00-1316-020 _ Y
7
DO NOT SCALE DRAWINGS CONTRACTOR MUST VERIFY -1a•+� w =` tie:, 9a
ALL DIMISIONS AND ADVISE CONSULTANTS OF ANY ERRORS
^ ^ OR UQ d SSIONS. NO VARIATIONS OR MODIFICATIONS TO v
WORk- SHOWN SHALL BE IMPLEMENTED WITHOUT PRIOR WRITTEN uK}
APPF;OVAL-. ALL PREVIOUS ISSUES OF THIS DRAWING ARE .
^ ------ SI IPFSPFFOED BY THE LATEST REVISION. ALL DRAWINGS
AND SPECIFICATIONS REMAIN THE PROPERTY OF a 14
MORRISON HERSHFIELD CORPORATION. NEITHER r"
MORRISON HERSHFIELD NOR THE ARCHITECT WILL '
BE PROVIDING CONSTRUCTION REVIEW OF THIS PROJECT.
, II
WALL-MOUNTED AIR- CONDITIONING UNIT SCHEDULE
O.A. ESP FAN MBH BTUH MIN.
TAG MODEL No. CFM CFM "WC HP COOLING HEATING VOLTS SEER j ACCESSORIES
EXISTING ALTAR
AC-1 WA301-13 1000 150 0.4 1/5 31.0 - 230/208 10 1,2,3,4,5 I ROOM
AC-2 WA301-B 1000 150 0.4 1/5 31.0 - 230/208 10 1,2,3,4,5 I REMOVE AND RELOCATE f
EXISTING WALL MOUNTED A/C
UNIT (REFER TO ARCH DWGS)
NOTES: I
A. COOLING CAPACITY BASED ON 80 DEC. F. db/67 DEC. F. wb EAT AND 95 DEG. F. AMBIENT.
ACCESSORIES: .. s .
�r
1. RETURN FILTER GRILLE AND SUPPLY GRILLE.
2. BAROMETRIC FRESH AIR DAMPER. AC I / I
3. PLEATED FILTER.
4. BARD J-PACKAGE CONTROLS. 1 8 110
5. BARD MODEL TEC20 ELECTRONIC CONTROLLER. OO (BELOW) 1F O
SELECTIONS ARE BASED ON PRODUCTS BY BARD.
NEW BELLSOUTH
EQUIPMENT ROOM
(BELOW)
S
— — — — — 6
SCHEDULE - FANS 5
AC10
0
TAG MODEL DUTY CFM E.S.P. MOTOR SIZE RPM DRIVE ACCESSORIES 00 00 •_ .,w
EF-1 LITTLE GEM III EXHAUST 135 0.5" 115 W 1500 DIRECT 1,2,3,4,5 3
NO LESS THAN 20' TO NEW A/C UNITS •—
PROPERTY LINE REPLACE EXISTING 2
(COORDINATE IN FIELD) UNDER SEPERATE
ACCESSORIES: PERMIT 1
1. GRAVITY BACKDRAFT DAMPER. F L O O R PLAN — HVAC
2. WIRE INTO WALL SWITCH. A 11/10/00 ISSUED FOR PERMIT
3. SPEED CONTROLLER.
4. TIMECLOCK CONTROL WITH HOA OVERRIDE SWITCH. M • 1
5. DISCONNECT SWITCH.
1/4 = 1'-0" No. Date Action ';A
SELECTIONS ARE BASED ON PRODUCTS BY COOK.
a
&G LLSOUTH Mobility
MECHANICAL FLAG NOTES: O
1. AC-1, AC-2, WALL MOUNTED AIR CONDITIONING UNIT. SEE DETAIL A THIS
M 0 R R I S 0 N
DRAWING. H E R S H F I E L D
1000 W McNab Road, suite 300, Pompano Bch,FIDrida 33069
2. "IEF-1, CABINET CEILING FAN. MOUNT WITH SOLID STATE SPEED Tel: (954) 781-0177 Fax: (954) 781-0593
CONTROLLER HIGH ON ADJACENT WALL WHERE ACCESSIBLE.
COORDINATE FAN AND DUCTWORK WITH CABLE TRAYS AND OTHER ,,•'', w
TRADES. COORDINATE ROOF PENETRATION WITH EXISTING CONDITIONS.
MOUNT FAN AS HIGH AS POSSIBLE. INTERLOCK FAN WITH TIMECLOCKjn's t ' ' '�! �•
AND MANUAL OVERRIDE SWITCH. SEE DETAIL B THIS DRAWING.
3. HVAC CONTROL PANEL. MOUNT ON WALL AT 5'-0" A.F.F.
4. NEW THERMOSTAT MOUNTED ON CONTROL PANEL, TYPICAL. .'4
� '('
BREIDERT TYPE L ROOF CAP 5. TIMECLOCK AND MANUAL OVERRIDE SWITCH TO EF-1. PROVIDED BY p _
W/ SFR-SF BASE SUPPLY MECHANICAL AND WIRED BY ELECTRICAL. MOUNT AT 60" A.F.F. ; t1.(p�`
FLASHING AND LAIRCF AIR ONDTIONING UNIT GENERAL NOTES: Project:FACTORY COUNTERFLASHING FURNISHED WITH WEATHER PROOF CASE FH G 0 CELL SITE
INSTALL UNITS WITH 20 CLEAR FOR 1. INSTALL WORK IN ACCORDANCE WITH ANY APPLICABLE LOCAL CODES HOPE LUTH E RAN CHURCH
GRILLES MAINTENANCE ON BOTH SIDES AND ORDINANCES. MAKE ANY MODIFICATIONS REQUIRED TO SATISFY 6330 BIRD ROAD
ROOF 18" M
THE LOCAL INSPECTING AUTHORITY. MIAMI, FLORIDA
3/4" AC UNIT CONDENSATE DRAIN WITH TRAP. 2. COORDINATE THE INSTALLATION OF THE MECHANICAL WORK WITH THE
TERMINATE APPROXIMATELY 6 ABOVE GRADE. WORK OF OTHER TRADES. COOPERATE WITH THE OTHER TRADES SO Drawing Title:
THAT NO WORK NEEDS TO BE REMOVED AND REINSTALLED DUE TO LACK
/-FROM STRAP o INSTALL CLEANOUTS IN CONDESATE DRAINS. OF COORDINATION. THE LOCATIONS REQUIRED FOR THE CELL SITE FLOOR PLAN
STRUCTURE STRAP DRAIN PIPE TO STRUCTURE AND EQUIPMENT, CONDUITS AND CABLE TRAYS HAVE PRIORITY.
EQUIPMENT- PAINT TO MATCH BUILDING. - HVAC
ROOM FLOOR\
LXH-FAN SPECIAL NOTE:
T• NEW GRAVEL CONCRETE SPLASH BLOCK
- SAME SIZE AS UNIT SLOPED AWAY FROM STRUCTURE THIS ROOM IS A Scale: Project No.
OPENING. AS SHOWN 6003708
EXHAUST FAN DETAIL B WALL MOUNTED AC UNIT DETAIL A CELLUAR EQUIPMENT Designer: Date:
SCHEMATIC - NO SCALE SCHEMATIC - NO SCALE FACILITY, AND IS JWE 10/27/00
Drawn By: Checked By:
UNMANED. ( NOT OPEN JWE
TO THE PUBL C) Drawing File: Client Approval
Revision No. Drawing No.
RDA Engineering 0 M1 ` 1
134 South Avenue, Suite 100, Marietta, Georgia, 30060
www.rdaeng.com, Tel. 770-421-0870, Fax 770-421-0885