07-1605-008I
0 f
Electrical Notes:
I. All electrical work shall comply with the latest editions National Electrical Code, Florida Building
Code and all other applicable codes.
2. Electrical Contractor shall obtain all necessary and required permits and licenses for the work under this
contract.
3. Electrical Contractor shall provide and maintain temporary power and light outlets for use by other trades.
4. Electrical Contractor shall provide all material and labor for the connection of equipment being installed
under this contract by other trades.
S. Electrical Contractor shall visit the site and verify all existing conditions. Notify Architect/Engineer in the
case of a discrepancy.
6. Electrical Contractor shall be responsible for providing roof sleeves and proper flashing for all pipes crossing
any roof and all required pipe wall sleeves inclusive of any required fire stopping through fire rated walls.
1. Gable and wire Indicated on drawing shall be cooper. WC in sizes no. 14,12 And 10 awg; 75'C in sizes no.
6 and larger.
6. Condult Installed under ground shall be pvc schedule 40. Conduit installed exposed to weather shall be IMC
conduit, installed elsewhere shall be EMT.. Flexible conduit used where indicated shall be "seal-tite".
cl. 6enerally outlet locations may be scaled with reasonable accuracy. Outlets shall be flush with finish surface.
Two or more light switches 1n the some wall shall be installed In gang type boxes.
10. Junction boxes shall be.9olvanized steel with screw or hinged covers for Indoor locations and weatherproof
where exposed to weather or as Indicated in plans.
11. Electric Contractor shall perform all necessary work for a complete electrical installation and shall provide
all necessary instruments and special apparatus to conduct any test that shall be required to insure the system
is free of all Improper grounds and short circuits.
12. Although drawings are usually to scale, the drawings are diagrammatic; location of any equipment shall be
verified at the site unless otherwise noted on plans.
15. Electrical Contractor shall verify all wlre and conduit sizes, and loads of equipment prior to proceeding with
work and must make all necessary adjustments as required. Notify the Architect in the case of a discrepancy.
14. Electrical Contractor shall provide and Install all lighting fixtures and lamps as shown on drawings. Provide
10% (min 5 for interior and 3 for exterior) spare lamps of each type to Owner.
15. All electrical receptacles, switch plates and other wiring devices shall be by "Leniton Decora" smooth white color
to match background or approved equal. (stainless steel metal plates for exterior use). Submit sample to
Architect for approval
16. All circuits shall be numbered and identified at the panel.
11. Bond panel to main as per N.E.G. 680.
16. Electrical Contractor shall prior to installatlon of rough electrical wiring, check and verify name plate data
of all electrical equipment to obtain current wire sizes aid over -current protection as per N.E.G. 240-21.
Iq. Upon completion of this work the Electrical Contractor shall test the electrical system and shall guarantee all
work free from defects of workmanship and/or material for a period of one year from date of acceptance, and
shall also provide the Architect/Engineer with as built drawings showing all work Installed.
20. Equipment Intended to break current at fault levels shall have an interrupting rating sufficient for the nominal
circuit voltage and the current that Is available at the line terminals of the equipment.
Equipment Intended to break current at other than fault levels shall have on interrupting rating at nominal
circuit voltage sufficient for the current that must be interrupted. As per N.E.C. 110-d1.
21. The overcurrent protective devices, the total impedance, the component short-circuit withstand ratings, and
other characteristics of the circuit to be protected shall be so selected and coordinated as to permit the circuit
protective devices that are used to clear a fault without the occurrence of extensive damage to the electrical
components of the circuit. This fault shall be assumed to be either between two or more of the circuit
conductors, or between any circuit conductor and the grounding conductor or enclosing metal raceway. As
per NE.G. 110-10.
TYPE: LOAD CENTER
VOLTAGE: 120/208., 3PH.,
MAINS: 150A. M.L.O.
AIC RATING: 10K
(SYS. SERIES RATED.
4W
PANEL I A
(INSTALLED BY CONDO)
ENCLOSURE: FLUSHED
MODIFICATION: GROUND BUS
LOCATION: OFFICE SPACE
FED FROM: METER BANK NORTH ELECT. ROOM
SERVING
WIRE AND
COND SIZE
LOAD
(VA)
POLE
TRIP
CIRC.
No.
PHASE
A B
C
CIRC.
No.
POLE
TRIP
LOAD
(VA)
WIRE
COND
AND
SIZE
SERVING
AHU-530 INDOOR UNIT
#6-1"
107922
60
1
2
2
40
(4080
#8-3/4"
CU-530 OUTDOOR UNIT
ROOFTOP
3
4
RECEPT. OFFICE AREA
12-1 2"
600
1 20
5
+ 6
1
20
1200
12-1
2"
OUTLET SIGN GFI FUTURE
LIGHT OFFICE AREA
12-1
2"
900
1
20
7
8
1
20
1200
12-1
2"
RECEPT. OFFICE AREA
RECEPT. OFFICE AREA
12-1
2"
11200
1
20
9
10
1
20
11200
12-1
2"
RECEPT. OFFICE AREA
RECEPT. OFFICE AREA
12-1
2"
1200
1
20
11
12
1
20
1200
12-1
2
RECEPT. OFFICE AREA
TELCO OUTLET
12-1
2"
1000
1
20
13
14
1
20
1500
12-1
2"
REFRIGERATOR
PRINTER COPIER
12-1
2"
1500
1
20
15
16
1
20
1500
12-1
2
MICROWAVE
SERVER
12-1
2"
1200
1
20
17
18
1
20
1500
12-1
2"
LIGHTING
SPARE
----
1200
2
20
19
20
1
20
1500
12-1
2
LIGHTING
21
22
EMERGENCY EXIT
12-1
2"
600
1
20
23
24
25
26
27
28
29
30
TOTAL= 30,992 VA / 360 x 1.25 D.F.
=
108 AMPS
+ CONTROLLED BY TIME SWITCH.
( ) FIGURES IN PARENTHESIS INDICATES LOAD IS NON —CONCURRENT.
THEREFORE, NOT PART OF TOTAL LOAD.
EXIST. TELCO 50ARD
COORD. W/ SELLSOUTH
t AT4T
EXIST. GROUND
CONDUCTORS -
EXIST. SERViC
CONDUCTORS
EXIST. P W/ PULL C 4ORD. CONTRACTOR
SHALL VERIFY TERMINATION OF PULL
SOX N SUITE 530 t EXTEND TO NEW
TELCO PANEL
ROOF
OFFICE NEW SEMI-ihECESSED
CONTRACTOR SHALL SPACE STRUCTURED WiRING PANEL
INSTALL (2) NEW 1 1/2° IN SUITE 530
SCHED. 40 W/ PULL PNL
CHORDS TO EXiST. EXIST. PANEL 'A' IN
TELCO 50ARD 'A' SUITE 530 - 120/208,
3PH, 4W -150A MLO
EXiST.
MAIN NORTH
ELECTRICAL
ROOM 8
3P-1000A
Electrical Riser
scale: n.t.5.
EXIST. 30 1/0 4 1 • 6 (G)-2"C. —
00ORD. W/ CONDO MANAGEMENT t
VERIFY ROUTE 4 LOCATION OF
METER N FIELD
N. ELEC. ROOF? FIFTH LEVEL
RD. INSTALL OF TER W/ POWER CO—
L L W/ PEWANE T ENGRAVED PLAQUE
STATING "SELDEN 4 MEATTIE INSURANCE" SUITE 530
E IST. 150A MCS
N. ELEC. ROOM FOURTH LEVEL
Ci i Y UF= SOUTH MTAMI
BUILDING DEPT.
ELECTRICAL SECTION
APPROVED BY: �k_
DATE: I a-- k(o - `ti)
,.__Tc-e=� --ldrd
Ar&hite,c,fmre;
M�I4619eMent
D e, sIP9ri
8450 sw 201 street
miami, tbrida 33189
754.264.4773
A I A
NCAKE5
General Note: My errors, ambiguities,
and omissforu h drawings and
spedflcatlorushall be repoded to rice
archried for corrections before any part
of the work i lore. Unlessgxe*
stWated, no addriiond d an will
be made in the controd and/or
manufoclurer's fava or by virlue d
errors, ambigriliesandla on ifts
which should have been dwered
during the preparation of the bid edmafe
and directed to our dtenlion In a timely
manner.
DO NOT XE DRAWINGS.
Ike figured dlmendons any. Contractor
shah verify od dmerWom and
conditions. In the eventot a contid,
notiy the Designer before Mcoeding
whh the work
r-
�...
•
• /_ .,
LA, ma 1 S�p1,",71w no. 266,yyMWy����(]J�/��
s
oL
k, ISSUE DATE
sheet
E .2
of
9