7615 SW 62 AVE ERPB-07-078-042 ... f
..................................
8
5
k.
FIXTURE S C H E D U L E TELEPHONE / DATA RISER DIAGRAM ELECTRICAL RISER DIAGRAM
LAMPS MANUFACTURER CZ) 1' CONE). STUB r
TYPE VOLTS DESCRIPTION N0. DESIGNATION MOUNTING & CAT. NO. REMARKS ABOVE CLNG.
,a
ELECTRICAL TENANT SPACE
WET LABEL WALL >:
26 WATT DAMP LABEL ROOM r CEILING yF ::.::.:.::::::::::•::::.::: �{
120 - - - - - - - - - - — - - - - - - - - - -
— 2 SETS OF
BRACKET W/ "JELLYJAR" 1 QUAD PL WALL -
40 3/0, 4 1 03 (G)
FLUORESCENT 2 F32TB SURFACE LITHONIA C232
IN 2' COND
120 STRIP LIGHT EXIST. TEL. 3/4' COND. STUB
EACH.
GUTIERDEZ
CEILING INFINITY LIGHTING DATA/CATV � TENANT 6' ABOVE CLG.C 120 COMPACT FLUORESCENT 1 42 WATT, RECESSED COMPACT "PL" FLUORESCENT DAMP LABEL BOARD TELEPHONE 400 AMP
4 —PIN PH75-142T—EB � A-38 TERMINAL Q LOZANO
POLE HUBBELL LIGHTING &BOARD
D 120 COMPACT FLUORESCENT 1 42 WATT, COMPACT "PL" FLUORESCENT 30 3�
� ARCJTLJJL MOUNTED RA65—PLT42—ELB-120—SAL—BOAR—LP -38
E 120 COMPACT FLUORESCENT 1 23 WATT RECESSED HUBBELL LIGHTING
PANEL 4W EL PANE
WALL LMS 100—PL7-120—SAL I c '15' '25' 2830 W. STATE ROAD 84, SUITE117
FT. LAUDERDALE, FL. 33312
F 120 INCANDESCENT 1 70 WATT RECESSED HUBBELL LIGHTING �
— — — —FIRST FLOOR PHONE: (954) 321 —3442
WALL KL 100— A-120
GROUND - - - - - - - - - - - - - - - - - - - - - — - - - (
BONDED TO FAX: 954) 321 -3864
MAIN ELEC. 400 AMP
SERVICE GROUND. 2-5ECTION
XIST. IY4' EMPTY CONDUIT TO TENANT SPACE/ EXTEND FEED-TRHU REVISIONS
RELOCATE TO NEW TENANT TEL. TERMINAL LOCATION 3 400 PANEL
EXIST. TELEPHONE SERVICE
METER
30 4W M
3 125 EXT. LIGHTS
125 CONTACTOR
ELEVATOR
BASEMENT
TO FPL
03 THWN CU GROUND MANUEL GUTIERREZ
TO C.WP., TO BLDG
FOOTING STEEL AND STATE OF FLA.''REG. No: 8253
TO 5/5'0 X 10'-0' r •• 'i
GROUND ROD. —
�,..o . u.t i�
V 11
CARLOS LOZANO
STATE OF FLA. REG. No. 0014722
D... .......................................................................................
................... ............ ................................................................................................
.......... D
_ .. .
J
2A-ZSOL
B 2A-32
ELECTRICAL SPECIFICATIONS
' C C c
E ;
EQUIP ROOM
1. PERI=ORM ALL WORK IN ACCORDANCE WITH 1=BG, NEC, AND ALL CODES, ORDINANCES,
AND AUTHORITIES HAVING JURISDICTION.
2. VERIFY SERVICE CHARACTERISTICS, LOCATION, AND CONNECTIONS At JOBSITE AND WITH E'
f.
F.P.<L. CO. PERFORM ALL WORK RELATED TO SERVICE IN ACCORDANCE WITH F.PAL. CO. ...
.................. .... ...... ... ...
D
STANDARDS AND REQUIREMENTS.
•
3. INSPECT JOBSITE i VERIFY ALL EXISTING CONDITIONS BEFORE SUBMISSION OF BID.
ADVISE ARCHITECT/ENGINEER OF ALL CONFLICTS BEFORE SUBMISSION OF BID. 2A-28 •
2A-32
4. ALL WIRE COPPER, TYPE THWN/THHN. CONDUIT IN SLAB OR UNDERGROUND SHALL BE •
PVC SCHEDULE 40. CONDUIT WITHIN BUILDING AND ABOVE GRADE MAY BE EMT. INSTALL W
NEC EQUIPMENT GROUNDING CONDUCTOR IN ALL CONDUITS. INSTALL PULL WIRES
IN ALL EMPTY RACEWAYS.MAINTAIN COLOR CODING FOR DIFFERENT VOLTAGE SYSTEMS
THROUGHOUT PROJECT.
C C C
5. PROPERLY ALIGN AND LEVEL PANELS. INSTALL TYPEWRITTEN DIRECTORIES INSIDE
COVER DOORS OF ALL PANELS IDENTIFYING EACH CIRCUIT IN PANEL.
6. USE PULLBOXES, SPLICE BOXES, WIREWAYS, AND GUTTERS WHERE REQUIRED OR
NEEDED TO SUPPLEMENT RACEWAY SYSTEMS.
CO
O
Z. GROUNDING SHALL CONFORM TO NEC 250. BOND ALL METAL PARTS. INSTALL
EQUIPMENT GROUNDING CONDUCTOR TERMINAL STRIPS IN ALL PANELS, BONDED �+
TO PANELBOX. 1 F W C�
... .. ...
8. ALL WIRING DEVICES SHALL BE SPECIFICATION GRADE, WHITE COLOR "
a RECEPTACLES LOCATED IN EXAM ROOMS SHALL BE HOSPITAL GRADE.
2A-18 �, w
D
f
2 9. WHERE SWITCHES, DIMMERS, RECEPTACLES ARE LOCATED SIDE-BY-SIDE, THEY SHALL E B O ►-�--1
BE INSTALLED IN MULTI-GANG BOXES WITH MULTI-GANG COVER PLATES, CUSTOM - P—�--4
21 MADE IF NECESSARY. USE BARRIERS AS REQUIRED TO SEPARATE DIFFERENT - �..�
VOLTAGES IN SAME BOX. E E
° 10. DELIVER CATALOGUE CUTS OF ALL LIGHTING FIXTURES, WIRING DEVICES, PANELS, A 24_:32 C 2A-34 Z
o DISTRIBUTION EQUIPMENT, ETC. TO ENGINEER FOR APPROVAL AT BEGINNING 2A 32 SEE SECTION A A-2�
C C
F O HT.
R POLE
S OF JOB AND BEFORE ORDERING.
ro B C. OOM ELE r O
11. VERIFY ELECTRICAL CHARACTERISTICS AND CONNECTION REQUIREMENTS OF ALL A
fi.
EQUIPMENT BEFORE INSTALLING BRANCH CIRCUIT OR CONNECTING TO ............. SHEET TITLE
.... ........
....... ................................ _ . ....
CIRCUIT. PROVIDE MATCHING RECEPTACLES FOR ALL EQUIPMENT FACTORY EQUIPPED .. ....... ....
E
WITH CORDS AND CAPS. .: -a ......... .............. .. .... ..
o Q
D D_
12 WI U _ L :................. ..................................... .... ......................................................... ..... .......... ELECTRICAL SITE PLAN
m RE P COMPLETE ALL A/C EQUIPMENT AND CONTROLS AS DIRECTED BY A/C 2A 28
o CONTRACTOR THERMOSTAT LOCATIONS ARE AS SHOWN ON A/C PLANS.
........
° __ .....
13. CONSULT WITH SECURITY, TELEPHONE, CABLE TELEVISION CONTRACTORS/PROVIDERS
N AND PROVIDE EMPTY RACEWAYS AS REQUIRED AND DIRECTED BY THE RESPECTIVE
CONTRACTORS. THIS INCLUDES CONDUIT NECESSARY FOR SERVICES ENTRANCES SCALE: 1'■ 1/8'
FROM PROPERTY LINE TO BUILDING.
......... ...............
G 14. CONSULT WITH ......... _.._. ........ ............ .. .... ._._.... ....... .... ........ _. . ......_ _ ......_. _._.
L BELLSOUTH TELEPHONE CO. AND WITH BUILDING OWNER TO VERIFY ....... ............
w TELEPHONE SERVICE REQUIREMENTS TO BUILDING.
JOB No.:
cm 15. OUTLET LOCATIONS SHOWN ON DRAWINGS ARE DIAGRAMMATIC ONLY. EXACT
LOCATIONS SHALL BE AS DIRECTED BY ENGINEER AND/OR ARCHITECT TO BEST
° SUIT FINAL CONSTRUCTION CONDITIONS. DATE:
16. COORDINATE WORK WITH WORK OF OTHER TRADES TO AVOID ALL CONFLICTS. 09/12/08
_ o
17. IT IS THE INTENT OF THESE DRAWINGS AND SPECIFICATIONS TO CALL FOR A
Z COMPLETE JOB, EVERYTHING CONNECTED, READY FOR USE. SHEET
Z 18. PROVIDE A REDUNDANT GROUND PATH TO OUTLETS AND EQUIPMENT LOCATED WITHIN
a PATIENT CARE AREAS AS PER NEC 511-13(A),(5)
ELECTRUCAL SITE P LAN
19. ALL OUTLETS IN PROXIMITY TO SINKS / LAVATORIES MUST BE GFCI. �®
3
E - 1
OF
u MARIANI