00-1316-017 DO NOT SCALE DRAWINGS CONTRACTOR MUST VERIFY
- ALL- DIMISIONS AND ADVISE CONSULTANTS OF ANY ERRORS
--—
OR OMMISSIONS. NO VARIATIONS OR MODIFICATIONS TO
WORK SHOWN SHALL BE IMPLEMENTED WITHOUT PRIOR WRITTEN
APPROVAL. ALL PREVIOUS ISSUES OF THIS DRAWING ARE
3UPERSEDED BY THE LATEST REVISION. ALL DRAWINGS
- AND SPECIFICATIONS REMAIN THE PROPERTY OF
- - MC,RRISON HERSHFIELD CORPORATION. NEITHER
W,ORRISON HERSHFIELD NOR THE ARCHITECT WILL
WALL SURFACE BE PROVIDING CONSTRUCTION REVIEW OF THIS PROJECT.
BLACKBURN GUV 5821 U—BOLT
GROUND CLAMP ON EACH CABLE ANTENNA CABLE SUPPORT
BY OTHERS
SUPPORT. (TYP.) CABLE GROUND BAR 2"W x 1/4"D x LENGTH
REQUIRED FOR # OF CABLES USED, SOLID
COPPER W/ PREDRILLED 3/8" HOLES 2"O.C.
"TEE" TYPE EXOTHERMIC LENGTHWISE. COORDINATE HOLE SEPARATION /--ANTENNA CABLE
WELD TO GROUND BAR. W/ DIMENSIONS OF TWO HOLE CONNECTOR / BY OTHERS (TYP.)
USED.
CABLE SUPPORT
#2 AWG, GREEN COPPER,
#2 AWG SOLID BARE O STRANDED WIRE (INTERIOR
ti GROUND RING)
TINNED COPPER #2 AWG SOLID BARE TINNED COPPER
CONDUCTOR TO
- - - - - - - - - - - - -
GROUND CABLE. USE O 0 0 0 0 0 0 0 0 CONDUCTOR, TYP. CONNECT TO STEEL
MECHANICAL SPLIT BOLT O O 00000000 ON DRAWINGS
I O CABLE SUPPORT WHERE SHOWN
— _ _ _ _ _ — — — — — — — — TYPE CONN.
SEE DETAIL #3 CONNECT ANTENNA CABLE
GROUNDING SHEATH
CABLE SUPPORT CONDUCTORS TO GROUND
#2 AWG SOLID BARE TINNED COPPER (TYP.) BAR USING TWO HOLE 3/4" THREADED STEEL ROD (TYP.)
GROUND CONDUCTOR, TYP. CONNECT CONNECTORS TYP. BY 1/8�� MIN. 1" ±1/810 „
1/8" MIN.
TO GROUND BAR AT CABLE SUPPORT
ANTENNA CABLE INSTALLER. 1/4 MAX. 1/4 MAX.WHERE SHOWN ON DRAWING USING TWO SEE DETAIL #4
HOLE CONNECTOR. 4" °
COPPER CRIMP
JILL CONNECTOR,
T&B #54740
°dA g. OR APPROVED
d•: < ' ,.. EQUAL
#2 AWG SOLID BARE TINNED #2 AWG SOLID BARE TINNED
COPPER CONDUCTOR TO NEXT COPPER CONDUCTOR, TYP.
CABLE SUPPORT CONNECT TO GROUND BAR
AT CABLE SUPPORT WHERE
SHOWN ON DRAWING USING
TWO HOLE CONNECTOR. 7
6
BLACKBURN GUV 5821
U—BOLT GROUND CLAMP
ON EACH CABLE SUPPORT (TYP.) 5
- 7 GROUND SPLICE DETAIL 4
1 ANTENNA CABLE SUPPORT GROUNDING DETAIL 2 ANTENNA CABLE GROUNDING BAR DETAIL 3 ANTENNA CABLE WALL SUPPORT GROUNDING DETAIL (PROVIDED WITH PREFAB EQUIPMENT SHELTER/CABINET)
N.T.S. N.T.S. N.T.S. N.T.S. 3
2
1
A 11/08/00 ISSUED FOR BUILDING PERMIT
No. Date Action
—WALL SURFACE
®BELL S®NTH Mobility
ANTENNA CABLE SUPPORT BY OTHERS
CABLE GROUND BAR 2"W x 1/4"D x LENGTH AS
REQUIRED FOR # OF CABLES USED, SOLID COPPER M 0 R R IS 0 N
WITH PREDRILLED 3/8" HOLES 2"O.C. LENGTHWISE. H E R S H F I E L D
COORDINATE HOLE SEPARATION WITH DIMENSIONS FOR REMOVABLE COVER. COVER SHALL INTERIOR HALO GROUND RING
BRAND OF CONNECTOR USED. 3730 Chamblee Tucker Rd. Atlanta, GA. 30341
BE REMOVABLE BY HAND. NO Tel: (770) 939 2370 Fax: (770) 934 9476
FINISHED GRADE TOOLS SHALL BE REQUIRED FOR
INTERIOR INTERIOR REMOVAL.
01GROUND RING GROUND RING
00 IIII= III=III CONNECT GROUNDING
0 ° ° IIII=IIII =IIII= CONDUCTOR TO INTERIOR ,r
° = 2—0 LONG X 6 DIA.
0_1
2 COAXIAL CABLE, TYP. GROUND RING USING
1 SCHEDULE 40 WHITE PVC PARALLEL CRIMP TYPE
ANTENNA CABLE GROUNDING CONNECTOR. POINT TO
O° SHEATH CONNECTIONS TO 00 EXOTHERMICALLY WELD TO THE SHORTEST DIRECTIONS
00 GROUND BAR BY CABLE CONNECTOR, TYP. °0 0O GROUND ROD. TO THE HATCHPLATE.
O INSTALLER TYP. BRAIDED COPPER .0 A
q{
°° o0
1" WIDE SLOT FOR GROUND WIRE. Project: °
0o FLEXIBLE STRAP, TYP. 00 00 EXTEND 2 ABOVE GROUND RING.
TO oo FROM ANTENNAS #6 AWG GREEN INSULATED
STRANDED COPPER FHGO CELL SITE
SHELTER 00 °° GROUNDING CONDUCTOR
O PROVIDE STAINLESS 00 °° TYPICAL. HOPE LUTHERAN CHURCH
STEEL BOLTS, LOCK o0 W300
WASHERS AND NUTS, 00 O0 #2 AWG BARE TINNED SOLID COPPER
TYPICAL FOR ALL 00 0o WIRE (EXTERIOR GROUND RING) 6330 BIRD ROAD
EXTERIOR CONNECTIONS. U.L. APPROVED MIAMI, FLORIDA
#2 AWG SOLID BARE TINNED
GROUNDING CLAMP,
COPPER CONDUCTOR FROM GROUND ROD CRUSHED ROCK INSIDE, BELOW AND TYPICAL AT EACH
CABLE SUPPORTS. AROUND SLEEVE. EXOTHERMIC WELD CONDUIT. Drawing Title:
SHALL REMAIN VISIBLE.
PARALLEL EXOTHERMIC WELD 3 GROUNDING
"TEE" TYPE EXOTHERMIC DETAILS
WELDS TO GROUND BAR
#2 AWG SOLID BARE TINNED REFERENCE NOTES
COPPER CONDUCTOR TO THE O1 SOLID COPPER GROUND BAR, TYP.
NEAREST LIGHTNING PROTECTION
DOWNLEAD. 02 TWO—HOLE CONNECTORS WITH #2 AWG SOLID BARE TINNED COPPER.
PROVIDE #2 AWG SOLID BARE TINNED COPPER GROUND CONDUCTOR. Scale: Project No.
EXOTHERMICALLY WELD TO STRUCTURAL STEEL FRAME AND GROUND N.T.S. 6003708
BAR WITH A TEE TYPE WELD AT BOTTOM OF GROUND BAR.
BLACKBURN GUV 5821 U—BOLT GROUND
Designer: Date:
CLAMP ON THREADED ROD K.M.H. NOV/00
Drawn By: Checked By:
5 EXTERIOR HATCHPLATE GROUNDING DETAIL 6 GROUND ROD INSPECTION SLEEVE DETAIL TYPICAL MULTIPLE CONDUITS GROUNDING DETAIL H.S. K.M.H.
ANTENNA CABLE WALL GROUNDING BAR DETAIL (PROVIDED WITH PREFAB. EQUIPMENT SHELTER/CABINET) N.T.s. $ N.T.s. Drawing File: Client Approval
4 N.T.S. N.T.S.
Revision No. Drawing No.
* REFER TO DWG. E4.1 FOR MORE GROUNDING DETAILS CONTINUATION. 0 E 4 . 1