07-1605-012APPROVED 5TAINLE55
HANGERS ® 12" O.G. —
8" DIA. METAL
DECORATIVE
1/2" ROUND x 1 1/2"
I I STAINLE55 STL.
DUCT HANGER
...................................................................................................................
O BOTT OF FIXTURE
4 DIFFUSER
DIFFUSER
Duct Sectaim - A/A
scale: n.t.5.
24"L UN I STRUT W/
GAPPED EN05
(5TAINLE55 5TLJ
+/— II'—O" (EXIST. CLG)
5/8"L STA I NLE55
TREADED RODS
ROUND MTL. DUCT SPRAY PAINT
COLOR AS SELECTED BY
OWNER +/— ell-III
AIRCRAFT
WIRE
LIGHT FIXTURE HUNG
FROM I NSTRUT
(NOT TYP)
1"1EGa--IAN I CAL SPEG I F I GAT I ONS
UNIT
TONS
DEL N0.
CU/ANU
S.E.E.R.
C.F.M.
��
LRA
NEq7
STRIP SIZE
MAX. CIRC.
AMP.
SfN518LE NEAT
CAPACI7Y(B7U)
TOTAL HEAT
LAPAGTY(87U)
NEW
4.0
CARRIER CU # 24APA598A0030
15.5
100
21.8/ 110.0
IOKW
CA-45
36, 820
481 210
CARRIER ANU o FV413JB006010
OUTSIDE AIR CALCULATION:
TOTAL 50. FT. = 1500
NEAREST USE - 'OFF I OE'
PER TABLE 405.5 F5C.M
OCCUPANTS/ 1000 50. FT. _ -7
TOTAL OCCUPANTS = 1.1
TOTAL GFM/ PER50N REG. = 20
TOTAL OUTSIDE AIR REG. 182 GFM
TOTAL OUTSIDE AIR PROVIDED = 200 GFM
CEILING GRILLE SPECS.
A TITUS V—I (VORTEX DIFFUSER)
\LY MOUNT ® 8'-2" A.F.F. ATTACHED
TO METAL DUCT
B TITUS FTIOx 48"
O WHITE FINISH LINEAR
DIFFUSER
G TITUS 'MB-50' 5ERIE5
O MODU-510-Co WHITE FINISH
4 WAY, SUPPLY DIFFUSER W/
2 SLOTS, 24x24. COORD. INSTALL
OF CENTER TILE W/O.C.
D TITUS WHITE FIN15H 'PXP'
O PERFORATED 50REEN 4 FRAME
ONLY TRANSFER GRILLE, 24x24
OTITUS 'MB-50' MODU-510-G,
WHITE FINISH, 444AY, SUPPLY
DIFFUSER W/ 4 SLOTS, 24x24
COORD. INSTALL OF CENTER
TILE W/ O.G.
NV ADJ. VOL.
DAMPER
Mechanical Plan
scale: 114" = V-011
UC - UNDERCUT DOOR I"
50 GFM
I WAY
160 GFM W/
ADJ. VOLUME
new
DETECTOR
TROUBLE LIGHT
INDICATOR
12x24" PERFORATED
SCREEN 4 FRAME
RETURN GRILLE
NOTES DOLT UNIT
(4) "" STAINLESS
THRU DOLTS TO
EXIST. FRAME —
APPROX. LOCATION
OP NEW GU MOUNTW
ON ROOF
NOTE: CONTRACTOR
SHALL LOCATE EXIST.
MAIN COND. LINE OR
ROOF DRAIN LINES 4
TAP IN NEW COND.
PIPES (TYP)
I" COPPER SECONDARY
EMERGENCY COND.
DRAIN LINE SLOPE 1/4"
PER FT.
1 1/2" COPPER PRIMARY
CONDENSATION LINE
SLOPE 1/4" PER FOOT
20x2O FILTER
(GOORD.
YV/ MANUF)
20x2O RETURN AIR
MAIN (METAL)
NEW CEILING HUNG AHU
UNIT NV DRAIN PAN
(5EE DETAIL)
DUCT SMOKE
DETECTOR
150 GFM 4 WAY
YV/ ADJ. VOL.
DAMPER
AT INLET (TYPJ
9" PlAjOPENIN&
Q YV A0j. DAMPER
ON SIDE
EXIST. MTL. ROOF
STAND. VERIFY IN
FIELD
(2) 16 6ALV. I V21A
MTL. STRAPS BOLTED
TO EXIST. FRAM
W VIA. MTL. DUCT THROUGH
ROOF 200 GFM FRESH AIR
INTAKE YV/ VOLUME DAMPER —
PROVIDE APPROVED SCREENED
GOOSENECK AT ROOF 4
CONSULT W/ BUILDING ROOFER —
COORD. EXACT ROUTE IN —FIELD
ANY GORE DRILLING SHALL
REQUIRE X-RAY OF EXISTING
SLAB
:Rher - 1drd
ArGhItoot mre;
Marla9e,rne;nt
Des T3rt
8450 sw 201 bet
fti, Edda 33189
754.264.4773
AAA
NCAKE5
General We: Any errors, a ndgles,
and omissions In drawings and
speclficaf m shoo be reported to the
arch W for comscibru beloreary part
of the work is started. Unless expressly
douded, no oddhbrlal alowance A
be made in thew*ocl and/or
manufadurer's favor or byvidue al
errors, ambigrifiesandlasomissions
which should have been dsoovered
during the preparation of the bid eshmale
and directed to our ahenlion In a Hmeiy
manner.
DO NOT SCALE DRAWINGS.
We tigM dimensions only. Conhactor
Shall ve*all dh wslons and
conditions. In the event of a conks,
no* the Designer before praceedng
whh the work
i ;
el
.1U
r •••IIOW rQ
legiSht�f011�n� l�lR42844 ,j� �`
5
4
3
2
1 Issued for Permit 12/04/07
ISSUE DATE