07-316R-010HVAC NOTES 1.0 GENERAL 1.1 PROVIDE ( FURNISH AND INSTALL ) ALL NECESSARY MATERIALS AND LABOR FOR A COMPLETELY OPERATIONAL HEATING, VENTILATING AND AIR CONDITIONING (HVAC) SYSTEM AS DEPICTED ON THESE CONTRACT DOCUMENTS. 1.2 INSTALL IN ACCORDANCE WITH THE FLORIDA BUILDING CODE, ASHRAE SMACNA, NFPA AND LOCAL ORDINANCES. 1.3 SCOPE OF WORK : PROVIDE THE FOLLOWING COMPLETE SYSTEMS A. AIR CONDITIONING SUPPLY AND RETURN DUCT SYSTEM. B. EXHAUST SYSTEM FOR TOILET ROOMS. C. EXHAUST SYSTEMS FOR WAREHOUSE. D. AIR CONDITIONING UNITS AND CONTROLS. E. INDEPENDENT TEST AND BALANCE. 1.4 NOT USED 1.5 PAY FOR ALL FEES, INSPECTIONS AND CONNECTION CHARGES REQUIRED 1.6 VERIFY AT JOB SITE ALL SPACE CONDITIONS AVAILABLE FOR THE INSTALLATION OF MATERIALS AND EQUIPMENT PRIOR THE INSTALLATION OF EQUIPMENT AND FABRICATION OF DUCTS AND PIPING SYSTEMS. COORDINATE SPACE REQUIREMENTS FOR SERVICE AND MAINTENANCE AND COORDINATE INTERFERENCE WITH OTHER TRADES. 1.7 NATURE OF DESIGN DRAWINGS; DESIGN DRAWINGS ARE DIAGRAMMATIC AND DO NOT INTEND TO SHOW EVERY FITTING, ELBOW, TRANSITION, ETC. THAT WILL BE NECESSARY FOR A COMPLETE AND OPERATIONAL SYSTEMS REQUIRED BY THESE SPECIFICATIONS. 1.8 COORDINATION DRAWINGS; PREPARE 1/4" SCALE (MIN.) COORDINATION DRAWINGS SHOWING DUCTWORK, PIPING AND ALL MAJOR SYSTEM COMPONENTS FOR A/E APPROVAL BEFORE PROCEEDING WITH THE INSTALLATION. IMPLEMENT ALL INFORMATION FROM 1.6 ABOVE. 1.9 SUBMIT SHOP DRAWINGS FOR A/E APPROVAL BEFORE PROCEEDING WITH THE THE PURCHASE OR INSTALLATION OF EQUIPMENT AND MATERIALS. ALL SHOP DRAWINGS MUST BE SUBMITTED IN A SINGLE BOUND AND INDEXED PACKAGE NO LATER THAN 30 DAYS FROM THE ADJUDICATION OF THE PROJECT. 1.10 GUARANTEE ALL WORK FREE OF DEFECTS IN MATERIALS AND WORKMANSHIP FOR A A PERIOD OF ONE YEAR FROM THE DATE OF PROJECT ACCEPTANCE. 2.0 .MATER�$ 2.1 DUCTWORK 2.1.1 GENERAL. ALL DUCT SIZES SHOWN ARE CLEAR INSIDE DIMENSIONS. 2.1.2 DUCTWORK MATERIALS: A: GENERAL OFFICE AREAS: FIVE POUNDS DENSITY 1.5" THICK GLASS FIBER R-6) DESIGNED, CONSTRUCTED AND INSTALLED IN ACCORDANCE WITH SMACNA'S FIBROUS GLASS DUCT CONSTRUCTION STANDARDS. DUCT JOINTS SHALL BE SEALED AND TAPED. B: TOILET ROOM EXHAUST AND FRESH AIR INTAKES: GALVANIZED SHEET METAL, CONSTRUCTED, AND INSTALLED ACCORDING TO LATEST EDITION OF SMACNA'S. LOW PRESSURE CONSTRUCTION STD. (0.5" W.G.) C: EXPOSED AIR CONDITIONING DUCTWORK SPIRAL GALVANIZED SHEET METAL, CONSTRUCTED, AND INSTALLED ACCORDING TO LATEST EDITION OF SMACNA'S. LOW PRESSURE CONSTRUCTION STD. (0.5" W.G.) 2.1.3 PROVIDE DOUBLE THICKNESS TURNING VANES AT ALL SQUARE ELBOWS. WHERE THE ELBOWS ARE RECTANGULAR INSTALL SINGLE THICKNESS VANES. .1 ALTERNATE A: PROVIDE 3-PIECE ELBOWS IN LIEU OF TURNING VANES FOR GLASS FIBER DUCTS ONLY. .2 ALTERNATE A: PROVIDE FULL RADIOS ELBOWS IN LIEU OF TURNING VANES. 2.1.4 PROVIDE VOLUME EXTRACTORS BEHIND EACH SUPPLY OUTLET AND AT EACH DUCT BRANCH.. 2.2 NOT USED. 2.3 NOT USED. DICKERSON OFFICE CONDO BUILDOUT SUITE 400, FOURTH FLOOR, PLAZA 57 7301 S.W. 57TH COURT CITY OF SOUTH MIAMI SOUTH MIAMI, FLORIDA 33143 2.4 AIR DISTRIBUTION PRODUCTS : 2.4.1 PROVIDE EXTRUDED ALL ALUMINUM AIR DISTRIBUTION PRODUCTS. 2.4.2 PROVIDE SUPPLY AND RETURN GRILLES AND DIFFUSERS AS INDICATED ON THE DRAWINGS AND SCHEDULES. 2.4.3 PROVIDE FINISHES AND TYPES OF MOUNT IN COORDINATION WITH THE CEILING TYPES AS SHOWN ON ARCHITECTURAL DRAWINGS. 2.4.4 PROVIDE OPPOSED BLADE, KEY OPERATED DAMPERS BEHIND ALL AIR SUPPLY OUTLETS. 2.5 PROVIDE A MINIMUM 5 YEAR WARRANTY FOR ALL AIR CONDITIONING COMPRESSORS STARTING FROM THE DATE OF PROJECT ACCEPTANCE. 2.6 CONTROLS: 2.6.1 GENERAL: PROVIDE THE NECESSARY AUTOMATIC CONTROLS FOR PROPER OPERATION OF ALL EQUIPMENT SPECIFIED HEREIN. FURNISH MAGNETIC STARTERS AND INTERLOCK WIRING INDICATED FOR EACH PIECE OF EQUIPMENT. 2.6.2 OFFICE AREA DX EQUIPMENT: PROVIDE AIR CONDITIONING UNITS WITH MATCHING LOW VOLTAGE HEAT/COOL THERMOSTATS WITH ON -OFF AUTO SUB -BASE SWITCH AS FURNISHED BY THE EQUIPMENT MANUFACTURER. 2.7 STARTERS: PROVIDE MAGNETIC STARTER FOR ALL MECHANICAL EQUIPMENT IN THIS SECTION AS DESCRIBED ON THE EQUIPMENT SCHEDULES. ALL STARTERS MUST HAVE HAND -OFF -AUTO POSITION SWITCH ON THE COVER AND RED/GREEN PILOT LIGHTS. PROVIDE THE NECESSARY AUXILIARY OPEN AND CLOSED CONTACTS FOR THE INTENDED OPERATION AND INTERLOCKS. 2.8 NOT USED. 2.9 IDENTIFICATION: 2.9.1 LABEL ALL EQUIPMENT WITH ENGRAVED BLACK PLASTIC PLAQUES 12"x4" HIGH WITH WITH 1.5" LETTERS. USE THE SAME NOMENCLATURE AS IN THESE DOCUMENTS. 2.10 RETURN AIR CEILING PLENUMS: 2.10.1 WHEN CEILING SPACES ARE USED AS "RETURN AIR CEILING PLENUMS" ALL MATERIALS INSIDE THE R/A CEILING PLENUM SHALL HAVE A MAXIMUM FLAME SPREAD INDEX OF 25 AND A MAXIMUM SMOKE DEVELOPED INDEX OF 50 PER NFPA 90A. "NO PVC PIPING IS ALLOWED INSIDE THE R/A PLENUM." 2.10.2 PROVIDE FREE PATH FOR R/A INSIDE CEILING SPACE. SEE ARCHITECTURAL PLAN FOR COORDINATION 3.0 EXECUTION 3.1 INSTALL ALL EQUIPMENT AND MATERIALS IN STRICT ACCORDANCE WITH THE MANUFACTURER'S MANUALS AND RECOMMENDATIONS, PAYING SPECIAL ATTENTION TO REQUIRED CLEARANCES FOR INSTALLATION, OPERATION & SERVICE. FOR INSTALLATION, OPERATION AND SERVICE. 3.2 NOT USED 3.3 THERMOSTAT LOCATION. THERMOSTAT LOCATION IS CRITICAL TO PROPER EQUIPMENT OPERATION. INSTALL THERMOSTAT AT LOCATIONS SHOWN ON PLANS. RELOCATE ONLY WHEN APPROVED BY THE A/E IN WRITING. 3.4 RETURN AIR FOR INDIVIDUAL ROOMS IS BEING PROVIDED AS SHOWN ON PLANS AND IS SIZED COUNTING ON A 1" UNDERCUT FOR ALL DOORS IN ADDITION TO THE REQUIRED RETURN OR TRANSFER SYSTEM. 3.5 EQUIPMENT MUST OPERATE FREE OF OBJECTIONABLE NOISE AND VIBRATION REPAIR AND/OR REPLACE ALL SOURCES OF NOISE AND VIBRATION FOUND TO BE OBJECTIONABLE, TO THE SATISFACTION OF THE A/E. 3.6 BALANCE ALL SYSTEMS TO PROVIDE AIR AND WATER QUANTITIES AND CAPACITIES TO MATCH SPECIFIED FLOWS & CAPACITIES. CALIBRATE FLOWS TO NEW EQUIPMENT PER MANUFACTURER'S REQUIREMENTS. SUBMIT FINAL TEST AND BALANCE REPORT TO A/E FOR ACCEPTANCE. 7TEL: 0. 582a 3eN= DESl;,N- JOB NUMBER A/C SPLIT SYSTEM SCHEDULE DESIGNATION AHU-5 AC -I QUANTITY 2 2 AREA SERVED SUITE SERVER ROOM MANUFACTURER TRANE CARRIER FAN COIL MODEL No. TWE063 401CMCOIS CONDENSING UNIT MODEL No. 2TTR2060 38HDF018 COMBINED RATINGS TOTAL SENSIBLE CAPACITY BTU HR 6I000 - GRAND TOTAL CAPACITY BTU HR 45100 11,400 TOTAL HEATING CAPACITY BTU HR 25,500 - ENERGY EFFICIENCY RATIO SEER (EER) 12.0 13.0 COEFFICIENT OF PERFORMANCE COP - FAN COIL UNIT TYPE VERTICAL IN C I ING TOTAL AIR SUPPLY CFM 20W 450 OUTSIDE AIR SUPPLY CFM 230 45 ENTERING AIR CONDITIONS FDB FWB 80/(Ol 80/61 EVAPORATOR COIL MIN. ROWS MAX. F.P.I. - - EXTERNAL STATIC PRESSURE "H z0 05 0.23 FAN SPEED RPM HIGH SPEED HIGH SPEED FAN MOTOR HP 3/4 120W ELECTRICAL SERVICE AVAILABLE 1 208/1/60 208/1/60 RUNNING LOAD AMPS 3. S 1.3 ELECTRIC RESISTANCE HEATER SIZE KW 1.5 - UNIT WEIGHT 225 L5 4S L5 C O N D E N S I N G U N I T TYPE - AIR COOLED LOCATION ROOF ROOF REFRIGERANT TYPE R-22 R-22 AMBIENT AIR TEMPERATURE FDB 95T_ S5T_ NUMBER OF COMPRESSORS I 1 NUMBER OF REFRIGERANT CIRCUITS I 1 CAPACITY REDUCTION STEPS % 0-100 0-100 ELECTRICAL SERVICE AVAILABLE 208/1/60 208/1/60 RUNNING LOAD AMPS 24.0 10.8 MINIMUM CIRCUIT AMPS 38.0 13.3 MAXIMUM FUSE SIZE AMPS 60.0 20.0 UNIT WEIGHT 212 4S A C C E S S O R I E S REFRIGERANT PIPING LENGHT FT. P-z: 60 SEE PLANS LIQUID LINE TYPE O.D. - AS PER MANUF. SUCTION LINE SIZE O.D. _ RE 4 SPEC. COOL THERMOSTAT HEAT/COOL FILTER SECTION AND FILTER TYPE Ily THgoUjAWAy 1 SMOKE DETECTOR IN SUPPLY - I BRATION ISO LA T O R S FOR FAN COIL UNIT FOR CONDENSING UNIT AUTO MATI C C O T R O L S TYPE - - DESCRIPTION - - I ANTONIO FRANYIE PE #11640 MECH VIVIANA FRANYIE PE #49985 ME Certificate of Authorization # 00002906 27 Street, Miami FL 33172 FAX: (305) 594-9279 01-109 CHANDLER AND ASSOCIATES NO. DATE PA AA 0003050 74SON R CE ANDI EK AiA AR NO. 16055 SOUTH hUAANM FLORMA 33143 TEL M 669-73192 FAX 00 6619-733 AIR DISTRIBUTION SCHE-n-I,lLE= -, F SIGNATION E SUPPLY RETURN CONSTRUCTION ALUMINIUM ALUH34:_UMM _ -- CAPACITY C.F.M. SHOUN ON PLAN 1- - SIZE SHOUJrI ON PLAN - TYPE 24' x 24' MODULAR COMMENTS DIRECTIONAL CEILING DIFFUSER FINISH ALL ALUMINIUM ALL ALUMINIUM MOUNTING TYPE T - BAR T - BAR NOISE CRITERIA 30 MAX 30 MAX i MANUFACTURER METALAIRIEi MEtALAIRE MODEL 5500 RH A C C E S S O R I E S OPPOSED BLADE REGIST. 05D - FIRE DAMPER - - CONNECTION SIZE SHM ON fDLMS NOTES 1. FINISHES AND TYPES OF MOUNTS SHALL BE COORDINATED WITH ARCHITECTURAL DRAWINGS. 2. PROVIDE SINGLE THICKNESS TURNING VANES AT ALL 900 RECTANGULAR ELBOWS AND DOUBLE THICKNESS TURNING VANES AT ALL 900 SQUARE ELBOWS, OR 3 PIECE ELBOWS. 3. PROVIDE VOLUME EXTRACTORS BEHIND EACH SUPPLY OUTLET AND AT EACH DUCT BRANCH SUPPLY OUTLETS MODEL - OBDC. DUCT BRANCH TAKE -OFF MODEL - AIRTROL MOD. 102 4. PROVIDE O.B. DAMPER AT ALL SUPPLY OUTLETS. 5. DUCT WORK TYPE SEE A/C NOTES. 6. AIR PATTERN AND DIFFUSOR FACE SHOWN ON PLANS. 7. DIFFUSOR NECK SIZE SHOWN ON PLANS. (6x6, 9x9, 1202, OR 15x15) HVAC DESIGN REQUIRES: YES NO Remarks DUCT SMOKE DETECTOR I/ _ - FIRE DAMPER($) - ✓ - SMOKE DAMPER(S) - I/ - FIRE RATED ENCLOSURE - i/ - FIRE RATED ROOF/FLOOR CEILING ASSEMBLY _ ✓ - FIRE STOPPIWG - I/ - SMOKE CONTROL - ✓ - OUTSIDE AIR CALCULATIONS OFFICES 2858 V x 7 PERS / 1000 m = 20 PERS x 20 CFM / PER5 = 400 cni i O/A --------------------------------------------------- O/A PROVIDED 1 400 s DRAWNG TITLE- KV.A.C. NOTES AND SCFEDULES ;SCALE= i DATE. 01-24-07 100X c:de PROJECT NO 2=4 r DRAWNO NOS 07 M-2 I 2