Loading...
08-985(2)-017UPPER ATTACHMENT PER SMACNA --- - -- -- FLEXIBLE DUCT- 8'-0'* MAX. 2"-0" MIN. LENGTH MAXIMUM D/8 OFFSET ALLOWED IN LAST D INCHES TO DEVICE WHERE D IS THE INTERNAL FLEX DIAMETER MAX. SAG 1/2" PER FOOT BETWEEN SUPPORT POINTS 45- TAKEOFF OR ROUND BELLMOUTH COLLAR MOUNT IN SIDE OF DUCT ADJUSTABLE CLAMP \ � SADDLE 22 GUAGE GALVINIZED STEEL NECK SIZE TO STRAP HANGER AS PER MATCH FLEX SMACNA FIG. 3-10 (SEE NOTE x5) DUCT SIZE INDICATED ADJUSTABLE CLAMP DUCT SEALER INSULATE TOP PANEL OF DIFFUSER OR GRILLE AIR DISTRIBUTION DEVICE CEILING (T-BAR SHOWN. LAYIN SHOWN. GYP. BOARD SIMILAR) SURFACE MOUNT SIMILAR NOTES I. FLEXIBLE DUCTS SHALL BE ONE PIECE AND SHALL NOT BE SPLICED TOGETHER. 2. EXTEND FLEXIBLE DUCT INSULATION TO DUCT/DIFFUSER PANEL INSULATION AND SEAL WITH MASTIC. 3. FLEXIBLE AIR DUCT SHALL NOT EXCEED 8 FT. WHEN EXTENDED, ELBOW RADIUS SIZED FOR NO LESS THAN R / D * 1.0. 4. 24 INCH ORANGE SURVEY TAPE SHALL BE PROVIDED ON ALL DUCT QUADRANT LOCKING LEVERS DIRECTLY ABOVE THE ACCESS PANEL. 5. MINIMUM 1 1/2" WIDE 22 GALVANIZED STRAP HANGER WITH HEMMED EDGES. (FBMC 2004 603.5.6.6) FLEXIBLE DUCT TAKEOFF DETAIL SHEET METAL RUNNER TOP AN[ - SECURED TO DUCT WITH SHEET SHEET METAL SINGLE THICKNESS QUARTER ROUND TURNING VANES DUCT TURNING VANE DETAIL NTS 3 WAY MODULATING CONTROL VALVE FLOW MEASURING DEVICE WATER RETURN GATE VALVES WATER SUPPLY 2--i- PRESSURE GAGE SINGLE VANE SCHEDULE "R" SP 3A. SMALL 2" IV 24 LARGE 4" 3' ° 22 TYPICAL FABRICATED SHEET METAL ELBOW SHEET METAL SINGLE THICKNESS TURNING VANES WITH FLANGED FASTENERS TOP AND BOTTOM SWEET METAL RUNNER FASTENED DUCT WITH SWEET METAL SCREW: P. PLUG GAGE COCK MANUAL AIR VENT (3/8" LINE TO DRAIN PAN) COIL �--UNIONS L�""-DPAIN TPERMOMETEP METAL PIPE OR CONDUIT I, 2, 3, OR 4 HOUR FIRE - RATED CONCRETE FLOOR SLAB. INSULATION (IF REQUIRED BY SPECIFICATION FILL GAP COMPLETELY AROUND PIPE WITH 3M CP-25 S/L (*) CAULK (SEE NOTES 3-5) - DUCT SEALER AT 45- TAKEOFF OR ROUND BELLMOUTH COLLAR NOTES: CONNECTION TO MAIN USE 3M CP-25 S/L t*) SELF -LEVELING CAULK DAMPING MATERIAL (FIBERGLASS SLIPPY AIR DUCT ON RZONTAL SURFACES WHEN FILLING INSULATION, BACKER ROD OR MINERAL GAPSS FROM ABOVE THE PENETRATION. WOOL) ENOUGH TO SUPPORT WEIGHT OF USE 3M CP-25 N/S (*) NO SAG CAULK 3M CP-25 S/L O CAULK. 7 ON VERTICAL SURFACES AND ON HORIZONTAL — SURFACES WHEN FILLING GAPS FROM BELOW.cj SECTION VIEW (SLAB) 1, 2, 3, OR 4 HOUR RATED CONCRETE BLOCK WALL VOLUME DAMPER W/ LOCKING FOR SOLID CONCRETE WALL QUADRANT E 2" STANDOFF (SEE NOTE 1) NOTES: DAMPING PIPE I. FOR SOLID CONCRETE WALLS. CENTER 3M CP-25 N/S W CAULK FULLY HINGED E GASKETED MATERIAL OR CONDUIT WITHIN WALL WITH DAMPING MATERIAL ON ONE SIDE. ACCESSDOOR FOR DAMPERS 2. RECOMMENDATION BASED ON PRODUCT PERFORMANCE IN NON -ACCESSIBLE CEILINGS PER ASTM E-814 (UL-1479) FIRE TEST AND UL CLASSIFICATION FIRE STOP SYSTEM 49. INSULATION (IF REQUIRED7' BY SPECIFICATION 3. WET INSTALLED DEPTH OF 3M CP-25 (*) CAULKS DEPENDS ON Cp-25 (+) S CAULK N/ N/ TYPE AND SIZE OF PIPE: AND DESIRED RATING. BOTH SIDES WALL WET DEPTH PIPE SIZE FIRE RATING (SEE NOTE) I/2" (13MM) MAX. 8' (203MM) 1-2 HRS. El I" (25MM) MAX. 8' (203MM) 3-4 HRS, 4, UP TO 40% SHRINKAGE OF 3M CP-25 (w) N/S OR S/L CAULK IS ACCEPTABLE AFTER INITIAL WET DEPTH INSTALLATION. SECTION VIEW (WALL) 5 MAXIMUM ANNULAR SPACE TO BE FILLED IS 2 1/2" (64MM). FAN COIL PIPING CONNECTION N.T.S. TYPICAL: 1/4" S.S. 7-WIRE 250 K STRAND HURRICANE TIE DOWN WITH TURNBUCKLE. 3/8" S.S. BOLT WITH WASHER AND NUTS - 1/4" STAINLESS STEEL WIRES SECURED TO - STEEL ANGLES VIA 3/8" S.S. EYE BOLTS AND NUTS (DO NOT OBSTRUCT UNIT ACCESS) PROVIDE 2 PER UNIT UNISTRUT SUPPORT 2" X2" X 3/16"— HOT DIP GALV. ANGLE WELDED UL APPROVED PIPING SAFING ASSEMBLIES EQUAL TO UL SYSTEM *49 FOR INSULATED PIPE AND SYSTEM *91 FOR INSULATED PIPE PIPE PENETRATION FIRESTOP DETAIL N.T.S. () (OR APPROVED EQUIVALENT) SCREW: SCK't m) MAT tsC OMITTED IF HANGER LOOPS STRAP HANGERS CU- FREEZER Z COOLER �•r NOTE: I. INSTALLATION MUST MEET MINIMUM OF 146 MPH WIND LOADING, MINIMUM REQUIREMENTS ARE HEREBY INDICATED, HOWEVER BASED ON ACTUAL EQUIPMENT INSTALLED EPA ( EFFECTIVE PROJECTED AREA) ADDITIONAL SECURING SHALL BE PROVIDED. 2. CORROSION PROTECTION. BUILDINGS LOCATED WITHIN 3,000 FT. OF THE OCEAN SHOULD USE NON-FERROUS METAL, STAINLESS STEEL OR STEEL WITH MINIMUM G-90 HOT -DIP GALVANIZED COATING FOR EQUIPMENT STANDS AND ANCHORS AND STAINLESS STEEL SCREWS, COE UNLESS FOOT OF TRAP IS PLACED UNDER A BOTTOM REINFORCEMENT CONDENSING UNIT MOUNTING DETAIL N.T.S. —WALL CONCRETE 12" MIN. 1►i�l�l�� ROOFTOP EQUIPMENT HEIGHT REQUIREMENTS WIDTH OF EQUIPMENT HEIGHT OF LEGS UP TO 24" 14" 24" TO 36" 18" 36' TO 48" 24" 48" TO 60" 30" 60" AND WIDER 48" 30" --�� 4. 0 1/4"X4"X34" HOT DIP GALV, STEEL PLATE 5/16" HOLE FOR 1/4" S.S STEEL BOLT W/ NUTS E WASHERS. 1/2" THREADED GALV. STEEL ROADS HANGER TO STRUCT. NUT Z WASHER NEOPRENE PAD BET UNIT AND CHANNEL FLEX, CONN. -flPLENUM SUPPLY AIR �\ � � �� n R/AIR DUCT DUCT 11 I 1 G III 11!__ I C 1 11 VD NOTE: FILTER SMOKE DETECTORS REOUIERED IN SUPPLY SECUNDARY DRAIN PAN AIR SYSTEM WITH DESIGN CAPACITY (SEE NOTE) GREATER THAN 2000 CFM (FMC 2004, 606.2.1) AIR CONDITIONING UNIT MOUNTING DETAIL. N.T.S. NOTE' EACH FCU MUST BE PROVIDED WITH AUXILIARY SECONDARY DRAIN PAN, AS AN ALTERNATIVE TO SEPARATE DRAIN LINE, AN APPROVED WATER LEVEL DETECTOR OR FLOAT SWITCH DEVICE SHALL BE USED TO CONTROL OVERFLOW BY AUTOMATICALLY SHUTTING DOWN THE EQUIPMENT OR APPLIANCE THAT PRODUCES THE CONDENSATE. AUXILIARY DRAIN PANS SHALL HAVE A MINIMUM DEPTH OF 1.5 IN., SHALL NOT BE LESS THAN 3 IN. LARGER THAN THE UNIT OR COIL DIMENSIONS IN WIDTH AND LENGHT, AND SHALL BE CONSTRUCTED OF AN APPROVED CORROSION -RESISTANT MATERIAL. METALIC PANS SHALL HAVE A MINIMUM THICKNESS OF NOT LESS THAN 0.0276 IN. GALVANIZED SHEET METAL. (FMC 2004, 307.2.3) 2" 2" PERFORATED VENT CAP 12" MIN ABOVE TOP OF CD PAN C.O. PLUG CONNECTION A.H.U. TEE UNION �- ELBOW T5P + 2" AUXILIARY DRAIN PAN 3" NOTE A. SLOPE DRAIN LINE TO CONDENSATE RECEPTOR (MIN. 1/8" PER FOOT) _ B. DRAIN LINE SHALL BE COPPER TYPE "L" AND INSULATED C. TSP - FAN TOTAL STATIC PRESSURE D. PROVIDE CONDENSATE OVERFLOW SAFETY SWITCH TO TURN OFF THE UNIT IF DRAIN PAN APPROACHES OVERFLOW. A/C CONDENSATE P-TRAP DETAIL N.T.S. 10" X 4' SHEET METAL EXHAUST DUCT STEEL HANGER WIRE TYPICAL CEILING CABINET EXHAUST FAN WITH BACKD12AFT DAMPER, LOW NOISE LEVEL AND NO VIBRATION. FRONT FACE GRILLE WITH FASTENING SCREENS EXHAUST FAN HANGING BRACKET (ADJUSTABLE) CEILING MOUNTED CABINET EXHAUST FAN DETAIL Revisions: M < M C� u- Q Qz --- Q 0J0 is Lj_j OM Ur U) QQ :DD 0 OW'- ���to w m W V I M cD n � 3 0 vi to 04 (00 h 00 m N 0 -� � to 2 04 (Ei U 0 li a M to VJnn ll o � r� o!5- cn e V) 1 �=1 o�� z Uo�n� N ~ �- i o 0 c-) DRAWN: JB CHECKED: ES DATE: 02-18-08 SCALE: A5 NOTED SEA ��E ANI A ERILESTO SANTANA P.E. 1-ICENSE, w "60788 Sheet No. M7.00 JOB # 21033