. THE THE ARCHITECTURAL REFLECTED CEILING PLANS.
OUT TO NEAREST INDIRECT HUB DRAIN, FLOOR DRAIN, FLOOR SINK OR Y FITTING IN MOST STRINGENT REQUIREMENTS SHALL GOVERN WORK. 25 COORDINATE CEILING ACCESS PANELS WITH ARCHITECTURAL REFLECTED
LAVATORY TAILPIECE. TERMINATE WITH A 2" AIR GAP.
4 THE ENTIRE WORK SHALL BE PERFORMED IN ACCORDANCE WITH THE CEILING PLANS AND ELECTRICAL LIGHTING LAYOUTS.
5 N/A LANDLORD'S APPROVED CONSTRUCTION DOCUMENTS AND LANDLORD'S
TENANT'S MANUAL, 26 NOT USED
6 PROVIDE AIR CHAMBERS AT ALL FIXTURES OR SHOCK ABSORBERS AT EACH BATTERY. ALL DETAILS AND INFORMATION CONTAINED IN THE LANDLORD'S TENANT Q
DESIGN HANDBOOK, WHETHER APPEARING ON THESE PLANS OR NOT, SHALL Q
7 PROVIDE SECTIONAL SHUT-OFF VALVES ON EACH BRANCH AND RISER, CLOSE TO MAIN, BE CONSIDERED AS PART OF THE TENANT'S PLANS AND CONSTRUCTION 27 INSTRUCT OWNERS REPRESENTATIVE OF THE OPERATION AND MAINTEN-
WHERE BRANCH OR RISER SERVES 2 OR MORE PLUMBING FIXTURES OR EQUIPMENT REQUIREMENTS. ANCE OF THE SYSTEM. PROVIDE AT LEAST ONE OPERATING MANUAL �--
CONNECTIONS, AND ELSEWHERE AS INDICATED. FOR EACH AND EVERY PIECE OF EQUIPMENT, INCLUDE COPIES OF ALL U o
5 INCLUDE DUCTWORK, THERMAL AND ACOUSTIC LINING INSULATION, AIR BULLETINS, INSTRUCTIONS, OPERATING AND MAINTENANCE PROCEDURES W
8 PROVIDE SHUTOFF VALVES AT INLET OF EACH PLUMBING EQUIPMENT ITEM, AND AT DISTRIBUTION DEVICES, AIR CONDITIONING UNITS, EXHAUST FANS, AUTOMATIC AND PART LISTS. INCLUDE CERTIFICATES OF WARRANTY AND/OR
INLET OF EACH PLUMBING FIXTURE, AND ELSEWHERE AS INDICATED. TEMPERATURE CONTROLS AND ALL THE EQUIPMENT ACCESSORIES AND GUARANTEE WITH ALL NECESSARY INFORMATION FILLED IN APPROP- _
DEVICES REQUIRED TO MAKE A COMPLETE AND OPERATIONAL SYSTEM. RIATELY. u �
9 INSTALL CLEANOUTS IN BUILDING DRAIN PIPING AS INDICATED AND AS REQUIRED BY
LOCAL PLUMBING CODE, AT EACH CHANGE IN DIRECTION OF PIPING GREATER THAN 6 COORDINATE WORK WITH RESPECTIVE TRADES. VERIFY LOCATIONS 28 PROVIDE TWO SETS OF RECORD DRAWINGS SHOWING ACCURATELY Q N
45 DEG, AT MINIMUM INTERVALS OF 50' FOR PIPING 4" AND SMALLER AND 100' FOR FROM ARCHITECTURAL, STRUCTURAL AND ELECTRICAL DRAWINGS, THE ACTUAL AS BUILT CONDITIONS.
LARGER PIPING, AND AT BASE OF EACH CONDUCTOR. INSTALL FLOOR AND WALL DRAWINGS, FIELD MEASUREMENTS AND SUPPLIERS SHOP DRAWINGS Z
CLEANOUT COVERS FOR CONCEALED PIPING, SELECT TYPE TO MATCH ADJACENT VERIFY AND COORDINATE ELECTRICAL CHARACTERISTICS WITH THE 29 ALL MECHANICAL EQUIPMENT SHALL BE UL APPROVED WITH UL LABEL Q Lo
BUILDING FINISH (VERIFY SELECTION WITH ARCHITECT PRIOR TO ORDERING.) ELECTRICAL CONTRACTOR, BEFORE PURCHASING EQUIPMENT OR AND SHALL MEET STATE REQUIREMENTS. N
DEVICES, TO INSURE COMPATIBILITY BETWEEN THE EQUIPMENT o
10 INSULATE ALL EXPOSED SANITARY AND WATER PIPING AT ALL HANDICAP RATED REQUIREMENTS AND THE DESIGNED ELECTRICAL WIRING. 30 REMOVE ALL RUBBISH CAUSED BY THIS WORK AND KEEP ALL EQUIP-
LAVATORIES WITH FULLY MOLDED, TRUEBRO, HANDI LAV-GUARD INSULATION KIT MENT CLEAN. L U)
MODEL #102. 7 VISIT THE PREMISES TO DETERMINE EXISTING CONDITIONS, FULL EXTENT Q x
31 ELECTRIC MOTORS SHALL BE NON-OVERLOADING HIGH EFFICIENCY TYPE, Q J
11 PROVIDE CAST BRASS OR CHROME ESCUTCHEONS WITH SET SCREW, DEEP TYPE, TO OF THE WORK AND VERIFY WITH GOVERNING BODIES. REVEAL AND NON-RADIO INTERFERING. o
COVER SLEEVES OR OF A SIZE TO COVER FITTING PROJECTIONS. PROVIDE DISCLOSE TO THE OWNER AND/OR THE LANDLORD ALL UNUSUAL, J O
ESCUTCHEONS FOR ALL EXPOSED PIPING THROUGH WALLS, FLOORS AND EXPOSED IRREGULAR, CONFLICTING, SPECIAL OR UNFORESEEABLE CONDITIONS, 32 EQUIPMENT ACCESS SHALL CONFORM TO UMC SECTION 505.
CEILING. POSSIBLE CONFLICTS WITH REGULATORY OR UTILITY RELATED RESO- � o Q
LOTIONS OR STANDARDS THAT MAY POTENTIALLY MODIFY OR IMPAIR 33 PROVIDE FIRE DAMPERS AT ALL PENETRATIONS OF FIRE RATED WALLS. Q Q, Q
12 THE DOMESTIC WATER PIPING SYSTEM SHALL BE STERILIZED PER LOCAL CODE. THE QUALITY OF THE INTENDED DESIGN, CEILINGS, ETC. AND AT ALL PLACES REQUIRED BY CODES. U .o 0
13 PROVIDE TRAP PRIMERS ON ALL FLOOR AND HUB DRAINS. NO SUBSEQUENT ALLOWANCE FOR TIME OR MONEY WILL BE CONSIDERED 34 PENETRATIONS OF FIRE RATED SURFACES SHALLBE MADE WITH A
14 N/A FOR ANY CONSEQUENCES RELATED TO THE FAILURE TO EXAMINE SITE NON-COMBUSTIBLE MATERIAL OF FIRE RATING EQUAL TO THE MATERIAL
CONDITIONS, REVIEW OTHER TRADES REQUIREMENTS AND VERIFY PENETRATED AND SHALL COMPLETELY FIRE STOP. REFER TO THE
FIRE SPRINKLER SPECIFICATIONS ARCHITECTURAL PLANS TO DETERMINE FIRE-RATED SURFACES.
REGULATORY ISSURES BEFORE SUBMITTING ANY PROPOSALS. LU
8 OBTAIN AND PAY ALL PERMIT AND INSPECTION FEES AS REQUIRED 35 LABEL EVERY PIECE OF EQUIPMENT, EACH DUCTWORK SYSTEM AND
1 THE EXISTING SPRINKLER SYSTEM SHALL BE MODIFIED AS REQUIRED DUE TO THE NEW FOR MECHANICAL WORK INCLUDING ALL CHARGES BY THE LOCAL EACH PIPING SYSTEM. WHERE APPLICABLE INDICATE THE NAME OF THE Q
CONSTRUCTION TO MEET THE REQUIREMENTS OF NFPA 13, THE LOCAL CODE, AND THE GOVERNMENT AND UTILITY COMPANIES. STORE.
OWNER/TENANT/LANDLORDS INSURER. PIPING DRAWINGS SHALL BE SUBMITTED TO THE EL
APPROPRIATE APPROVAL AGENCY AS OUTLINED BY THE CITY SUBMITTAL REQUIRE- 9 LAYOUT IS STRICTLY DIAGRAMMATIC. INSTALL EQUIPMENT, DUCTWORK 36 N/A W
MENTS, THE SPRINKLER CONTRACTOR SHALL BE LICENSED TO DO WORK IN THIS STATE. AND PIPING SYSTEMS TO MEET FIELD CONDITIONS. INCLUDE ALL 37 INCLUDE ALL WIRING UNDER 100 VOLTS, WIRING FOR AUTOMATIC
ALL PIPING MODIFICATIONS REQUIRED WILL BE INCLUDED IN THIS CONTRACT. DUT AND PIPING TRANSITIONS, FITTINGS, OFFSETS AND REQUIRED CONTROL AND INTERLOCKS. LINE VOLTAGE WIRING ABOVE 100 VOTS Z W
SPRINKLER HEAD TYPES SHALL BE BUILDING STANDARD. (VERIFY WITH ARCHITECT.,) SIZE CHANGES AS NECESSARY TO SUIT THE SPACE AVAILABLE. SHALL BE UNDER THE ELECTRICAL DIVISION OF THE SPECS INCLUDING ::D >
SPRINKLER CONTRACTOR SHALL PROVIDE TO THE OWNER'S AND LANDLORD'S STARTERS AND DISCONNETS UNLESS INCLUDED WITH EQUIPMENT. 0!�
REPRESENTATIVE A COMPLETE SET OF SPRINKLER DRAWINGS INCLUDING MODIFIED 10 PROVIDE SEIXMIC ANCHORAGE AND BRACING FOR THE LATERAL AND 0
PIPING LAYOUT AND SPRINKLER HEAD LOCATIONS FOR APPROVAL PRIOR TO VERTICAL SUPPORT OF PIPING AND MECHANICAL EQUIPMENT AS 38 CONTROLS AND INTERLOCK WIRING SHALL BE INSTALLED IN CONDUIT --I Q [-
INSTALLATION. SUBMIT SPRINKLER PIPING DRAWINGS TO LANDLORD'S INSURER FOR REQUIRED BY T-22-94215 (M) AND/OR SMACNA GUIDELINES FOR OR EMT. - W
APPROVAL AND PROVIDE INSURER'S WRITTEN APPROVAL PRIOR TO COMMENCING WORK. SEISMIC RESTRAINT OF MECHANICAL SYSTEMS AND PLUMBING PIPING. n U)
39 PROVIDE FIRE RESISTANT TYPE FLEXIBLE DUCT CONNECTORS ON THE � 0 z
2 UPON COMPLETION OF THE SPRINKLER SYSTEM, THE SPRINKLER CONTRACTOR SHALL 11 DUCTWORK SHALL BE GALVANIZED ZINC COATED STEEL SHEETS INLET AND DISCHARGE T W Q
HYDROSTATICALLY TEST ALL PIPING PER NFPA AND LOCAL CODE AUTHORITIES. . DUCT CONNECTIONS OF ALL EQUIPMENT s
FABRICATE IN ACCORDANCE WITH SMACNA STANDARDS, WITH AIR CONTAINING FANS. U _
PROPERLY FILLED OUT SPRINKLER CONTRACTORS MATERIAL AND TEST CERTIFICATES �
MUST BE FURNISHED TO THE LANDLORD'S PROJECT MANAGER AT THE JOB SITE, AND TO MAXIMUM FLEXIBLE DUCTWORK SHALL NOT EXCEED 5 FEET IN TIGHT JOINTS. ROUND DUCTWORK SHALL BE FACTORY FABRICATED. 40 LOCATE THE THERMOSTAT AND INSTALL AS SHOWN ON THESE DOCUMENTS. < = oD
THE LANDLORD'S INSURANCE RATING BUREAU HAVING JURISDICTION. LENGTH. COMPLY WITH ALL THE RECOMMENDATIONS SET FORTH U) � Lo
3 ALL SPRINKLER PIPING SHALL MATCH EXISTING. IN THE LATEST EDITION PUBLISHED BY THE SHEET METAL AND AIR 41 CONDENSATE DRAIN PIPING SHALL BE TYPE IN OR "M" OR HARD
DRAWN COPPER WITH WROUGHT COPPER FITTINGS.
4 ALL SPRINKLER WORK TO BE BY LANDLORD'S CONTRACTOR AS DETAILED IN THE CONDITIONING CONTRACTORS NATIONAL ASSOCIATION (SMACNA).
TENANT MANUAL. DUCT SIZES SHOWN ARE CLEAR INSIDE DUCT LINING.. 42 RUN CONDENSATE LINES PER LANDLORD REQIREMENTS.
12 ALL MISCELLANEOUS METAL, ANGLES, BRACING, OR SUPPORTS EXPOSED 43 RE-USE EXISTING MANUAL RESET IONIZATION TYPE SMOKE DETECTOR
EXHAUST FAN SCHEDULE
TO THE WEATHER SHALL BE GALVANIZED IRON OR BLACK IRON PAINTED IN RETURN AIR DUCT AHEAD OF ANY OUTSIDE-AIR INLET. UPON DETECTI-
WITH ONE COAT OF RUST INHIBITING PAINT AND ONE COAT GRAY PRIMER. ION OF PRODUCTS OF COMBUSTION DETECTORS SHALL ACTIVATE. sa
NO. EF-1 13 CONSTRUCT , BRACE AND SUPPORT AND AIR PLENUMS, IN FULL ACTIVATION OF ANY DETECTOR SHALL CAUSE THE AIR-MOVING EQUIP-
ACCORDANCE WITH SMACNA RECOMMENDATIONS, TO PREVENT SAGGING MENT TO AUTOMATICALLY SHUT DOWN. ULS
MAKE NUTONE LIGHT/FAN COMBINATION AND TO MINIMIZE VIBRATIONS AFTER INSTALLATION. ADD AS AS MANY
(SEE ELECTRICAL DRAWINGS FOR MORE INFORMATION) BRACES AND SUPPORTS AS REQUIRED WITHOUT ADDITIONAL COST 44 ALL HVAC SYSTEM SMOKE AND FIRE DETECTORS SHALL BE COMPATIBLE
MODEL QTIOOL TO THE OWNER. WITH LANDLORDS FIRE ALARM SYSTEM.
CFM 100 14 DURING CONSTRUCTION, PROTECT DUCTWORK FROM INTRUSION OF 45 REFURBISH HVAC EQUIPMENT TO GOOD AS NEW CONDITION WHEN SHEET MP1
ESP" .10 DUST, DIRT AND DEBRIS. CLEAN DUCTWORK PRIOR TO INSTALLATION INDICATES EXISTING HVAC EQUIPMENT TO BE REUSED.
WATTS 100 OF AIR DISTRIBUTION DEVICES. THIS INCLUDES BUT IS NOT LIMITED TO PROVIDING NEW FILTERS, RECHARGING
V-PH 120-1 SYSTEM, REPLACING ANY DEFECTIVE PARTS. CONTRACTOR SHALL SUBMIT
UNIT SHALL INCLUDE: BACKDRAFT DAMPER, FLEXIBLE INLET AND OUTLET 15 INSULATE HOT AND COLD WATER PIPING ENTIRELY. PROPOSAL TO OWNER DETAILLING WORK TO REFURBISH EXISTING UNIT.
CONNECTIONS. 16 SUPPLY AND RETURN DUCTWORK SHALL BE ACOUSTICALLY LINED 46 VERIFY THE CONDITON , DEPT, AND LOCATION OF UTILITIES.
FOR A MINIMUM OF 16 FEET FROM THE INLET AND OUTLET OF THE AIR
PLUMBING FIXTURE SCHEDULE HANDLING UNIT OR DEVICE, IN ALL DIRECTIONS. 47 ALL WORK AND EQUIPMENT SHALL BE FULLY GUARANTEED FOR ONE (1)
YEAR FROM THE DATE OF FINAL PAYMENT AND ACCEPTANCE.
17 NOT USED
18 SUPPLY AIR SHALL BE FILTERED BEFORE ENTERING OCCUPIED SPACES. THERMOSTAT SCHEDULE
TYPE DESCRIPTION WHERE FILTERS ARE NOT INTEGRAL PART OF THE EQUIPMENT PROVIDE A
WC AMERICAN STANDARD ELONGATED CADET VITREOUS CHINA WATER CLOSET MINIMUM OF 1" THICK THROWAWAY FILTERS IN A SHEET METAL FILTER RACK MAKE: TED-AW MFG BY LIGHTSTAT
WATER CLOSET #2168.128, HANDICAPPED APPROVED, WITH OLSONITE #95 OR FRAME, FABRICATED AS PER SMACNA STANDARDS. o
OPEN FRONT SEAT LESS COVER, BOLT CAPS, AND ANGLE VALVE IN FLEX MODEL: ELECTRONIC o
�
SUPPLY. TO MEET A.D.A. AND MALL STANDARDS. 19 CEILING DIFFUSERS SHALL HAVE OPPOSED BLADE VOLUME DAMPERS. N TECH SUPPORT CONTACT: 800-292-2444 N Lo
Z U N Cl
FD JOSAM 30000A SERIES FLOOR DRAIN, NIKALLOY STRAINER. USE 30000E 20 PROVIDE VOLUME OR SPLITTER DAMPERS AT EACH BRANCH. � o a U
VERIFY COMPATIBILITY W/ EXISTING CONTROLS � u N
WHERE FUNNEL CALLED OUT ON DRAWINGS. 21 SQUARE DUCT ELBOWS SHALL HAVE DOUBLE THICKNESS TURNING APPROVED FOR a Lo
LAV AMERICAN STANDARD WHEELCHAIR LAVATORY 9141.011 WITH GOOSENECK VANES. BUILDING PERMr nNG PURPOSES u m ly 11
W 11
FAUCET AND WRISTBLADE HANDLES 7516.172, DRAIN ASSEMBLY 7723.018 AND BY MIAMI-DADE COUNTY EIRE DEPARTMENT w > __
'o �
CONCEALED CARRIER. PROVIDE STOPS IN SUPPLYS AND P-TRAP. FIRE PROTECTION CONTRACTOR'S 0 c o a w
INSULATE ALL EXPOSED SANITARY AND WATER PIPING AT ALL HANDICAP WORKING PLAN A3 PER NFPA 13 w
RATED LAVATORIES WITH FULLY MOLDED, TRUEBRO, HANKI LAV-GUARD SHALL 6E SUBMITTED FOR APPROVAL
INSULATION KIT MODEL #102. TO MIAMI-DADS FIRE DEPARTWNT DATE 7-11 -00
L'EFORE ANY FIRE PROTECTION SYSTEM
TP TRAP PRIMER, SMITH #2699 WITH STAINLESS STEEL ACCESS COVER IS INSTALLED OR REMODELED
WH CHRONOMITE #S-302, 120/1/60, WALL MOUNTED INSTANT WATER HEATER, -DATE SCALE 1/4"=1'-0"