09-74R-006
ELECTRICAL NOTES 1. GROUNDED ROMEX or "SMURF MAY BE USED. 2. RIGID GALVANIZED STEEL CONDUIT SHALL BE USED WHERE EXPOSED UP TO 4 FEET AND SUBJECT TO MECHANICAL INJURY OR IN DAMP OR WET LOCATIONS. 3. STEEL RACEWAY INSTALLED UNDERGROUND SHALL BE PAINTED WITH TWO COATS BITUMASTIC PAINT. 4. WALL OUTLET BOXES SHALL BE 4• SQUARE. CEILING OUTLET BOXES SHALL BE 4" OCTAGON OR SQUARE. 5. CONTRACTOR SHALL FURNISH AND INSTALL ALL ELECTRICAL PANELS, WIRING DEVICES, CONDUIT, WIRING, MISCELLANEOUS SYSTEM, ETC. AS SHOWN ON PLANS OR AS REQUIRED FOR ACOMPLETE ELECTRICAL INSTALLATION. 6. FIXTURES AND LAMPS SHALL BE FURNISHED BY THE OWNER AND INSTALLED BY THE ELECTRICAL CONTRACTOR, UNLESS NOTED OTHERWISE, SEE NOTE 17. 7. PANELBOARD-ALL CURRENT CARRYING COMPONETS SHALL BE COPPER. SPLIT OR TWIN TYPE BREAKERS ARE NOT ACCEPTABLE. CIRCUIT DIRECTORIES SHALL BE NUMBERED CONSECUTIVELY ON THE LEFT SIDE TO 5OX AND CONTINUED ON THE RIGHT SIDE. & DISCONNECT SWITCHES SHALL BE GENERAL DUTY. 9. PROVIDE PULL WIRE IN EACH EMPTY RACEWAY. 10. CONTRACTOR SHALL DO ALL CUTTING, SLEEVING, EXCAVATING AND BACKFILLING NECESSARY FOR THE INSTALLATION OF HIS EQUIPMENT AND THE PATCHING THEREAFTER. PROVIDE ARC -FAULT CIRCUIT INTERRUPTER PROTECTION FOR ALL 15 AND 20 AMP 125 VOLT BEDROOM BRANCH CIRCUIT RECEPTACLE OUTLETS. NEC 210-12. CONTRACTOR TO VERIFY LOCATION WITH OWNER PRIOR TO INSTALLATION OF ALL TELEPHONE AND TELEVISION OUTLETS AS WELL AS FAN AND LIGHTING LOCATIONS. SYMBOL LEGENID MARK DESCRIPTION MARK DESCRIPTION DUPLEX RECEPTACLE OUTLET f i 5UIRFACE MTD. FLOURESCENT SWITCHED RECEPTACLE OUTLET RECESSED MTD. FLOURESCENT SINGLE RECEPTACLE OUTLET >(D< FLOODLIGHTS SURFACE MTD. QUADRUPLEX RECEPTACLE OUTLET O ® HEAT LAMP 4 EXHAUST FAN COMBO FLOOR DUPLEX RECEPT OUTLET ELECTRICAL PANEL SINGLE SPECIAL PURPOSE OUTLET �j SINGLE POLE SWITCH TELEPHONE OUTLET] 3 THREE WAY SWITCH TV TELEVISION OUTLET D SINGLE POLE SWITCH W/ DIMMER JO JUNCTION BOX ❑� DISCONNECT SWITCH FAN BOX W/ INCANDESCENT FIXTURE EXHAUST FAN WALL MTD. INCANDESCENT DOOR BELL SURFACE MTD. INCANDESCENT `'0 SMOKE DETECTORS TO BE HARDWIRED t INTERCONNECTED TO NOWSWITCHED KITCHEN OR BATHROOM LIGHTING CIRCUITS. 4" RECESSED HI -HAT -� COMPUTER DATA / LAN OUTLET ELECTRICAL SCHEDULE 'A' 150 A FLUSH 10 MTD. PA EL CIRCUIT NUMBER WIRE SIZE DESCRIPTION LOAD (WATTS) POLES C/B TRIP DEMAND NO. DEM. EXISTING LOADS * 14 LIGHTS / RI=G3=PT. (3W x 1803 S.F.) IF-15 A 5409 012 SMALL APF'LIANCES (2 Q 1500 W) IF-20 A 3000 012 GFI RECEPTACLES 10 BATHROOM 1P-20 A 1000 1112 REFRIGERATOR IP-20 A 1000 012 GARBAGE DISPOSAL IF'-20 A 600 * 6 RANGE 2P-50 A 12000 012 EXHAUST FAN OVER GOOKTOP IP-20A 1000 012 D15HWASHER IF-20 A 1000 012 WASHER IP-20A 1000 05 DRYER 2P-50A 5000 010 WATER HEATER *1 2P-30 A 3500 05 A/C-1 - A.N.U. W/ -1.5 KW HEATER (I 2P-40 A 5100 • 08 A/C-1 - G.U. a 125% (1) 21=-40 A 6200 NEW LOADS ( NEW SUBPANEL B) A 1-4 014 LIGHTS / REGEF T. (3W x 315 5.F_) IF-15 A 1125 A 5 012 SMALL APPLIANCE5 (1 m 1500 W) IP-20 A 1500 A (o 012 GFI RECEPTACLES 4v BATHROOM IF-20 A 1000 TOTAL LOAD 38,134 8,100 NON -CONCURRENT LOADS LOAD CALCULATIONS FIRST 10,000 W ,0 100% = 10,000 WATTS 2935 4 / 240 = 123 AMPS REMAINING 28,134 W * 409. = 11254 WATTS A/C LOAD 8,100 W w 100% 8,100 WATTS TOTAL LOAD = 29354 WATTS 1 11. CONTRACTOR SHALL INSTALL ALL STARTERS AND CONTROL DEVICES FURNISHED BY OTHER CRAFTS AND COMPLETE WIRING IN ACCORDANCE WITH MANUFACTURERS RECOMMENDATIONS AND APPROVED WIRING DIAGRAMS. ELECTRICAL EQUIPMENT FURNISHED BY OTHERS WILL BE CONNECTED UNDER THIS CONTRACT INCLUDING ALL NECESSARY WIRING, CONDUIT, AND FITTINGS. CONTROL WIRING SHALL BE UNDER THE SUPERVISION OF THE SUB -CONTRACTOR FURNISHING THE EQUIPMENT. 12. ELECTRICAL WORK SHALL COMPLY WITH ALL APPLICABLE LOCAL OR NATIONAL CODES AND WITH THE UTILITY COMPANY REGULATIONS. 13. PRIOR TO INSTALLATION OF ROUGH ELECTRICAL WIRING CHECK NAMEPLATE DATA OF AIR CONDITIONING EQUIPMENT, HOT WATER HEATERS, AND OTHER EQUIPMENT TO OBTAIN CORRECT WIRE SIZES AND OVERCURRENT PROTECTION. 14. ELECTRICAL INSTALLATION SHALL CONFORMTO REQUIREMENTS OF N.E.C.110-14(a) AND N.E.C. 384-2 FOR PANELBOARDS, INCLUDING SPACES ABOVE THE EQUIPMENT. 15. CONTRACTOR SHALL PREWIRE ALL TELEPHONE OUTLETS WITH 4/C #24 TELEPHONE CABLE RUN IN PARTITIONS AND DROPPED CEILING FROM INCOMING TELEPHONE JUNCTION BOX. 16. CONTRACTOR SHALL PREWIRE ALL TELEVISION OUTLETS WITH RGS COAXIAL CABLE RUN IN PARTITIONS AND DROPPED CEILINGS FROM INCOMING CABLE T.V. JUNCTION BOX. 17. CONTRACTOR SHALL PROVIDE 4" RECESSED H-HAT LIGHTING. COORDINATE SELECTIONS WITH OWNER. LECTRICAL INSTALLATION DESIGNED OF THIS PLAN IS INCOMPLIANCE AS SET =ORTH BY STATE OF FLORIDA STATUTES MODEL ENERGY EFFICIENCY CODES. EXIST COMBINATION ELECT. METER CAN 4 D I8C. 150 AMP WF' MAIN DISCONNECT (2) 5/0" x 10' GROUND RODS 111/0) 1/0 (CU) 1N 3/4" CONDUIT EXIST UNDERGROUND (3)-1/0 THW (CU) IN 11/2" CONDUIT TO F.P.L_ X-MER ELECTRIC (3)-1/0 THW (CU) IN 1-I/2" CONDUIT ELECT. i=ANEL 11,411 150 A W/ MC-5 RISER ELECT. SUBPANE II5 II 100A (3)-3 THW (CU) IN 1-I14" CONDUIT BOND TO COLD WATER LINE GROUND TO STL. iw FIOUNDATIONNT N.T.S. NOTE: ALL SAFETY SWITCHES TO HAVE 100,000 RMS SYS MINIMUM FAULT CURRENT RATING. (USE TYPE R FUSES REJECTION KIT AND SOLID NEUTRAL) PANEL SHALL BE DEAD FRONT CIRCUIT BREAKER TYPE AS SCHEDULED. CICUIT BREAKERS SHAL HAVE A MINIMUM INTERRUPTING RATING OF 10,000 AMPS AT 120 VOLTS, 15,000 AMPS AT 277 VOLTS. ELECTRICAL _PLAN 1/4" = EXISTING RESIDENCE •••• ••r • • ••r•• ••• • • • r • • • • • Y Y ••• ••• • • • •••W U • • •••• r•••• ••• •...' • • • • R • • Eusebio M. Mora Architect Fla. Lic. # AR0011732 6761 Southwest 68th Terrace Miami, Florida 3 3 1 4 3 (305) 7 4 0 --5 1 8 5 W J W U zz J J Q U_ U w W J W Q LA} w. 0 0 w � o 0 J W �F- 4 F- �Q �o �oo © a CC L.LJ� d W i>�O Of �o z C .� lL 10 � � C .0 ,r co L ai W 0 '> cd c lyW H c O L ~ n 3 Q 0 C w ,[0 W 0 co L O ac � 0 J w O I DRAWN BY: MJA CHECKED BY: EMM ATTACHMENT NO.: ATTACHMENT DRAWING FILE NO.: DATE: 03/27/2006 SCALE: NOTED SHEET NUMBER: E1 OF 12