09-74R-007• • iJ r • • •Y•.�i r Yr• • •aU • • • r rNw w w •• Eusebio M. Mora Architect Fla. Lic. # AR0011732 L AIR CONDITIONING SPECIFICATIONS 1 THE WORK THAT IS TO BE DONE UNDER THIS HEADING INCLUDES THE FURNISHING OF ALL LABOR, MATERIALS, EQUIPMENT, PERMIT, FEES, INPECTIONS, TEST, INSURANCE, ETC. REQUIRED FOR THE COMPLETION OF THE AIR CONDITIONING SYSTEM SHOWN ON THE DRAWINGS AND/OR LISTED BELOW. 2 CONTRACTOR SHALL VISIT THE SITE TO BECOME FAMILIAR WITH ALL EXISTING CONDITIONS AND SCOPE OF WORK CONTRACTOR SHALL SUBMIT ANY DESCREPANCIE5 TO ARCHITECT -ENGINEER FIFTEEN (15) DAYS PRIOR TO BIDS. THE NATURE THIS PROJECT INVOLVES THE REMODELING OF EXISTING FACILITIES. 3 INTERRUPTION OF EXISTING FACILITIES AND / OR !SERVICES SHALL KEPT TO A MONIMUM AND THE CONTRACTOR SHALL FURNISH ALL MATERIALS REQUIRED VHENI=VER TEMPORARY CONNECTIONS ARE NECE55ARY TO MAINTAIN CONTINUITY OF SERVICES. COORDINATE ALL INTERRUPTIONS OF SERVICES WITH THE OWNER'S REPRESENTATIVE. 4 VENTILATION DUCTWORK SHALL BE GALVANIZED STEEL WITH GAUGES, DUCT CONSTUTION5, BRACING AND SUSPENSION IN ACCORDANCE WITH THE RECOMMENDATIONS SET FORTH IN THE LAT1r8T EDITION OF THE ASHRAE GUIDE AND SMACNA STANDARDS. DUCT SIZES SHOWN ARE "AIR5IDE" DIMENSION. VERIFY EXACT LOCATION OF DUCT WITH RESPECT TO STRUCTURE BEFORE FABRICATION. 5 FLEXIBLE DUCT SHALL BE SELF-SUPPORTING ALUMINUM CON5TRUTION WITH ]'THICK BLANKET TYPE INSULATON WITH EXTERIOR VAPOR BARRIER PROVIDE SPIN COLLAR WITH DAMPER AND EXTRACTOR WHERE FLEXIBLE DUCT IS CONNECTED TO RECTANGULAR DUCTWORK - AIR CONDITIONING: SUPPLY AND RETURN DUCTWORK SHALL BE 1-1/2" R-6 FIBERGLASS UL 181 LISTED. CLASS I' AIR DUCTWORK SHALL BE FABRICATED IN ACCORDANCE WITH 5.M.A.C.N.A. STANDARDS. "( ALL WORK SHALL BE COORDINATED WITH OTHER TRADFES TO AVOID INTERFERENCE WITH THE PROGRESS OF CONSTRUTION AND ITS STRICT COMPLIANCE WITH ALL APPLICABLE CODES AND STANDARDS. S VERIFY ALL DIMENSIONS WITH 5TRUCTURE PRIOR TO ANY FABRICATION OR INSTALLATION. S SUBMIT SHOP DRAWING OF ALL MATERIALS AND EQUIPMENTFOR APPROVAL PRIOR TO FABRICATION. 10 OBTAIN FULL INFORMATION REGARDING PECULIARITIES AND LIMITATIONS OF SPACE AVAILBLE FOR INSTALLATION OF THE EQUIPMENT AND MATERIALS UNDER CONTRACT.PROVIDE READY ACCESSIBILITY TO DAMPER$, VALVES AND OTHER APPARATUS, INCLUDING ANY PART OF SYSTEM REQUIRED TO BE REACHED FOR MAINTENANCE AND OPERATIONS. 11 VIBRATION ISOLATION: ALL EQUIPMENT AS PER MANUFACTURER RECOMMENDATIONS TO ELIMINATE ANY EQUIPMENT NOISE FROM BEING HEARD. 12 CUT ALL OPENINGS AND CHASES REQUIRED TO ACCOMMODATE THE WORK UNDER THIS DIVISION AND REPAIR ALL FLOORS, ETC. DAMAGED BY SUCH CUTTINGS_ ALL WORK DONE UNDER THIS HEADING MUST CONFORM IN EVERY RESPECT TO FINISH AND QUALITY MATERIALS AND WORKMANSHIP SPECIFIED UNDER APPROPRIATE 5ECTION5 FOR THE BUILDING. 13 GUARANTEES: A ALL COMPRESSOR MOTORS ON NEW EQUIPMENT FURNISHED UNDER TH15 CONTRACT SHALL HAVE A 5 YEARS PRODUCT GUARANTEE FROM DATE OF START-UP. B CONTRACTOR SHALL GUARANTEE ALL MATERIALS AND WORKMANSHIP FREE FROM DEFECTS FOR A PERIOD OF NOT LESS THAN I YEAR FROM DATE OF ACCEPTANCE. 14 TESTING: A ALL REFRIGERANT HIGH SIDE PIPING TO 300 PSIG LOW SIDE TO 150 PSIG AFTER TESTING EVACUATE SYSTEM TO 28" MERCURY GAUGE PRESSURE WITH VACUUM PUMP.HOLD FOR 25 HOURS WITH PUMP OFF BREAK VACCUM WITH REFRIGERANT. �3 BALANCE AIR SYSTEM TO DELIVER QUANTITIES AND EACH OUTLET WITHIN 5 PERCENT USING A.A.B.C. PROCEDURES AND TESTS SUBMIT AIR BALANCE TEST RESULTS FOR APPROVAL PRIOR TO FINAL INSPECTION. 15 REFRIGERATION SUCTION PIPING SHALL BE INSULATED WITH 3/4" INCOAFELX. ARMAFELX INSULATION MAY ONLY BE USED IN NON -PLENUM AREAS_ FINISH WHERE EXPOSED WITH 2 COATS OF WHITE LATEX PAIN ALL AS PER MANUFACTURER'S INSTRUCTION. 16 ALL REFRIGERANT PIPING SHALL BE TYPE "K" HARD COPPER, TOGETHER WITH WROUGHT COOPER SOLDER. FITTINGS JOINTS SHALL BE MADE WITH SILVER SOLDER OR "51LF05" ALL CONDENSATE DRAIN PIPING TO BE SCHEDULE 40 TYPE II HIGH IMPACT PVC WITH SLIP JOINT FITTING OF THE SAME MATERIALS WITH AN APPROVED SOLVENT INSTALLED IN A MANNER RECOMMENDED BY THE FITTING MANUFACTURER 11 DUCT MOUNTED SMOKE DETECTORS SHALL BE EDWARDS G5 MODEL No b2h45 IONIZATION DETECTOR OR APPROVED EQUAL. DETECTOR TO BE INSTALLED PER UL268A DETECTORS SHALL COMPLY WILL ALL REQUIREMENTS LISTED ON NF.P.A. SOA AND TIED TO FIRE ALARM SYSTEM. VENTILATION FAN SCHEDULE UNIT DESIGNATION TEF-1 AREA SERVED TOILETS LOCATION CEILING FAN TYPE CEILING TOTAL AIR CFM 80 FAN WHEEL TYPE CENT. DRIVE TYPE DIRECT FAN TIP SPEED,RPM MAX - FAN SPEED,RPM TOTAL STATIC PRESSURE,IN. OF H2O 0.10 z FAN MOTOR HP NON OVERLOAD 1.1 AMP FAN MOTOR STARTER TYPE - STARTER FURNISHED BY - ELECTRICAL SERVICE AVAILABLE 120-1-60 DESIGN MANUFACTURER NUTONE MODEL NUMBER LS 80L SERVICE SWITCH - SMOKE DETECTORS FIRE DAMPER - CONSTRUCTION STEEL MULTIBLADE BACKDRAFT DAMPER YES _w ":� 0 BIRDSCREEN YES E CONTROL TYPELj - AUTOMATIC SHUTTER Q FACTORY FABRICATED CURB - SONES 0.8 NOTES: 1. INTERLOCK TEF-1 WITH LIGHTS. 2, ACCEPTABLE MANUFACTURERS ARE COOK, GREENHECK OR PENN. FLEXIBLE COP ELECTRICAL E NT AANNDD LIQUID L NEOPRENE P) ANGLE FRAME THROUGH THROUGH VIBi 4" CONC. SLAE PROVIDE 1/8" STAINLESS 5%. CABLES AROUND UNIT (4) TYP A/C COMPRESSOR (1) 1/4 x 2 ANCHOR BOLT OR "HILTI SHOT IN EACH CORNER (4) TOTAL SEAL OPENING AROUND REFRIG. LINES W/ FOAM OR EQUAL. REFRIG. LINES w EXT. IN 4" PVC SLEEVE. A/C COMPRESSOR DETAIL 3/41 NOTE: A/C COND. UNIT 4 ANCHORAGE SHALL BE CAPABLE OF SUSTAINING 146 MPH WIND LOAD AS PER FBC 161S2_ A.H.U. MOUNTING DETAIL N.T.S. VOTE: t ALL FLEX AND RIGID DUCT TO BE A MIN, OF R-6 VALUE 2. INSULATE DRAIN PAN W/ 112" THIGH FIBEF;6LASS BLANKET WITH VAPOR BARRIER OR 3. SHEET FOAMED PLASTIC INSULATION W/ APPROVED FIRE RATING ON OUTSIDE SUFfACE ONLY. GOOSE NECK BIRD SCREEN BARREL TILE ROOF INTEGRAL CAP AND BASE FLASHING WOOD SHEATHING ON WOOD TRUSSES TYP. GOOSENECK DETAIL n.t.s. NOTE: PROVIDE BACKDRAFT DAMPER FOR EXHAUST FANS HVAG DE51raN REQUIRES: YES NO Duct Smoke; Detector X Fire Dam er(s) X Smoke Damper(s) X FTre Rated Enclosure X Fire Rated R/GeTlIng Assembly X Fire 5topping X Smoke Control X EXIST. A/C -EQUIPMENT SCHEDULE OUTDOOR UNIT - "RHEEM" RAPC-024JA INDOOR UNIT - "RHEEM" RCG2C-361-1 TOTAL. CAPACITY - 24,500 (BTU/H) NET 5EN515L£ - 18,100 (BTU/H) NET LATENT - 6,-100 (BTU/H) 5EER RATING - 14.40 AHU HEATER - 5 kW (11,065 BTU) INDOOR CFM - 600 MECHANICAL PLAN 1/4"..:.;;.; = EX15TING RE5I1DENCE a••r wrYr• •r• •a•• err• r r • • rase • ••r•• • •r• • •r•• • NOTE: PROVIDE P UNDEfRGUT00PR, Q ALL HA5ITA5LE cs w a 17 w k9 s 6761 Southwest 68th Terrace Miami, Florida 3 3 1 4 3 (305) 7 4 0— 5 1 8 5 F- 0 Z Z Q J Q. J Q 0 Z a I U' W' J 0 w M m � w rn L Li i r) ") o 0 J w �2-1 J �Q Of© cii o� a a Y Q � LJ� � �0 Of O z C .0 •,L{{ L O W U- E � C I W 4� z ca W w cc C w ,.. 0 L00 n 3 ca O (N cw O O'"' L �O iO v 0. U Lil w 7) O H F- � a DRAWN BY: MJA CHECKED BY: EMM ATTACHMENT NO.: ATTACHMENT DRAWING FILE NO.: DATE: 03/27/2006 SCALE: NOTED SHEET NUMBER: M1 o F 12