AIR CONDITIONING SPECIFICATIONS
I THE WORK THAT IS TO BE DONE UNDER THIS HEADING INCLUDES THE
FURNISHING OF ALL LABOR, MATERIALS, EQUIPMENT, PERMIT, FEES,
INFECTIONS, TEST, INSURANCE, ETC. REQUIRED FOR THE COMPLETION
OF THE AIR CONDITIONING SYSTEM SHOWN ON THE DRAWINGS AND/OR
LISTED BELOW.
2 CONTRACTOR SHALL VISIT THE SITE TO 15ECOME FAMILIAR WITH ALL
EXISTING CONDITIONS AND SCOPE OF WORK. CONTRACTOR SHALL
SUBMIT ANY DE5CREPANCIE5 TO ARCHITECT -ENGINEER FIFTEEN (15)
DAYS PRIOR TO BIDS. THE NATURE TH15 PROJECT INVOLVES THE
REMODELING OF EXISTING FACILITIES.
3 INTERRUPTION OF EXISTING FACILITIES AND / OR SERVICES SHALL
KEPT TO A MONIMUM AND THE CONTRACTOR SHALL FURNISH ALL
MATERIALS REQUIRED VHENEVER TEMPORARY CONNECTIONS ARE
NECESSARY TO MAINTAIN CONTINUITY OF SERVICES. COORDINATE ALL
INTERRUPTIONS OF 5ERVICE5 WITH THE OWNER'S REPRESENTATIVE.
4 VENTILATION DUCTWORK SHALL BE GALVANIZED STEEL WITH GAUGES,
DUCT CONSTUTION5, BRACING AND SUSPENSION IN ACCORDANCE WITH
THE RECOMMENDATIONS SET FORTH IN THE LATEST EDITION OF THE
ASHRAE GUIDE AND SMACNA STANDARDS. DUCT SIZES SHOWN ARE
"AIR,5IDE:" DIMENSION. VERIFY EXACT LOCATION OF DUCT WITH
RESPECT TO STRUCTURE BEFORE FABRICATION.
5 FLEXIBLE DUCT SHALL BE 5ELF-6UPPORTING ALUMINUM CON5TRUTION
WITH 1' THICK BLANKET TYPE INSULATON WITH EXTERIOR VAPOR
BARRIER PROVIDE SPIN COLLAR WITH DAMPER AND EXTRACTOR
WHERE FLEXIBLE DUCT 15 CONNECTED TO RECTANGULAR DUCTWORK
ro AIR CONDITIONING SUPPLY AND RETURN, DUCTWORK SHALL BE 1-1/2"
R-ro FIBERGLASS UL 181 LISTED. CLASS I' AIR DUCTWORK SHALL BE
FABRICATED IN ACCORDANCE WITH S.M.A.CN.A. STANDARDS.
i ALL WORK SHALL BE COORDINATED WITH OTHER TRADES TO AVOID
INTERFERENCE WITH THE PROGRESS OF CONSTRUTION AND ITS STRICT
COMPLIANCE WITH ALL APPLICABLE CODES AND STANDARDS.
6 VERIFY ALL DIMENSIONS WITH STRUCTURE PRIOR TO ANY FABRICATION
OR INSTALLATION.
S SUBMIT SHOP DRAWING OF ALL MATERIALS AND EQUIPMENTFOR
APPROVAL PRIOR TO FABRICATION.
10 OBTAIN FULL INFORMATION REGARDING PECULIARITIES AND LIMITATIONS
OF SPACE AVAILBLE FOR INSTALLATION OF THE EQUIPMENT AND
MATERIALS UNDER CONTRACT.PROVIDE READY ACCESSIBILITY
TO DAMPERS, VALVES AND OTHER APPARATUS, INCLUDING ANY
PART OF SYSTEM REQUIRED TO BE REACHED FOR MAINTENANCE
AND OPERATIONS.
11 VIBRATION ISOLATION: ALL EQUIPMENT AS PER MANUFACTURER
RECOMMENDATIONS TO ELIMINATE ANY EQUIPMENT NOISE FROM
BEING HEARD.
12 CUT ALL OPENINGS AND CHASES REQUIRED TO ACCOMMODATE
THE WORK UNDER TH15 DIVISION AND REPAIR ALL FLOORS, ETC.
DAMAGED BY SUCH CUTTINGS- ALL WORK DONE UNDER THIS
HEADING MUST CONFORM IN EVERY RESPECT TO FINISH AND
QUALITY MATERIALS AND WORKMANSHIP SPECIFIED UNDER
APPROPRIATE SECTIONS FOR THE BUILDING.
13 GUARANTEES:
A ALL COMPRESSOR MOTORS ON NEW EQUIPMENT FURNISHED UNDER
THIS CONTRACT SHALL HAVE A 5 YEARS PRODUCT GUARANTEE FROM
DATE OF START-UF-
13 CONTRACTOR SHALL GUARANTEE ALL MATERIALS AND WORKMANSHIP
FREE FROM DEFECTS FOR A PERIOD OF NOT LESS THAN 1 YEAR FROM
DATE OF ACCEPTANCE.
14 TESTING:
A ALL REFRIGERANT HIGH SIDE PIPING TO 300 PSIG LOW SIDE TO 150
PSIG AFTER TESTING EVACUATE SYSTEM TO 28" MERCURY GAUGE
PRESSURE WITH VACUUM FUMF.HOLD FOR 25 HOURS WITH PUMP OFF
BREAK VACCUM WITH REFRIGI=RANT.
B BALANCE AIR SYSTEM TO DELIVER QUANTITIES AND EACH OUTLET
WITHIN 5 PERCENT USING A.A.B.C. PROCEDURES AND TESTS SUBMIT AIR
BALANCE TEST RESULTS FOR APPROVAL PRIOR TO FINAL INSPECTION.
15 REFRIGERATION SUCTION PIPING SHALL BE INSULATED WITH 3/4"
INCOAFELX. ARMAFELX INSULATION MAY ONLY BE USED IN NON -PLENUM
AREAS. FINISH WHERE EXPOSED WITH 2 COATS OF WHITE LATEX
PAIN ALL AS PER MANUFACTURER'S INSTRUCTION,
Iro ALL REFRIGERANT PIPING SHALL BE TYPE "K" HARD COPPER, TOGETHER
WITH WROUGHT COOPER SOLDER FITTINGS JOINTS SHALL BE MADE WITH
SILVER SOLDER OR "SILF05" ALL CONDENSATE DRAIN PIPING TO BE
SCHEDULE 40 TYPE II HIGH IMPACT PVC WITH SLIP JOINT FITTING OF
THE SAME MATERIALS WITH AN APPROVED SOLVENT INSTALLED IN A
MANNER RECOMMENDED BY THE FITTING MANUFACTURER
1� DUCT MOUNTED SMOKE DETECTORS SHALL BE EDWARDS G5 MODEL No
62648 IONIZATION DETECTOR OR APPROVED EQUAL. DETECTOR TO BE
INSTALLED PER UL268A DETECTORS SHALL COMPLY WILL ALL
REQUIREMENTS LISTED ON N.F.P.A. 90A AND TIED TO FIRE ALARM SYSTEM.
VENTILATION FAN SCHEDULE
UNIT DESIGNATION
TEF-1
AREA SERVED
TOILETS
LOCATION
CEILING
FAN TYPE
CEILING
TOTAL AIR CFM
SO
FAN WHEEL TYPE
CENT.
DRIVE TYPE
DIRECT
FAN TIP SPEED,RPM MAX
-
FAN SPEED,RPM
-
TOTAL STATIC PRESSURE,IN. OF H2O
0.10
z
FAN MOTOR HP NON OVERLOAD
1.1 AMP
i�
FAN MOTOR STARTER TYPE
-
STARTER FURNISHED BY
-
ELECTRICAL SERVICE AVAILABLE
120-1-60
DESIGN MANUFACTURER
NUTONE
MODEL NUMBER
LS 80L
SERVICE SWITCH
-
SMOKE DETECTORS
-
FIRE DAMPER
-
CONSTRUCTION
STEEL
w
MULTIBLADE BACKDRAFT DAMPER
YES
Fif0
BIRDSCREEN
YES
C
CONTROL TYPE
-
AUTOMATIC SHUTTER
-
Q
FACTORY FABRICATED CURB
-
SO N ES
0.8
N OTES:
1. INTERLOCK TEF-1 WITH LIGHTS.
2, ACCEPTABLE MANUFACTURERS ARE COOK, GREENHECK OR PENN.
PROVIDE 1/8" STAINLESS STL-
CABLES AROUND UNIT (4) TYP.
A/C COMPRESSOR
(1) 1/4 x 2 ANCHOR BOLT
OR "HILTI SHOT IN EACH
CORNER (4) TOTAL
SEAL OPENING AROUND REFRIG.
LINES W/ FOAM OR EQUAL.
---------------�� :� REFRIG. LINES a EXT.
IN 4 PVG SLEEVE. ----------------
A/C COMPRESSOR DETAIL 3/4ri
NOTE: A/C COND. UNIT E ANCHORAGE SHALL BE CAPABLE OF
SUSTAINING 14ro MPH WIND LOAD AS PER FBC 161SI,
S/A DUCT S/A DUCT
ATTIC SPACE CEILING
FLEXIBLE CONNECTION
FULL SIZE
ELECTRICAL HEATER S/A PLENUM
REFRIGERANT SUCTION FILTER FRAME W/ FILTER
AND LIQUID LINES
NEOPRENE PADSriSiZ�`i
.T4N�L BOLT
FRAUNIT TEEL / F L6611CCFD 11C11T}'V.�1 R1;�1'1a D
THROUGH VIBRATION ISOLATION SOR 5LA 111 OR OL
4" GONG. SLAB ----- ----� E y
2i
A.H.U. MOUNTING DETAIL N.T.S.
NOTE: 1. ALL FLEX AND RIGID DUCT TO BE A MIN. OF R-6 VALUE
2. INSULATE DRAIN PAN W/ viz" THICH RBER31-ASS BLANKET WITW VAPOR BARRIER OR
3. SHEET FOAMED PLASTIC INSULATION W/ APPROVED FIRE RATING ON OUTSIDE SURFACE ONLY.
GOOSENECK
BIRD SCREEN
BARREL TILE
ROOF
INTEGRAL CAP AND
BASE FLASHING
WOOD SHEATHING
ON WOOD TRUSSES
TYP. GOOSENECK DETAIL nis.
NOTE: PROVIDE BACKDRAFT DAMPER FOR EXHAUST FANS
1-IV,4C DESIGN REG2UIRE5:
YES
No
Duct Smoke Detector
X
Fire Dam er(s)
X
Smoke Dam sr(p)
X
Fire Rated Enclosure
X
Fire Rated fR/Gelling Assembly
X
Fire 5topping
X
Smoke Control
X
EXIST. A/C -
EQUIPMENT SCHEDULE
OUTDOOR UNIT
- "RHEEM" RAPC-024JA
INDOOR UNIT -
"RHEEM" RCQC-3617
TOTAL CAPACITY
- 24,800 (BTU/H)
NET SENSIBLE
- 18,100 (BTU/H)
NET LATENT -
6,700 (BTU/H)
SEER RATING -
14.40
AHU HEATER -
5 kW (17,065 BTU)
INDOOR CFM -
600
I
MECHANICAL PLAN
= EX15TING RE5IDENCE
UG•V U••VG ♦•• yW•y
VU•• • Y U
• U * y
• W Y •
U • U V • • V •
W�c+v • Gyrr• • y•• • YYYv
MOTE: PROVIDE 1" UNDERCUT ,D00fR , 6
ALL HA51TA5LE RDOM •�".
i
6761 Southwest 68th Terrace
Miami, Florida 3 3 1 4 3
(305) 7 4 0 — 5 1 8 5
W
4
z
z
Q
J
L
J
a
U
z
Q
U
W
w
F
2
F—
M
m
0
w
U)
O
w
i
0
tri
Y
Of
w
z
C
.�L{
0
W
�
•E
�E
C
u.
L
U
W
v
.�
Cd
LU
o
�
Uj
��
z
E
00
3(0
�
�N
w
U) n1
L
No
o
w
0
a_
DRAWN BY:
MJA
CHECKM F Y:'
Quo.
U
`yW
y
• FMM
ATTACHMENT NO.: W W ° •
• A7 TAC [I;,hENT
DRAWIN§ FIItiE; NO.:,, •
U G to
DATE:
y••y •
W 03/276 �U06
• V V
SCALE:Y
(
rrW••r
• y
Y .
V
NOTED �
V y .• r
•
� _'777—_w
SHEET ;NUMBER:
Y W V
U
M1
OF
12