08-357-014A/C RATING: IOK A/C
120/2461 PHASE 3 WIRE
200 AMP
MOUNT:
FLUSH
PANEL
A
CIRCUIT
LOCATION
BREAKER
POLE `VIRE CONDUIT
1
DISHWASHER
20
1
12
1/2
2
WASHER
20
1
12
1/2
3
DISPOSAL
20
1
12
1/2
4
BATH RECEPT
20
1
12
1/2
5
BATH RECEPT
20
1
12
1/2
6
SMALL APPL
20
1
12
1/2
7
SAIALL APPL
20
1
12
1/2
8
AHU 1
40
2
8
3/4
9
AHU 2
40
1
8
1/2
10
AHU 1
40
2
8
3/4
11
AIIU 2
40
1
8
1/2
12
CU 1
30
2
10
3/4
13
CU 2
30
1
10
1/2
14
CU 1
30
2
10
3/4
15
CU 2
30
1
10
1/2
17
OVEN
40
1
8
1/2
18
DRYER
30
1
10
1/2
19
OVEN
40
1
8
1/2
20
DRYER
30
1
10
1/2
21
WATER HEATER
40
1
8
1/2
22
DRYER
30
1
10
1/2
23
WATER HEATER
40
1
8
1/2
24
LIGHTS
15
1
14
1/2
25
LIGHTS
15
1
14
1/2
26
LIGHTS
15
1
14
1/2
27
LIGHTS
15
1
14
1/2
28
LIGHTS
15
1
14
1/2
29
LIGHTS
15
1
14
1/2
30
LIGHTS
15
1
14
1/2
31
RECEPT
15
1
14
1/2
32
RECEPT
15
1
14
1/2
33
RECEPT
15
1
14
1/2
34
RECEPT
15
1
14
1/2
35
RECEPT
15
1
14
1/2
36
RECEPT
15
1
14
1/2
37
RECEPT
15
1
14
1/2
ELECTRICAL, GENERAL NOTES
A. GENERAL PROVISION:
1. GENERAL: PROVIDE ALL LABOR, MATERIAL AND EQUIPMENT FOR A COMPLETE AND PROPERLY
OPERATING ELECTRICAL SYSTEM.
2. CODES AND STANDARDS: CONFORM TO THE REQUIREMENT OF ALL GOVERNING CODES AND
STANDARDS, INCLUDING NATIONAL ELECTRICAL CODE.
3. VISIT THE SITE OF PROPOSED PROJECT TO BECOME FAMIUAR WITH THE WORK CONDITIONS
AND NATURE OF WORK, PRIOR TO SUBMITTING BIDS. NOTIFY ENGINEER OF DISCREPANCIES
OR OMISSIONS FOR INTERPRETATION OR DECISION AND SUCH DECISION SHALL BE FINAL.
B. BASIC MATERIALS AND METHODS:
CONDUIT — INTERIOR WORK: CONCEALED ELECTRICAL METALLIC TUBING; EXTERIOR BELOW
GRADE: SCHEDULE 40 PVC; EXTERIOR EXPOSED: SCHEDULE 40 RGS.
OUTLET BOXES — 4" x 4" STEEL WITH PLASTER RINGS SIZED IN ACCORDANCE WITH N.E.C.
FOR CONCEALED INTERIOR WIRING, CAST FERROUS OUTLET BOXES WITH INTEGRAL HUBS FOR
EXPOSED AND EXTERIOR DEVICES.
WIRE — COPPER, THHN/THWN DUAL RATED.
WIRING DEVICES — SPECIFICATION GRADE DEVICES AND PLATES WITH IVORY FINISH, EXCEPT
MATCH PANELED WALL WITH DEVICES AND PLATES OF SIMILAR COLOR.
a. RECEPTACLES: 20 AMPS, 120V, 2 POLE, 3 WIRE, GROUNDING TYPE OR ISOLATED GROUND
TYPE AS SHOWN ON DRAWINGS.
b. SWITCHES: 20 AMPS
C. LIGHTING FIXTURES:
1. FURNISH LIGHTING FIXTURES AS REQUIRED BY OWNER AND AS INDICATED ON DRAWINGS.
FURNISH ALL NECESSARY MOUNTING HARDWARE AND LAMPS.
2. ALL RECESSED INCANDESCENT FIXTURES SHALL SATISFY THE REQUIREMENTS OF N.E.C.
410-65(2).
D. PANELS:
1. ALL PANELS SHALL BE U.L. RATED AND OF THE SAME MANUFACTURER. PROVIDE SIZE AND
TYPE AS INDICATED ON DRAWINGS. PANELS SHALL HAVE FULL SIZE NEUTRAL BUS AND 1/2
SIZE GROUND BUS.
E. GROUNDING:
1. PROVIDE CONTINUOUS GROUNDING SYSTEM IN ACCORDANCE WITH N.E.C. SECTION 250, AND
AS INDICATED. PROVIDE GROUND CONDUCTOR IN ALL RACEWAYS.
F. IF, THROUGH ERRORS OR OMISSIONS, THE INTENT OF ARCHITECT/ENGINEER WITH REGARD TO ANY DETAIL
IS NOT CLEAR, OR IS CAPABLE OF MORE THAN ONE INTERPRETATION, SUCH MATTERS WILL BE BROUGHT
TO THE ATTENTION OF THE ARCHITECT/ENGINEER IN WRITING BEFORE THE SUBMISSION OF BIDS, AND
THE ARCHITECT/ENGINEER SHALL MAKE CORRECTION OR EXPLANATION IN WRITING. OTHERWISE, NO
EXTRA CHARGE WILL BE ALLOWED FOR THE WORK OR MATERIAL WHICH THE ARCHITECT/ENGINEER WILL
REQUIRE, PROVIDED Ta,AT IT COMES WITHIN A REASONABLE INTERPRETATION OF THE DRAWINGS AND
SPECIFICATIONS.
G. THE PLANS AND SPECIFICATIONS ARE INTENDED AS A GENERAL DESCRIPTION OF THE WORK TO BE
PERFORMED, ALL ITEMS NOT SPECIFICALLY MENTIONED OR SHOWN, BUT NECESSARY FOR THE
COMPLETION OF THE INSTALLATION, SHALL BE FURNISHED AND INSTALLED BY THIS CONTRACTOR. THIS
CONTRACTOR SHALL THOROUGHLY ACQUAINT HIMSELF WITH THE MECHANICAL, ARCHITECTURAL,
STRUCTURAL AND ELECTRICAL PLANS BEFORE SUBMITTING HIS FINAL BID. NO ADDITIONAL
COMPENSATION WILL BE ALLOWED DUE TO THE CONTRACTOR'S FAILURE TO FAMILIARIZE HIMSELF WITH
THE PLANS.
H. INFORMATION SHOWN ON THE DRAWINGS AS TO THE LOCATION OF EXISTING UTILITIES HAS BEEN
PREPARED FROM THE MOST RELIABLE DATA AVAILABLE TO THE ENGINEER. THIS INFORMATION IS NOT
GUARANTEED, HOWEVER, AND IT SHALL BE THIS CONTRACTOR'S RESPONSIBILITY TO DETERMINE THE
LOCATION, CHARACTER AND DEPTH OF EXISITNG UTILITIES.
CALCULATIONS FOR PANEL
GENERAL LIGHTING (3650 x 3)
10,950
APPLIANCE CIRCUIT
3,000
LAUNDRY CIRCUIT
1,500
DISPOSAL
500
RANGE
12,000
DISHWASHER
1,500
WATER HEATER
5,000
DRYER
51000
TOTAL
39,450 W
20.0 KW AT 100%
20.0 KW
29.4 KW AT 40%
11.7 KW
SUBTOTAL
31.7 KW
HEATING@ 65% 9.7 KW
41.4 KW
PROPOSED ELECTRICAL PLAN
1/4 INCH =1 FOOT
ELECTRICAL LEGEND
NOTES-
1. ELECTRICAL OUTLETS OR BOXES LOCATED ON ❑PPOSITE SIDES OF
RATED WALLS OR PARTITIONS SHALL BE SEPARATED BY A
HORIZONTAL DISTANCE OF NOT LESS THAN 24 INCHES,
O
LIGHTING FIXTURE, CEILING MOUNTED
LIGHTING FIXTURE, WALL MOUNTED
S
SINGLE POLE SWITCH, MOUNTED @ 4B'
AFF., TO CENTER, '3'—DENOTES 3—WAY,
'D'—DENOTES DIMMER,
DUPLEX 15A, 125V, 2P, 3W, GROUNDING
RECEPTACLE, MOUNT @ 18'AFF, TO CENTER,
Per NEC 210.12, Arc Fault Circuit Interrupter Protection All circuits that supply outlets installed in dwelling unit
bedrooms shall be protected by an arc fault circuit
interrupter listed to provide protection to the existing
branch circuit
RISER DIAGRAM
NO SCALE
RELOCATE EXISTING
ELECTRICAL PANEL,
METER AND O
GENERATOR TO
THIS AREA f
METER
O
(A
a
T❑ POWER
COMPANY
TRANSFORMER,
120/240V, 1PH,
3W SERVICE
n
al
0
v
7
3
META
C.W.P.
0
PANEL '
RISER DIAGRAM NOTES
GRADE LINE
1, 3—#3/0 KCM, THWN CU, 1-1/21C,
2, 3—#3/0 KCM, 1—#6 GND, THWN CU, 2'C,
3. 1-#4 GND, THWN Cu, 1/2'C,
4. 3/4'0 x 10' LONG COPPERCLAD GROUND ROD.
5.
6. 200' AMP, 2P, S/N, ENCLOSED CIRCUIT BREAKER,
NEMA 3R ENCLOSURE, AIC=22,000 AMP,
7. NEUTRAL BUS,
B. GROUND BUS,
91 #4 GROUND TO NEUTRAL BUS TIE,
Y OF SOUrH h11AMl
BUILDING Dr_P'r.
ELELTRiCAL SECTION
APPROVED BY: 'yr_u
DATE:
0
ISSUE DATE: 3/16/08
PRO). NO, 080311
SCALE: AS NOTED
DRAWN BY: MW
CHECKED BY: JCGriffin
SHEET NO.;
A 8.0
AMPS AT 240 V/ 1 PHASE 172 AMPS