Loading...
07-1605-009HN.A.C. heat load design calculations Project: Tenant Improvement Selden and Beattie Insurance Group 7301 SW 57 Court South Miami, FL 33143 Zone: AIC #1 (existing) AIE of Record: Robert J Lara, RA 8450 SW 201 ST, Miami, FL 33189 roof component &YAWA U value Foor Area 1,300.00 sq. It. outside air. 0.17 5.8824 Avg. height of Rooms: 9.50 ft roofing: 0.44 2.2727 Est # of Occut 1000 sq ft: nla plywood: 0.00 0.0000 Perimeter of CMU wall: 29.83 In it concrete: 0.77 1.2987 Gross area of CMU wall: 283.42 sq. it insulation: 19.00 0.0526 Perimeter of stud wall: 119.15 In It drywall: 0.00 0.0000 Gross area of stud wall: 1131.93 sq. it. accoustic: 0.45 2.2222 inside air. 0.61 1.6393 Area of glass: N 0.00 44 btulhr. total: 21A4 0.0466 HE 0.00 60 bhnfir. S 0.00 44 btulhr. CUU wall component: SE 0.00 74 btulhr. R. vali4 ale E 0.00 85 btulhr. outside air. 0.17 5.8824 SW 0.00 74 btulhr. stucco: 0.13 8.0000 W 176.00 85 badhr. block 1.04 0.9615 NW 0.00 60 btulhr. plywood: 0.00 0.0000 H 0.00 158 btulhr. insulation: 3.00 0.3333 176.00 total glass area drywall: 0.45 2.2222 inside air. 0.68 1.4706 Area of glass block 0.00 sq. ft total: 5.47 0.1830 Area of wood doors: 0.00 sq. ft Area of metal doors: 20.00 sq. It, Interior Stud wag component Net area of CMU wall: 107.42 sq. ft outside air. 0.68 1.4706 Net area of stud wall: 1111.93 sq. It. drywall: 0.45 2.2222 Studs: 1.04 0.9615 Room Conditions: 75 deg. F. DB plywood: 0.00 0.0000 50% relative humidity insulation: 11.00 0.0909 Number of Occupants: 13.0 drywall: 0.45 2.2222 Activity: Office inside air. 0.68 1.4706 tow: 14.30 0.0699 Outdoor Conditions: 90 deg F. DB 79 deg F. WB doors: Charge in temp: 15 deg F. R value U value Heat Gain of people: 315 btulhr. sensible wood: 3.13 0.3195 (table 5.21) 425 bbAr. latent steel: Z13 0.4695 Daylight factom 2.71% Heat Gain of Igts: 3.5 btulhr. sensible windows: Heat Gain of equip.: 4.5 btwbr. sensible RR value U value tinted: 0.96 1.0417 Heat Gain x # of Occupants: 4,095.00 btulhr. sensible glass block 1.76 0.5682 5,525.00 bhAr. latent Heat Gain of Glass: 14,960.00 bWlhr, sensible Heat Gain of Building: 21,478.57 btulhr. sensible (including glass) Eauioment Selection: Carrier Heat Gain of Lights: 4,550.00 bW/hr. sensible 24APA598A0030I FV4BN8006010 Heat Gain of equipment 5,850.00 blulhr. sensible Unit Sensible: 36,820 badhr Infiltration: 311.76 btulhr. sensible Unit Latent: 11.390 btulhr Unit Total: 48.210 btulhr Room Sensible Heat 36,285.33 btulhr. sensible r Equip. Total Capacity I oalculafATQ* tow Room Latent Heat-- 5.525.00 btulhr. latent ' • • 1.02 times tg►446 Total Heat Gains= 41,810.33 bWMr ; Sensible heat factor-- 0.867855622 ----- 'J.. CFM= 2,239.84 cfm �•: rr CFM=HXSQ. FT. IR `00 •` _ From Psychrometric chart y i ,tti'• " Robed Lora,4, l (enthalpy) He_ Hb= 24.3 (1' l 4 Grand Total Loads 47,372.51 btulhr TOTAL TONAGE= 3.95 ' •+? •1�2�8bn 08r� ' Use: 4.0 ton unit