08-985-017UPPER ATTACHMENT PER SMACNA FLEXIBLE DUCT- 8'-0" MAX. 2'-0" MIN. LENGTH —� MAXIMUM D/8 OFFSET ALLOWED IN LAST D INCHES TO DEVICE WHERE D IS THE INTERNAL FLEX DIAMETER NECK SIZE TO MATCH FLEX DUCT SIZE INDICATED MAX. SAG 1/2" PER FOOT BETWEEN SUPPORT POINTS 45- TAKEOFF OR ROUND BELLMOUTH COLLAR MOUNT IN SIDE OF DUCT ADJUSTABLE CLAMP SADDLE 22 GUAGE GALVINIZED STEEL STRAP HANGER AS PER SMACNA FIG. 3-10 (SEE NOTE n5) ADJUSTABLE CLAMP DUCT SEALER INSULATE TOP PANEL OF DIFFUSER OR GRILLE CEILING (T-BAR SHOWN. AIR DISTRIBUTION DEVICE LAYIN SHOWN. GYP. BOARD SIMILAR) SURFACE MOUNT SIMILAR NOTE I. FLEXIBLE DUCTS SHALL BE ONE PIECE AND SHALL NOT BE SPLICED TOGETPER . 2. EXTEND FLEXIBLE DUCT INSULATION TO DUCT/DIFFUSER PANEL INSULATION AND SEAL WITH MASTIC. 3. FLEXIBLE AIR DUCT SHALL NOT EXCEED 8 FT. WHEN EXTENDED. ELBOW RADIUS SIZED FOR NO LESS THAN R / D = 1.0. 4. 24 INCH ORANGE SURVEY TAPE SHALL BE PROVIDED ON ALL DUCT QUADRANT LOCKING LEVERS DIRECTLY ABOVE THE ACCESS PANEL. 5. MINIMUM 1 1/2' WIDE 22 GALVANIZED STRAP HANGER WITH HEMMED EDGES. (FBMC 2004 603.5.6.6) FLEXIBLE DUCT TAKEOFF DETAIL SHEET METAL RUNNER TOP ANf SECURED TO DUCT WITH SHEET SWEET METAL SINGLE THICKNESS QUARTER ROUND TURNING VANES DUCT TURNING VANE DETAIL NTS 3 WAY MODULATING CONTROL VALVE FLOW MEASURING DEVICE WATER RETURN �T^ GATE VALVES WATER SUPPLY PRESSURE GAGE SINGLE VANE SCHEDULE 'R' SP A. SMALL 2' IV 24 LARGE 4' 3 22 TYPICAL FABRICATED SHEET METAL ELBOW SHEET METAL SINGLE THICKNESS TURNING VANES WITH FLANGED FASTENERS TOP AND BOTTOM SHEET METAL RUNNER FASTENED DUCT WITH SHEET METAL SCREW; — DUCT SEALER AT 45- TAKEOFF OR ROUND BELLMOUTH COLLAR CONNECTION TO MAIN SLIPPY AIR DUCT VOLUME DAMPER W/ LOCKING QUADRANT E 2" STANDOFF FULLY HINGED E GASKETED ACCESSDOOR FOR DAMPERS IN NON -ACCESSIBLE CEILINGS PLUG 3PAGE COCK ,--MANUAL AIR VENT (3/8' LINE TO DRAIN PAN) --UNIONS -��L DRAIN THERMOMETER FAN COIL PIPING CONNECTION N.T.S. METAL PIPE OR CONDUIT I, 2, 3, OR 4 WOU12 FIRE RATED CONCRETE FLOOR SLAB. NOTES: USE 3M CP-25 S/L (a) SELF -LEVELING CAULK ON HORIZONTAL SURFACES WHEN FILLING GAPS FROM ABOVE THE PENETRATION. USE 3M CP-25 N/S (*) NO SAG CAULK ON VERTICAL SURFACES AND ON HORIZONTAL SURFACES WHEN FILLING GAPS FROM BELOW. INSULATION (IF REQUIRED BY SPECIFICATION FILL GAP COMPLETELY AROUND PIPE WITH 3M CP-25 S/L W CAULK (SEE NOTES 3-5) "-- DAMPING MATERIAL (FIBERGLASS INSULATION, BACKB2 ROD OR MINERAL WOOL) ENOUGH TO SUPPORT WEIGHT OF 3M CP-25 S/L (■) CAULK. 11 SECTION VIEW (SLAB) I, 2, 3, OR 4 HOUR RATED CONCRETE BLOCK WALL FOR SOLID CONCRETE WALL (SEE NOTE I) NOTES: DAMPING PIPE I. FOR SOLID CONCRETE WALLS. CENTER 3M CP-25 N/S () CAULK MATERIAL OR CONDUIT WITHIN WALL WITH DAMPING MATERIAL ON ONE SIDE. 2. RECOMMENDATIONS BASED ON PRODUCT PERFORMANCE PER ASTM E-814 (UL-1479) FIRE TEST AND UL INSULATION (IF REQUIRED CLASSIFICATION FIRE STOP SYSTEM 49. BY SPECIFICATION 3M CP-25 (*) N/S CAULK 3. WET INSTALLED DEPTH OF 3M CP-25 (*) CAULKS DEPENDS ON BOTH SIDES OF WALL TYPE AND SIZE OF PIPE: AND DESIRED RATING. (SEE NOTE) WET DEPTH PIPE SIZE FIRE RATING 1/2" (13MM) MAX. 8• (203MM) 1-2 HRS. I' (25MM) MAX. 8° (203MM) 3-4 HRS. 4. UP TO 40% SHRINKAGE OF 3M CP-25 (■) N/S OR S/L CAULK IS ACCEPTABLE AFTER INITIAL WET DEPTH INSTALLATION. SECTION VIEW (WALL) 5 MAXIMUM ANNULAR SPACE TO BE FILLED IS 2 1/2' (64MM) UL APPROVED PIPING SAFING ASSEMBLIES EQUAL TO UL SYSTEM u49 FOR INSULATED PIPE AND SYSTEM u91 FOR INSULATED PIPE PIPE PENETRATION FIRESTOP DETAIL N.T.S. () (OR APPROVED EQUIVALENT) UNLESS FOOT OF TRAP IS PLACED UNDER A BOTTOM REINFORCEMENT TYPICAL: 1/4' S.S. 7-WIRE 250 KSI STRAND PURRICANE TIE -DOWN WITH TURNBUCKLE. 3/8' S.S. BOLT WITH WASHER AND NUTS- 1/4' STAINLESS STEEL WIRES SECURED TO — STEEL ANGLES VIA 3/8' S.S. EYE BOLTS AND NUTS (DO NOT OBSTRUCT UNIT ACCESS) PROVIDE 2 PER UNIT U IISTRUT SUPPORT 2' X2' X 3/16' NOT DIP GALV. ANGLE WELDED SCREW; SCRCVVJ MH I W= OMITTED IF HANGER LOOPS STRAP HANGERS CU- FREEZER E COOLER PAD N TES I. INSTALLATION MUST MEET MINIMUM OF 146 MPH WIND LOADING, MINIMUM REQUIREMENTS ARE HEREBY INDICATED, HOWEVER BASED ON ACTUAL EQUIPMENT INSTALLED EPA ( EFFECTIVE PROJECTED AREA) ADDITIONAL SECURING SHALL BE PROVIDED. 2. CORROSION PROTECTION. BUILDINGS LOCATED WITHIN 3,000 FT. OF THE OCEAN SHOULD USE NON-FERROUS METAL, STAINLESS STEEL OR STEEL WITH MINIMUM G-90 HOT -DIP GALVANIZED COATING FOR EQUIPMENT STANDS AND ANCHORS AND STAINLESS STEEL SCREWS. CONDENSING UNIT MOUNTING DETAIL N.T.S. CONCRETE 12' MIN. ROOFTOP EQUIPMENT WEIGHT REQUIREMENTS WIDTH OF EQUIPMENT HEIGHT OF LEGS UP TO 24' 14' 24' TO 36' 18' 36' TO 48' 24' 48' TO 60' 30' 60' AND WIDER 48' WALL 30'4' 0 1/4'X4'X34' HOT DIP GALV. STEEL PLATE 5/16' HOLE FOR 1/4' S.S STEEL BOLT W/ NUTS E WASHERS. 1/2' THREADED GALV. STEEL ROADS HANGER TO STRUCT. NUT E WASHER lVL-\JI-KLJ NIL- rHV OL.I FLEX. CONN. UNIT AND CHANNEL PLENUM R/AIR DUCT SUPPLY AIR III \ 16 DUCT VID NOTE: FILTER SMOKE DETECTORS 12EGUIERED IN SUPPLY SECUNDARY DRAIN PAN AIR SYSTEM WITH DESIGN CAPACITY (SEE NOTE) GREATER THAN 2000 CFM (FMC 2004, 606.21) AIR CONDITIONING UNIT MOUNTING DETAIL. N.T.S. NOTE: EACH FCU MUST BE PROVIDED WITH AUXILIARY SECONDARY DRAIN PAN. AS AN ALTERNATIVE TO SEPARATE DRAIN LINE, AN APPROVED WATER LEVEL DETECTOR OR FLOAT SWITCH DEVICE SHALL BE USED TO CONTROL OVERFLOW BY AUTOMATICALLY SHUTTING DOWN THE EQUIPMENT OR APPLIANCE TWAT PRODUCES THE CONDENSATE. AUXILIARY DRAIN PANS SHALL WAVE A MINIMUM DEPTH OF 1.5 IN., SHALL NOT BE LESS THAN 3 IN. LARGER THAN THE UNIT OR COIL DIMENSIONS IN WIDTH AND LENGTT, AND SHALL BE CONSTRUCTED OF AN APPROVED C012120SION-12ESISTANT MATERIAL. METALIC PANS SHALL HAVE A MINIMUM THICKNESS OF NOT LESS THAN 0.0276 IN. GALVANIZED SHEET METAL. (FMC 2004, 307.2.3) 2' PERFORATED VENT CAP 12' MIN ABOVE TOP OF CD PAN C.O. PLUG CONNECTION A.W.U. TEE UNION ELBOW I I TSP + 2' 3' AUXILIARY DRAIN PAN NOTES: A. SLOPE DRAIN LINE TO CONDENSATE RECEPTOR (MIN. 1/8' PER FOOT) B. DRAIN LINE SHALL BE COPPER TYPE 'L' AND INSULATED C. TSP - FAN TOTAL STATIC PRESSURE D. PROVIDE CONDENSATE OVERFLOW SAFETY SWITCH TO TURN OFF THE UNIT IF DRAIN PAN APPROACHES OVERFLOW. A/C CONDENSATE P-TRAP DETAIL N.T.S. 10" X 4" SHEET METAL EXHAUST DUCT TYPICAL CEILING CABINET EXHAUST FAN WITH BACKD12AFT DAMPER, LOW NOISE LEVEL AND NO VIBRATION. FRONT FACE GRILLE WITH FASTENING SCREENS EXHAUST FAN HANGING BRACKET (ADJUSTABLE) CEILING MOUNTED CABINET EXHAUST FAN DETAIL N.T.S. Revisions: 0 0 A ' z M Q o to Ny U_ o o to _j V X Q Q z a _ F— 0 V l (%� ton LLJ O M l_1__ V) z QQ Q J a' �Q U_ �0�� z��W� MO W (n I to to n 3 0 N M o " Q N_ O O N E U 0 v M Ol .— Q)co c $ N d z cn' a �Q z UoNNtj N J 3' z O g un _j U Q Q �-- o= DRAWN: JB CHECKED: ES DATE: 02- IS- 05 SCALE: A5 NOTED ME NI ICSTQaSAAr4A';PE. tICEN, tt i607tn • a '- w . ISheetNo. M7.00 I JOB # 21033 I