08-985-021#NEAT 1
NOT W
SUPPL'
P E T P
diby�
ELECTRIC WAT
HUNG FROM JC
NIGH AS POSSI
DRAIN V
SAFET'
1 1/2* MII
DEPTH
SHUT-OFF GATE
VALVE
COLD WATER
SUPPLY TO NEATER
PROVIDE 2 GAL. THERMAL
EXPANSION TANK
3/4'PET
RELIEF LINE
PROVIDE AIR GAP
FITTING IF TERMINATING
OUTSIDE ROOM.
3/4' PAN �U TERMINATE 11/2' OVER
DRAIN LINE SERVICE SINK FLOOD RIM
LEVEL OR EXTEND TO THE
EXTERIOR OF THE BUILDING
AND TERMINATE POINTING
DOWN 6' ABOVE FINISHED
GRADE.
NO ADDITIONAL HEAT TRAPS REQUIRED WHEN WATER HEATER HAS INTEGRAL HEAT TRAPS.
TYPICAL WATER HEATER DETAIL
N.T.S.
COVER SECURED
WITH SCREWS
THREADED C.O. PLUG
FIN. GRADE
4 X 6' DIA. CONCRETE
PAD FLUSH W/FIN. GRADE SLIP JOINT
EXTERIOR TYPE
TYPICAL CLEANOUT DETAIL
N.T.S.
F
System No. C-AJ-1156
F Rating -- 3 Hr
T Rating — 0 Hr
L Rating At Ambient -- Less Than 1 CFM/sq ft
L Rating At 400 F -- 4 CFM/sq ft
AM 11 InrAM C /N^1 I An
��A
FLOOR
1. Floor or Wall Assembly -- Min 4-1/2 in. thick reinforced lightweight or normal weight (100 to 150 pc) concrete. Wall may also be constructed of
any UL Classified Concrete Blocks*. Max diam of opening is 27 in.
See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers.
2. Steel Pipe -- Nom 21 in. diam (or smaller) 0.056 in. thick (or heavier) steel pipe. One pipe to be installed either concentrically or eccentrically
within the firestop system. The annular space shall be min 0 in. (point contact) to max 3 in. Pipe to be rigidly supported on both sides of floor or
wall assembly.
3. Firestop System -- The firestop system shall consist of the following:
A. Steel Wire Mesh -- (Not Shown) -- Where needed to aid in system installation in concrete block wall construction, No. 8 steel wire mesh or
min 0.034 in. thick (20 MSG) galv sheet steel may be formed, centered and installed within the through opening such that it is recessed a min
of 1/8 in. from each surface of the wall.
B. Packing Material -- Min 2 in. thickness of min 4.0 pcf mineral wool bait insulation firmly packed into opening as a permanent form. Packing
material to be recessed from top surface of floor or from both surfaces of wall as required to accommodate the required thickness of fill
material.
C. Fill, Void or Cavity Material* -- Sealant - Min 3/4 in. thickness of fill material applied within the annulus, flush with top surface of floor or with
both surfaces of wall. At the point contact location between pipe and concrete, a min 1/2 in. diam bead of caulk shall be applied at the
concrete/pipe interface on the top surface of floor and on both surfaces of wall.
HILT] CONSTRUCTION CHEMICALS, DIV OF HILTI INC - FS-ONE Sealant
*Bearing the UL Classification Mark
1/2' MIN.
FLUSH VALVE
LEFT OR RIGHT
AS APPLICABLE
(CONTR'S OPTION)
FIXTURE WALL
HUNG OR FLOOR
MTD. AS APPLICABLE
DRAIN
FINISH FLOOR
NON-FERROUS ZOOM
SLOPE DOWN TO OUTLET
a 1/87FT WJ NO TRAP OR
INTERMEDIATE LOW POINTS. Z ALTERNATE CONN. (CONTIZS. OPTION)
SYSTEM DIAGRAM
ALL EXPOSED COMPONENTS CHROME PLATED AND / OR STAINLESS STEEL (SLOAN F-72-AI)
FLUSH VALVE TRAP PRIMER DETAIL (F.V.P.,
N.T.S.
FACE OF WALL
WALL
STAINLESS STEEL COVER
SCREWED TO THREADED
C.O. PLUG.
System No. W-L-1054
F Ratings -1 and 2 Hr (See Items 1 and 3)
T Rating - 0 Hr
L Rating At Ambient - Less Than 1 CFM/Sq Ft
L Rating At 400 F - 4 CFM/Sq Ft
SECTION A -A
1. Wall Assembly -- The 1 or 2 hr fire -rated gypsum wallboard/stud wall assembly shall be constructed of
the materials and in the manner specified in the individual U300 or U400 Series Wall and Partition Designs
in the UL Fire Resistance Directory.
2. Through -Penetrants -- One metallic pipe, conduit or tubing to be installed either concentrically or
eccentrically within the firestop system. The annular space shall be min 0 in. to max 2-1/4 in. Pipe may
be installed with continuous point contact. Pipe, conduit or tubing may be installed at an angle not greater
than 45 degrees from perpendicular. Pipe, conduit or tubing to be rigidly supported on both sides of wall
assembly. The following types and sizes of metallic pipes, conduits or tubing may be used:
A. Steel Pipe -- Nom 30 in diam (or smaller) Schedule 10 (or heavier) steel pipe.
B. Iron Pipe - Nom 30 in. diam (or smaller) cast or ductile iron pipe.
C. Conduit - Nom 4 in diam (or smaller) steel electrical metallic tubing or 6 in. diam steel conduit.
D. Copper Tubing - Nom 6 in. diam (or smaller) Type L (or heavier) copper tubing.
E. Copper Pipe - Nom 6 in. diam (or smaller) regular (or heavier) copper pipe.
3. Fill, Void or Cavity Material* -- Sealant - Min 5/8 in. thickness of fill material applied within the
annulus, flush with both surfaces of wall. At the point or continuous contact locations between pipe and
wall, a min 1/2 in. diam bead of fill material shall be applied at the pipe wall interface on both surfaces
of wall.
HILTI CONSTRUCTION CHEMICALS, DIVOF
HILTI INC -- FS-One Sealant
*Bearing the UL Classification Mark
PLUMBING FIXTURE
COLD WATER TO FIXTURE
PIMER VALVE JOSAM tt88250-10
OR APPROVED EQUAL
W/ VACUUM BREAKER.
NOTE: ALL EXPOSED PLUMBING
ITEMS, SHALL BE CHROME PLATED
FLOOR DRAIN
PARTITION
OR CHASE
C.W. SUPPLY
TO PLUMBING
FIXTURE
FIXTURE VALVE
ESCUTCHEON
PLATES (SEAL
PARTITION
OPENINGS)
FINISH
FLOOR
PENETRATION
—pN.
SLEEVE E SEAL
AS REQUIRED
1/2' MIN. ALTERNATE
BY LOCATION
CONN'S. (CONTRACTORS
(REFER TO
OPTION) SLOPE DR TO
DETAIL)
TRAP PRIMER
N.T.S.
PERFORATED VENT CAP
12' MIN ABOVE TOP
OF CD PAN
OUTLET o 1/8' FT. W/
NO TRAP OR INTERMEDIATE
LOW POINTS.
NOTE
USED WHERE NO SUITABLE
WATER CLOSET, ELECTRIC
WATER COOLER, OR DRINKING
FOUNTAIN IS WITHIN 30 FEET.
VALVE DETAIL (T.P.V.)
C.O. PLUG
CONNECTION
A.H.U.
UNION
�- AUXILIARY DRAIN PAN
SLOPE 1/8'/ FT. TEE I I Q
UNIT TYPE
A
B
DRAW TNRU
2' PLUS X
X
BLOW TI-RU
I' MIN.
2X
WHERE 'X' = STATIC PRESSURE IN PAN.
NOTES:
A. SLOPE DRAIN LINE TO CONDENSATE RECEPTOR (MIN. 1/8' PER FOOT)
B. DRAIN LINE SHALL BE COPPER TYPE 'L' AND INSULATED
C. TSP = FAN TOTAL STATIC PRESSURE
D. PROVIDE CONDENSATE OVERFLOW SAFETY SWITCH TO TURN OFF
THE UNIT IF DRAIN PAN APPROACHES OVERFLOW.
A/C CONDENSATE P-TRAP DETAIL
N.T.S.
® Reproduced by HILTI, Inc. Courtesy of ��.SS I FiFo
Underwriters Laboratories, Inc.
FIRESTOP SYSTEMS December 4, 2002 C e L us
W med Waste Lim
Kftp Ouftt As
+S`UAW4 As Pofttft 1i h At
Leatat 114" Slops Per F*ot
WCO
Big Dipped iS Unit
-Grei= 0440;9eii Conll;*+os
GREASE TRAP SIZING CALCULATION
FIXTURE
# FIXTURES
FIXTURE VALUE
(GPM)
TOTAL FIXTURE
(GPM)
AVERAGING MULTIPLIER
FLOW RATING
(GPM)
3 COMPARTMENT SINK
1
25
25
0.25
6.25
• CALCULATION BASED ON BIG DIPPER 'SIZING BIG DIPPER SYSTEMS IN FOOD SERVICE OPERATIONS' PHAMPLET.
SINGLE FIXTURE BIG DIPPER EQUIPMENT
MODEL
GPM RATING
W-150-IS
15
:1 �I0I4>;10Q;t 4
;ONCRETE INSERT TNRU 8' PIPE SIZE
J.L./F.M. APPROVED. GRINNE-LL FIG.
!81/285 OR APPROVED EQUAL
THREAD ROAD
IPE RING
ICK X 12' LONG SLEEVE
PRENE FOAM (RUBATEX
MRMFLEX)
RING I' GREATER THAN
O.D.
IL, vrtiUGE X 12' LONG GALVANIZED
STEEL PIPE SHIELD
;ONCRETE ANCHOR SELF DRILLING
J.L. LISTED TNRU 4' PIPE SIZE
-ROAD COUPLING, U.L./F.M. G12INNELL
136 OR APPROVED EQUAL
ALL THREAD ROAD
PE RING
BEAM C TYPE CLAMP U.L./F.M.
ROVED TNRU 6' PIPE SIZE.
NELL FIG. 86 OR APPROVED EQUAL
THREAD ROD
RING G12INNEL FIG. 69
:.M. APPROVED (TYP)
Revisions:
A
0
0
0
I—
r
z
h
r
Q
N
LL
c
c
Jo L
Q
<z
V)
M�<
Lij
o m
z
QQ
Q
_J
Q
U_
z
ow�
�
O
U)
�
M
W
I
Q
N_
O -+J ;' 2
M
O N
d �m
U 0C
�vM
Q�00 EX
N
82
4--j a e
;�
W .%
d Cn a
U
d }
z
NNW
U t IN
n � J
z
O
U g
U�
�z
Q
LLJ
n
DRAWN: JB
CHECKED: ES
DATE: 02 -18-08
SCALE: AS NOTED
;EAR... .
v,
G) .
oIIINES 0 A�NT�NA P' .E
jLICEPSE"M, §jm8a,
a
F
Sheet No.
P7.00
® Reproduced by HILTI, Inc. Courtesy of
Underwriters Laboratories, Inc.
FIRESTOP SYSTEMS November24,199s eL us
PIPE HANGER DETAILS
N.T.S.
JOB # 21033