08-985-012AIR DISTRIBUTION LEGEND
DUCT: FIRST FIGURE IS SIDE
24XI2
NEW THERMOSTAT
O
SHOWN
® z
NEW CEILING DIFUSER.
POINT OF CONNECTION
NEW
SUPPLY RETURN GRILLE
BETWEEN AND EXISTING
WORK
L - - - - - - - -1
ALL ELBOW MUST BE PROVIDED
WITH TURNING VANES WHETHER
EQUIPMENT OR DUCTS
OR SHOWN ON DWGS. (SEE SPECS:EXISTING
l
TO REMAIN
i-------- i
171/7/%��ll�
TYP. 450 TAP -OFF WITH
EXISTING EQUIPMENT OR DUCT
VOLUME DAMPER
�L VD
VD
TO BE REMOVED-�-
i i
MANUAL VOLUME DAMPER
DIRECTION OF FLOW
TYPE OF DIFFUSER
6 X 6
SIZE OF DIFFUSER
1 5 O
CHILLER WATER SUPPLY £
f/
/���i�f/
AMOUNT OF CFM
RETURN TO BE REMOVED
Ti
EXISTING THERMOSTAT TO
CHILLER WATER SUPPLY E
--- CHWS ---
REMAIN
RETURN TO REMAIN
--- CHWR ---
HOT WATER SUPPLY E
NEW CHILLED WATER
CHWS
CHWR
RETURN TO BE REMOVED
/
SUPPLY E RETURN
--- HWS----
HWS
HOT WATER SUPPLY is
NEW HOT WATER SUPPLY
RETURN TO REMAIN
--- HWR-----
E RETURN
HWR
NOTES
I. 450 TAP -OFFS, SPUTTERS AT EACH TAP -OFF AND TEE, AND ACCESS DOORS SHALL BEE
USED WHERE REQUIRED, WHETHER OR NOT INDICATED IN THE DRAWINGS.
2. IN AREAS WHERE NON -REMOVABLE CIELINGS ARE USED, PROVIDE 45 TAP -OFFS OF THE
FIXED TYPE, WITH WIDTH PROPORTION TO BRANCH CFM.
FAN SCHEDULE
DESIGNATION
EF-1
EF-2
EF-3
MANUFACTURER
CARNES
CARNES
CARNES
MODEL NUMBER
VCDD010C
VCDD010C
VCDD010C
AREA SERVED
WOMENS
RESTROOM
MENS
RESTROOM
JANITOR ROOM
(101A)
C F.M.
90
85
85
E.S P. (IN. OF WATER)
0.25
0.25
0.25
SONES
1.3
1.3
1.3
R P.M.
SP'® CTRL
SPEED CTRL
SPEED CTRL
H.P. (A=AMP W=WATTS)
77W
77W
77W
V OLT - PH - HZ
120 - 1 - 60
120 - 1 - 60
120 - 1 - 60
DRIVE
DIRECT
DIRECT
DIRECT
BACKDRAFT DAMPER
YES
YES
YES
INTERLOCK
LIGHT SWITCH
LIGHT SWITCH
RUN
CONTNUOSLY
REMARKS:
1. ALTERNATE MANUFACTURERS OF EQUAL QUALITY MAY BE SUBMITTED FOR APPROVAL.
2. UNLESS OTHERWISE NOTED ALL FANS SHALL BE EQUIPPED WITH SAFETY DISCONNECT SWITCH.
3. CONTRACTOR SHALL PROV DE CORRESPONDING ALL GALVANIZED STEEL WALL CAP (SEE DRAWING)
AIR DISTRIBUTION SCHEDULE
DESIGNATION
A
B
MANUFACTURER
TITUS
TITUS
MODEL NO. AND 1 OR
TDC-AA
50 F
CATALOG NO.
LAY -IN
LAY -IN
FRAME TYPE
24X24
24X24
FIXED LOUVERS
EGG CRATE
DEVICE TYPE
1/2"X1/2"X1/2"
FUNCTION
SUPPLY
RETURN
PATTERN
SEE DRAWING
SEE DRAWING
OPPOSED BLADE DAMPERS
YES
YES
NOTES:
1. ALTERNATE MANUFACTURERS OF EQUAL QUALITY MAY BE SUBMITTED FOR APPROVAL.
2. ALL AIR DEVICES SHALL BE ALL ALUMINUM CONSTRUCTION AND FULLY GASKETED.
3. UNLESS OTHERWISE NOTED, ALL AIR DEVICES FINISH SHALL BE BAKED OFF-WHITE.
4. SUPPLY, RETURN OR EXHAUST OUTLETS SERVED BY AN INDIVIDUAL DUCT BRANCH
PROVIDED WITH AN ACCESIBLE MANUAL DAMPER SHALL BE SUPPLIED WITH INTEGRAL
O.B.D.
5. FOR SQUARE NECK OUTLETS CONNECTED TO A RIGID DUCT, PROVIDE THE REQUIRED
INSULATED SQUARE TO ROUND TRANSITION.
;UNIT VENTILATOR & FAN COIL UNIT SCHEDULE
!UNIT TYPE
FCU-1, 2,3 (E)ist.)
FCU-4 (NEW)
AREA SERVED
SALES/SEATING
Backroom (101)
TOTAL SUPPLY AREA - CFM
1030
1550
E.S.P. - INCHES OF WATER
0.20
0.25
'MOTOR HORSEPOWER - HP (WATTS)
1/6
3/4
'AVAILABLE ELECT. SERVICE -V/PH
20811 /60
208/1 /60
,GRAND TOTAL HEAT- BTU / HR
31,600
40790
TOTAL SENSIBLE HEAT- BTU / HR
24,200
36166
ENTERING AIR TEMP- DB/WB ff)
80/67
77.5/63.8
LEAVING AIR TEMP - DB/WB ff)
----
56.2 /55.0
WATER FLOW - GPM
5.6
5.58
ENTERING WATER ff)
45
45
1LEAVING WATER (OF)
57
57
lMAX. COIL PRESSURE DROP - FT. H2O
--
5.0 MAX.
MAX COIL VELOCITY - F.P.M.
i
---
558
HEATING CAPACITY - KW
,
HOT WATER
HOT WATER
STEPS OF ELECT. HEAT CAP. - No.
--
--
IWEIGHT- LBS.
----
195
'DIMENSIONS - (L, W, H) IN.
----
44 X40 X18
DESIGN MANUFACTURER
TRANE
TRANE
MODEL NUMBER
FCDB1202
BCHC036B
MAX. FUSE SIZE
----
15.0
WIN. CIRCUIT CAPACITY
----
7.5
NOTES:
1- Component of each U.V. shall be enclosed in a suitable apparatus casing constructed of 16 gage steel panel.
a) Each casing shall be lined thoroughly throughout with not less than 1 inch 3 pound density of fire retardant synthetic rubber -coated glass fiber insulat
b) Each cooling coil shall be provided with a steel drain pan adequately insulated
c) Drain pan shall extend under all uninsulated valves and piping wich are suject to candensation.
d) All steel surface shall be provided with an approvaed corrosion resistant coating.
2- Single source power of voltage.
RECTANGULAR DUCT HANGERS MINIMUM SIZE
MAXIMUM HALF OF
PAR AT 10 FT. SPACING
PAR AT 8 FT. SPACING
PAR AT 5 FT. SPACING
PAR AT 4 FT. SPACING
DUCT PERIMETER
STRAP
WIRE/ROD
STRAP
WRE/ROD
STRAP
WRE/ROD
STRAP
WRE/ROD
P/2 = 30"
1" X 22 ga.
10 ga.
(0.135)
1" X 22 ga.
10 ga.
(0.135)
1" X 22 ga.
12 ga.
(0.106)
1" X 22 ga.
12 ga.
(0.106)
P/2 = 72"
1" X 18 ga.
3/8"
1" X 20 ga.
1/4"
1" X 22 ga.
1/4"
1" X 22 ga.
1/4"
P/2 = 96"
1" X 16 ga.
3/8"
1" X 18 ga.
3/8"
1" X 20 ga.
3/8"
1" X 22 ga
1/4"
P/2 =120"
1 1/2" X 16 ga.
1/2"
1" X 16 ga.
3/8"
1" X 18 ga.
3/8"
1" X 20 ga.
1/4"
P/2 = 168"
1 1/2" X 16 ga
1/2"
1 1/2" X 16 ga
1/2"
1" X 16 ga.
3/8"
1" X 18 ga.
3/8"
P/2 = 192"
NOT GIVEN
1/2"
1 1/2" X 16 ga.
1/2"
1" X 16 ga.
3/8"
1 1/2" X 16 ga.
3/8"
P/2 = 193" UP
SPECIAL ANALYSIS REQUIRED
WHEN STRAPS ARE LAP JOINED USE
SINGLE HANGER MAXIMUM ALLOWABLE LOAD
THESE MINIMUM FASTENERS:
STRAP
WIRE OR ROD (DIA.)
1" X 18,20.22 ga. - TWO #10 OR ONE 1/4" BOLT
1 " X 22 ga. - 260 Ibs.
0.106" - 80 Ibs.
1" X 16 ga. - TWO 1/4" DIA. BOLT
1 " X 20 ga. - 320 Ibs.
0.135" - 120 Ibs.
1 112" X 16 ga. - TWO 3/8" DIA. BOLT
1 " X 18 ga. - 420 Ibs.
0.162" - 160 Ibs.
PLACE FASTENERS N SERES, NOT SIDE BY SIDE
1 " X 16 ga - 700 Ibs.
1/4" - 260 Ibs.
1 1/2"X 16 ga. - 700 Ibs.
3/8" - 680 Ibs.
1/2" -1250 Ibs.
5/8" - 2000 Ibs.
3/4" - 3000 Ibs.
NOTES:
1. DIMENSIONS OTHER THAN GAGES ARE IN INCHES.
2. TABLEALLOWS FOR DUCT WEIGHT, 1 Ib1ft2 INSULATION WEIGHT AND NORMAL REINFORCEMENT AND TRAPEZE WEIGHT,
BUT NO EXTERNAL LOADS.
3. STRAPS ARE GALVANIZED STEEL; OTHER MATERIALS ARE UNCOATED STEEL.
4. ALLOWABLE LOADS FOR P/2 ASSUMETHAT DUCTS ARE 16 GA. MAXIMUM, EXCEPT THAT WHEN MAXIMUM DUCT DIMENSION (W)
IS OVER 60" THAN P/2 MAXIMUM IS 1.25 in.
5. 12, 10, 8 ga. WIRE IS STEEL OF BLACK ANNEALED, BRIGHT BASIC, OR GALVANIZED TYPE.
MINIMUM HANGER SIZES FOR ROUND
DUCTS
DUCT
MAXIMUM
WIRE
ROD
STRAP
DIAMETER
SPACING
DIAMETER
10 DN
12'
ONE 12 ga.
1/4"
1"x 22 ga
250 mm DN
3.7 m
ONE 2.75 mm
6.4 rrm
25.4 X 0.85 mm
11"- 18"
12'
TWO 12 ga. OR ONE 8 ga.
1/4"
1"x 22 ga
460 mm
3.7 m
ONE 4.27 mm.
6 4 rrm
25.4 X 0.85 mm
19"- 24"
12'
TWO 10 ga
1/4"
1"x 22 ga
610 mm
3.7 m
TWO 3.51 mm.
6 4 mm
25.4 X 0.85 mm
25"- 36"
12'
TWO 8 ga.
3/8"
1"x 20 ga
900 mm
3.7 m
TWO 2.7 mm.
9.5 mm
25.4 X 1.00 mm
37" - 50"
12'
TWO 3/8"
TWO 1" X 20 ga.
1270 mm
3.7 m
TWO 9.5 mm
TWO 25.4 X 1.00 mm
51"- 60"
12'
TWO 3/8"
TWO 1" X 18 ga
1520 mm
3.7 m
TWO 9.5 mm
TWO 25.4 X 1.31 mm
61"- 84"
12'
TWO 3/8"
TWO 1" X 16 ga.
2130 mm
3.7 m
TWO 9.5 mm
TWO 25.4 X 1.61 mm
NOTES:
1. STRAPS ARE GALVANIZED STEEL: RODS ARE UNCOATED OR GALVANIZED STEEL; WIRE IS BLACK ANNEALED,
BRIGHT BASIC, OR GALVANIZED STEEL. ALL ARE ALTERNATIVES.
2. TABLE ALLOWS FOR CONVENTIONAL WALL THICKNESS, AND JOINT SYSTEMS PLUS ONE LB/SF INSULATION
WEIGHT. F HEAV ER DUCTS ARE TO BE INSTALLED, ADJUST HANGER SIZES TO BE WITHIN THBR LOAD LMITS.
HANGER SPACING MAY BEADJUSTEDBY SPECIAL ANALYSIS.
RECTANGULAR DUCT REINFORCEMENT
2" W.G. STATIC
POS. OR NEG.
NO
REINFORCEMENT
REQUIRED
RENFORCEMETIT
CODE
FOR DUCT
GAGE
NO.
REINFORCEMENT SPACING OPTIONS
DUCT DIM.
10' 1 8'
6'
1 5'
1 4'
=
2-1/2'
2'
10" dn.
26 ga.
B-26
B-24
NOT
B-26
&26
REQUIRED
11", 12"
24 ga.
B-26
B-26
B-26
B-26
B-26
13", 14"
22 ga.
B-26
B-26
B-26
B-26
B-26
15", 16"
20 ga.
G22
C-24
C-24
G26
C-26
C-26
B-26
B-26
17", 18"
20 ga.
C-22
C-24
G24
C-26
C-26
G26
G26
B-26
19", 20"
18 ga
C-20
G22
G24
G26
C-26
G26
G26
C-26
21", 22"
16 ga.
D-20
D-22
D-24
D-26
G26
G26
G26
G26
23", 24"
16 ga.
E-20
E= 22
D-24
D-26
D-26
G26
C-26
C-26
25", 26"
E-20
F-18
F-18
G-16
NOT
DESIGNED
E 22
E-20
F-20
G-18
H-16
[=1
E-24
E-22
E-22
F-20
G-18
H-18
1-16G
4-16G
D-26
E= 24
E 24
F 22
G-20
H-20
H-18G
118G
J-16H
D-26
D-26
E-26
E-24
F-24
G-22
K20G
K18G
118G
P 18G
J 18H
C-26
G26
G26
27", 28"
D-26
G26
G26
29", 30"
D-26
D-26
C-26
31" - 36"
E 26
D-26
D-26
37" - 42"
E= 24
E-26
E-26
43" - 48"
F-24
F-24
E= 24
49" - 54"
G-24
F-24
F-24
55" - 60"
G-22
G-24
F-24
61"-72"
H-22G
H-22G
H-24
73" - 84"
�20G
4 22G
122G
85" - 96"
1-18H
1.20H
MH
97" - 108"
K-18H
J 18H
1-18H
109" - 120"
K-181
J-18I
HVAC DESIGN REQUIRES:
YES
NO
DUCT SMOKE DETECTOR
X
FIRE DAMPER(S)
X
SMOKE DAMPERS)
X
FIRE RATED ENCLOSURE
X
FIRE RATED ROOF/FLOOR
CEILING ASSEMBLY
X
FIRE STOPPING
X
SMOKE CONTROL
X
HVAC GENERAL NOTES
1. THE CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS AN0 - LOUIPIVIE-11 ► -
NECESSARY FOR THE INSTALLATION OF HVAC SYSTEM IN ACCORDANCEVI'IT-H THtSE
DRAWINGS.
- FLORIDA BUILDING CODE 2004
- ANS/ASHRAE 15-1994 - -
- NFPA PAMPHLETS 90A, 90B-91-2002 ; - -
- SMACNA -1995
ASHRAE-2001
- OSHA-2005
2. THE WORK INCLUDES PROVIDING THE HVAC SYSTEMS, INCLUDING DUCTWORK,
DIFFUSERS AND GRILLES, INSULATION, CONTROLS AND EQUIPMENT NECESSARY
FOR A COMPLETE FUNCTIONING SYSTEM. HVAC SYSTEM INCLUDES BUT IS NOT
LIMITED TO THE FOLLOWING: SUPPLY, RETURN AND EXHAUST DUCTWORK SYSTEMS
WITH GRILLES, DIFFUSERS FILTERS AND DAMPERS.
3. TEMPERATURE CONTROL SYSTEM INCLUDING LOW VOLTAGE WIRING AND CONDUIT,
TRANSDUCERS, ACTUATORS, CONTROLLER.
4. WARRANTY: PROVIDE LABOR AND MATERIALS TO REPAIR OR REPLACE DEFECTIVE
PARTS AND MATERIALS AS REQUIRED FOR ONE YEAR AFTER SUBSTANTIAL
COMPLETION OR OWNER ACCEPTANCE OF THE COMPLETED PROJECT.
5. DRAWINGS FOR HVAC WORK ARE DIAGRAMMATIC, SHOWING THE GENERAL
LOCATION, TYPE, LAYOUT AND EQUIPMENT REQUIRED. THE DRAWINGS SHALL NOT
BE SCALED FOR EXACT MEASUREMENTS. REFER TO MANUFACTURER'S STANDARD
INSTALLATION DRAWINGS FOR EQUIPMENT CONNECTIONS AND INSTALLATION
REQUIREMENTS AS REQUIRED. FURNISH AND INSTALL ALL DUCTWORK,
CONNECTIONS, ACCESSORIES, OFFSETS AND MATERIALS NECESSARY TO
FACILITATE THE SYSTEM FUNCTIONING AS INDICATED BY THE DESIGN AND THE
EQUIPMENT INDICATED.
6. CONTRACTOR SHALL COORDINATE HIS WORK WITH ALL TRADES, ESPECIALLY WITH
THE LOCATION OF STRUCTURAL MEMBERS, PIPING, SPRINKLERS, CONDUITS AND
LIGHTING OUTLETS AND/OR FIXTURES.
7. ALL MATERIAL AND EQUIPMENTS SHALL BE NEW OF U.S. MANUFACTURER AND OF
GOOD QUALITY OF RESPECTIVE KIND AND GRADE, AND MUST BE FURNISHED SO AS
TO PREVENT ANY DELAY IN THE PROGRESS OF THE WORK. ALL WORK
THROUGHOUT SHALL BE PERFORMED IN A WORKMANLIKE MANNER BY SUFFICIENT
NUMBER OF SKILLED PERSONNEL.
8. FLEX DUCT: PROVIDE FACTORY ASSEMBLED CLASS 1 AIR DUCT (UL 181) WITH 1-1/2"
THICK 1 PCF FIBERGLASS INSULATION R-6 AND REINFORCED OUTER PROTECTIVE
COVERNAPOR BARRIER. FLEX DUCT SHALL MEET NFPA 90A WITH FLAME SPREAD
UNDER 25, SMOKE DEVELOPED UNDER 50, AND SHALL BE RATED FOR 2" W.G.
PRESSURE AND 0 TO 250 DEGREES FAHRENHEIT. PROVIDE METAL ADJUSTABLE
CLAMPING DEVICES, SCREW OPERATED. USE TWIST -LOCK CONICAL TAP COLLARS AT
CONNECTIONS INTO SHEET METAL DUCTWORK. FLEXIBLE DUCTWORK MAYBE USED
FOR BRANCHES TO DIFFUSERS AS INDICATED ON DRAWINGS. DO NOT EXCEED
EIGHT (8) FEET IN LENGTH FOR ANY FLEX DUCT.
9. BALANCING DAMPERS: FABRICATED OF SAME MATERIAL AS DUCT, TWO METAL
GAUGES HEAVIER THAN DUCT. MOUNT ON 3/8" SQUARE ROD WITH SAW SLOT
POSITION INDICATOR. PIVOT AND BEARING, LOCKING POSITION REGULATOR.
10. ALL EQUIPMENT AND MATERIALS SHALL BE NEW, FREE FROM DEFECTS AND WITH
MANUFACTURER'S WARRANTY.
11. PROVIDE DOUBLE THICKNESS TURNING VANES AT ELBOWS AND EXTRACTOR
DAMPERS AT ALL DUCT BRANCHES AND TAKE -OFFS.
12. ALL EXHAUST DUCTWORK SHALL BE OF GALVANIZED SHEET METAL FABRICATED IN
ACCORDANCE WITH SMACNA STANDARD FOR PRESSURE CLASS ACCORDING TO
EACH SYSTEM.
13. FLEXIBLE CONNECTOR: WHERE REQUIRED PROVIDE U.L. LABELED NEOPRENE
COATED FIBERGLASS FABRIC DUCT CONNECTORS.
14. CONTRACTOR SHALL BE RESPONSIBLE TO TEST & BALANCE THE HVAC SYSTEMS AS
PER ASSOCIATED AIR BALANCE COUNCIL STANDARDS.
15. CONDENSATE LINES SHALL BE INSULATED WITH 1/2 INCH FOAMED PLASTIC.
INSULATION SHALL BE WITH FLAME SPREAD 25, SMOKE SPREAD UNDER 50.
16. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS TO ENGINEER FOR APPROVAL OF ALL
EQUIPMENT, MATERIALS AND LAYOUTS PRIOR TO INSTALLATION.
17. CONTRACTOR SHALL PRINT UP INSTRUCTIONS FOR OWNER'S OPERATION OF
SYSTEMS.
18. THE CONTRACTOR SHALL PAY ALL INSPECTION FEES. ALL COSTS OF PERMITS AND
ALL OTHER COSTS INCIDENTAL TO THE COMPLETION AND TESTING OF THIS WORK
UPON FINAL ACCEPTANCE A CERTIFICATE FROM THE LOCAL INSPECTION AUTHORITY
SHALL BE FURNISHED TO THE OWNER.
19. THE CONTRACTOR SHALL VISIT THE SITE AND FAMILIARIZE HIMSELF WITH THE
LOCATION OF EXISTING EQUIPMENT, DUCTWORK, PIPING, CONDUITS, ETC., AND/OR
ANY CONDITION THAT MAY AFFECT HIS WORK.
20. ALL AIR CONDITIONING DUCTWORK SHALL BE CODE GAGE GALVANIZED SHEET
METAL INSULATED WITH 2 INCH THICK AND 1.0 PCF GLASS FIBER FLEXIBLE BLANKET
INSULATION WITH ALUMINUM FOIL REINFORCED WITH GLASS FIBER FASING (FSKL)
JOHN-MANVILLE MICROLITE (R-6 INSTALLED) OR APPROVED EQUIVALENT, DUCT
SIZES SHOWN ARE NET FREE AREA. PROVIDE DOUBLE THICKNESS TURNING VANES
AND EXTRACTORS AT ALL ELBOWS AND TAKE -OFFS.
21. ALL CONCEALED SUPPLY AIR DUCTS SHALL BE EXTERNALLY INSULATED WITH DUCT
WRAP AS INDICATED IN SPECIFICATIONS. RIGID INSULATION SHALL BE PROVIDED IN
EXPOSED LOCATIONS SUCH AS MECHANICAL ROOMS.
22. RETURN DUCTS LOCATED ABOVE UNCONDITIONED SPACES SHALL BE INSULATED
THE SAME AS THE SUPPLY AIR DUCTS.
23. EXHAUST AIR DUCTWORK SHALL BE UNINSULATED. OUTSIDE AIR DUCTWORK SHALL
BE INSULATED SLOPED BACK TOWARDS INTAKE LOUVER AT 1/8 INCH PER FOOT.
24. DUCT FINISHES AND SEALERS SHALL HAVE A SMOKE DEVELOPED RATING OF LESS
THAN 50 AND A FLAME SPREAD OF 25 OR LESS.
25. CHILLED WATER PIPING SHALL BE SCHEDULE 40 BLACK STEEL PIPE WITH 150 POUND
MALLEABLE IRON FITTINGS WITH SCREWED OR VITAULIC COUPLINGS TO MATCH
EXISTING, AND SHALL BE PROPERLY SUPPORTED THROUGHOUT. ALL RUNS MUST BE
SUPPORTED AT EVERY CHANGE IN DIRECTION AND A MINIMUM OF EVERY 6FT. (1"
SIZE), 7FT. (1 W SIZE), 9FT. (1 W SIZE), 1OFT. (2" & 2 W SIZES) AND 12FT. (SIZES 3" AND
LARGER).
26. ALL NEW CHILLED WATER PIPING SYSTEM SHALL BE INSULATED WITH 1-1/2" THICK
"FOAMGLASS" INSULATION INSTALLED IN STRICT ACCORDANCE WITH THE
MANUFACTURERS RECOMMENDATIONS. PROVIDE REMOVABLE INSULATION COVERS
TO ALL VALVES, FLOW MEASURING DEVICES, STRAINERS, AND ANY OTHER FITTINGS
THAT MAY REQUIRE PERIODIC ACCESS IN THE FUTURE.
27. ALL RE -HEAT PIPE SHALL BE COPPER PRESSURE TYPE "L" CONFORMING TO ATMB-88.
INSULATION THICKNESS FOR RE -HEAT PIPE SHALL BE 2" CELLULAR GLASS.
i
Revisions:
0
.0
I-
z
^'
M
r7
Q
o to
N
LL
� o
(�Ov
v
2 li
Q
QZ
a
M -
V J
O
V)
LLJ
m
z
QQ
Q
:2 J
n-
I=-Q
U
0
z
0
O �W�
MO
W
NI
M
3 0
N M
Q
C14 ~
N_
O
-4-J
n
M
G N
a
U
M
0t0
°�25
4
N
02 1
< o
Q
fN d
IV
Q z
UCrNNLj
o L"N
J
z
O
g
Cn
LLJ
J
LLJ
C) _
z �
LLJ UU
LLJ 8 U
Q
V)
O ��- _
m O
� z
Q
LLJ
z
W
0
DRAWN:
JB
CHECKED:
ES
DATE:
02 - IS-05
SCALE:
AS NOTED
SEAL. r
! vMEINI L C
�TO,SAMTANA .P.E
DQEN31r a 6'07$8' -�
Sheet No.
M0.00
I JOB # 21033 1