08-357-013SECURE WITH 1 /4"0 CONDENSING
VINYL COATED STAINLESS UNIT
STEEL CABLE OR EQUAL
STRENGTH STRAPS.
ANCHOR TO SLAB IN
CRISSCROSS PATTERN
ACROSS THE UNIT.
POWDER DRIVEN
STUDS, OR 1/2"0
EXPANSION BOLT. 3"
EMBEDMENT (MIN.) 4
PER UNIT (TYPICAL).
PROVIDE NEOPRENE
WASHERS BETWEEN
THE BOLT & CABINET.
TURN
ISO MODE PAD BUCKLE
(TYP.) (m'•)
SET AT ABOVE
FLOOD LEVEL • , ;� • '.� • p : •
MIN. 2" ABOVE
ADJOINING GRADE.
ALL EXTERIOR MOUNTED EQUIPMENT SHALL BE ANCHORED TO CONCRETE
SLAB WITH MINIMUM OF 4 ANCHOR BOLTS, EACH TO WITHSTAND 500
POUNDS MINIMUM PULL OUT CAPACITY AND MEET ALL OTHER WIND LOAD
REQUIREMENTS OF THE "FLORIDA BUILDING CODE - RESIDENTIAL".
CONDENSING UNIT MOUNTING DETAIL
N.T.S.
GRAC
AC UNIT
CONDENSATE TRAP DETAIL
N.T.S.
PACKAGED SPLIT SYSTEM SCHEDULE
SYSTEM DESIGNATION
AHU-1
AREA SERVED
SEE PLAN
REFRIGERANT TYPE
R-22
REFRIGERANT LINES SIZE (INCH) OD (SUCTION / LIQUID)
7/8 / 3/8
LOCATION
A/C CLOSET
OPERATING WEIGHT, POUNDS (MAXIMUM)
120
PHYSICAL DIMENSIONS D x W x H (INCHES)
23.5 x 24.0 x 44.5
DESIGN MANUFACTURER MODEL NO.
TWE04OE13FB
AIR FLOW (VARIABLE SPEED), CFM
1,280 / 600
OUTSIDE AIR, CFM/ MIN. HTG. CFM
--/ 600
C
TOTAL STATIC PRESSURE IN W.G.
0.5
v
FAN MOTOR HP (NON -OVERLOAD)
1/2 (4.3 F.L.A.)
ELECTRICAL SERVICE -VOLTS /PH/HZ
240/1/60
Qr-1
GRAND TOTAL CAPACITY, BTU/HR DESIGN/ (A.R.I. CONDITION)
32.08/ (34.4)
TOTAL SENSIBLE CAPACITY, BTU/HR DESIGN/ (A.R.I. CONDITION)
26.5 / (26.4)
ENTERING AIR TEMPERATURE, F DB/WB (A.R.I. CONDITION)
80 / 67
ELECTRICAL SERVICE
240/1/60
TOTAL HEATING CAPACITY, KW NOMINAL
4.80
NUMBER OF STEPS
1
AHU'S F.L.A. / MIN. CKT. AMP. / MAX. FUSE AMP.
24.3 / 30 / 30
TYPE
PERMANENT
THICKNESS
1"
QUANTITY AND SIZE
FACTORY SUPPLIED
UNIT DESIGNATION
CU-1
LOCATION
GRADE
NUMBER OF COMPRESSORS
2
CAPACITY REDUCTION
YES
CONDENSER FAN -TYPE /QUANTITY/HP/ No OF SPEED/FLA
PROPELLER/1 / 1/3 / 2 / 2.80
MINIMUM CIRCUIT AAPACITY / MAX FUSE SIZE
18 / 30
Cn
AMBIENT AIR TEMPERATURE F' OB
95
r4
OPERATING WEIGHT, POUND
400
PHYSICAL DIMENSIONS D x W x H (INCHES)
37.25 x 34.25 x 49.87
U
ELECTRICAL SERVICE -VOLTS /PH/HZ
240/1/60
DESIGN MANUFACTURER MODEL NO.
2TTZ9030AI000A
SEER RATING, MINIMUM
19.5
DESIGN MANUFACTURER
TRANS
NOTES
O O O O
O PROVIDE ALL KITS REQUIRED FOR SINGLE O PROVIDE PROGRAMMABLE THERMOSTAT.
POINT AHU ELECTRIC CONNECTION.
4 INSTALL FLOAT SWITCH OR MOISTURE SENSOR
O CIRCUIT BREAKER INTEGRAL WITH AHU. SIZE IN AUX. DRAIN CONNECTION OF AHU, TO SHUT
PER MANUFACTURER'S RECOMMENDATIONS. DOWN EQUIPMENT, UPON WATER DETECTION.
PROPOSED MECHANICAL PLAN
1/ INCH = 1 FOOT
Q
v.
THERMAL
VALVE W,
DX
SUCTION LINE
REFRIGERANT LINES
AIR HANDLING UNIT PITCH
SHALL BE ROUTED TO
ALLOW PIPING TO
MOVE WITHOUT STRAIN
OR STRESS
AIR COOLED
CONSULT MANUFACTURER
FOR PIPE SIZES & ADJUST
COND. UNIT
�.p SUCTION LINE PITCH
FOR FIELD CONDITIONS.
DOUBLE PORT
SIGHT GLASS VALVE
REFRIGERANT
PIPING DIAGRAM
REFRIGERANT PIPING TO
CONDENSING UNIT
MAINTAIN 4' MINIMUM
c� CLEARANCE ALL
AROUND.
R/A PLENUM WITH
NON-COMBUSTIBLE AHU! OVER FLOW
FRAME SUPPORT F CONNECTION
CONDENSATE DRAIN
CONNECTION.
FLOAT SWITCH BY MECHANICAL
CONTRACTOR, INTERLOCKED TO F 1 1/4' CD.
SHUTDOWN UNIT UPON
MOISTURE DETECTION. SEE
MECHANICAL PLANS.
L- 2' BELOW FLOOR
(SEE PLUMBING
PLANS).
AHU INSTALLATION DETAIL
N.T.S.
RVAC NOTES
1. ALL WORK REFLECTED ON THESE DOCUMENTS ARE IN STRICT ACCORDANCE WITH
2004 EDITION OF FLORIDA BUILDING CODE- RESIDENTIAL, INCLUDING 2006 SUPPLEMENTS
AND ALL APPLICABLE NFPA, ASHRAE STANDARDS & LOCAL ORDINANCES.
2. CONTRACTOR SHALL VISIT THE SITE AND BECOME FAMILIAR WITH ALL
CONSTRUCTION CONDITIONS.
3. CONTRACTOR TO PROVIDE ALL LABOR, MATERIALS, PERMITS, FEES,
INSPECTIONS, TESTS AND INSURANCE ETC.
4. ALL SUPPLY AND RETURN AIR DUCTWORK INDICATED ON THESE DOCUMENTS SHALL BE
FIBERGLASS DUCT BOARD OR FLEXIBLE INSULATED DUCT WITH CORROSION RESISTANT
REINFORCING WIRE HELIX WITH R-6 INSULATING VALUE WHERE INSTALLED IN ATTIC SPACE.
ALL OTHERS MAY BE FIBERGLASS DUCT BOARD WITH R-5 INSULATING VALUE.
EXHAUST DUCTWORK SHALL BE GALVANIZED SHEET METAL UNLESS OTHERWISE
INDICATED AND BE CONSTRUCTED AND INSTALLED IN STRICT ACCORDANCE WITH
SMACNA STANDARDS.
5. ALL AIR DISTRIBUTION DEVICES SHALL BE AS SCHEDULED.
8. CONTRACTOR SHALL. VERIFY SPACE CONDITIONS AND DIMENSIONS AND
COORDINATE WORK WITH ALL OTHER TRADES PRIOR TO FABRICATION
AND INSTAL ATION OF DUCTWORK AND ORDERING EQUIPMENT. THIS
SHALL INCLUDE BUT NOT BE LIMITED TO:
A) COORDINATE THE LOCATION OF THE GRILLES, LOUVERS, WALL AND
ROOF OPENINGS SIZES AND LOCATIONS WITH THE ARCHITECTURAL
& STRUCTURAL FEATURES AND ELEMENTS.
B) COORDINATE THE LOCATION OF THE A/C EQUIPMENT AND FANS TO
AVOID INTERFERENCE WITH OTHER TRADES AND THE ARCHITECTURAL AND
STRUCTURAL ELEMENT'S OF THE BUILDING.
7. ALL DUCT SIZES SHOWN ARE CLEAR INSIDE DIMENSIONS.
8. CONTRACTOR SHALL MAKE NECESSARY REPAIRS IN DUCTWORK FOR AN AIR
TIGHT SYSTEM.
9. PROVIDE FIRE DAMPERS AT ALL DUCT PENETRATION OF FIRE RATED
BARRIERS PER LOCAL CODES. CEILING FIRE DAMPERS SHALL BE RADIATION
TYPE, U.L LABEL
10. ALL EXHAUST FAN OUTLETS SHALL MEET ALL SEPARATION REQUIREMENTS
AS SET FORTH IN FLORIDA BUILDING CODE.
11 WHERE DUCTS PASS THROUGH BUILDING STRUCTURE THE OPENING SHALL
BE 1' LARGER IN ALL DIRECTIONS.
12. REFRIGERANT PIPING SHALL BE TYPE 'L' COPPER. INSULATE SUCTION LINE
WITH 3/4' THICK FOAMED PLASTIC INSULATION, 25/50 FLAME SPREAD AND
SMOKE DEVELOPED RATING (MAXIMUM) (R-4).
13. ALL EQUIPMENT AND MATERIALS SHALL BE GUARANTEED FOR PERIOD OF
ONE YEAR FROM DAIS OF ACCEPTANCE. COMPRESSORS SHALL CARRY
5 YEAR FACTORY WARRANTY.
14. ALL OTHER ELEMENTS / COMPONENTS AND PARTS NOT SPECIFICALLY
NOTED HEREIN AND IS REQUIRED AS STANDARD PRACTICE FOR A
COMPLETE WORKING SYSTEM SHALL BE PROVIDED AND INSTALLED AT NO
ADDITIONAL COST TO OWNER.
15. ALL ROOF MOUNTED EQUIPMENT AND ACCESSORIES, ALONG WITH EQUIPMENT
LOCATED AT GRADE, SHALL BE SECURED TO WITHSTAND THE FLORIDA BUILDING
CODE 1619.2 WIND LOAD REQUIREMENTS.
16. ALL WORK SHALL BE PERFORMED IN FIRST CLASS WORKMANLIKE MANNER.
17. INSTALL ALL EQUIPMENT AS PER MANUFACTURER'S RECOMMENDATIONS.
18. BALANCE EACH AIR SYSTEM TO DELIVER QUANTITIES INDICATED. SUBMIT
AIR BALANCE TEST RESULTS, PRIOR TO FINAL ACCEPTANCE BY OWNER.
19. BUILDING ENVELOP INSULATION:
o) ROOF R-30
b WALLS R-4.1
c) PARTITION - NONE
20. INSTALLATION AND TERMINATION OF ALL CONTROL WIRING IS THE RESPONSIBILITY
OF MECHANICAL CONTRACTOR. COORDINATE ALL REQUIRED J-BOXES AND
CONDUITS WITH THE ELECTRICAL CONTRACTOR.
21. CONDENSATE DRAIN PIPING:
SEE PLUMBING PLANS.
PVC SHALL. NOT BE INSTALLED IN RETURN AIR PLENUM.
Project:
O
Q E - O
O �w
o n�
Q � o0
Architect:
. •1 •� f r f � e
LA
M
M
r
u- w Q
u Lu
t�7
N r J°
a � N
�M
uJ Qomc�i�-
Ln
N In 1�0 Q
QMLn2
IN MY PROFESSIONAL JUDGEMENT AND TO THE BEST OF
MY KNOWLEDGE AND BELIEF, THESE PLANS AND THE
SPECIFICATIONS COMPLY WITH THE FLORIDA BUILDING
CODE AND ALL APPLICABLE CODES,
COPYRIGHT02007 James Griffin, Architect
ALL RIGHTS RESERVED. THESE DRAWINGS AND THE
SPECIFICATIONS ARE INSTRUMENTS OF SERVICE AND
SHALL REMAIN THE PROPERTY OF JG . WHETHER THE
PROJECT FOR WHICH THEY WERE PREPARED IS EXECUTED
OR NOT. THEY ARE NOT TO BE USED IN ANY MANNER
ON OTHER PROJECTS OR EXTENSIONS TO THIS PROJECT
EXCEPT BY AGREEMENT IN WRITING AND WITH THE
APPROPRIATE COMPENSATION TO JG. REPRODUCTIONS
OF SPECIFICATIONS WITHOUT THE WRITTEN CONSENT
OF JG IS PROHIBITED.
DRAWING TITLE
PROPOSED
MECHANICAL
PLAN
ISSUE DATE: 3/16/08
PROD. NO. 080311
SCALE: AS NOTED
DRAWN BY: MW
CHECKED BY: JCGriffin
SHEET N0.'
A /.0