07-1605-005Guide XHEZ Through -Penetration Firestop Systems December 02, IS131 W-L-1049 - A Card System No. W-L-1049 (Formerly Sgstern No. 635) F-Rating - 1 and 2 Hr (See Item 15) T-Rating - 0 Hr L Rating At Ambient - Less Than 1 C llsq ft L Rating At 400 F - Less Than 1 CFM/sq ft A LA Section A -A (Cont'd on W-L-1049 - B Card) Guide XHEZ Through -Penetration Firestop Systems System No. W-L-1156 F Rating - 1, 2 and 3 Hr (See Item 1) T Rating - 0 Hr L Rating At Ambient - Less Than 1 CFM/eq ft L Rating At 400 F - Less Than 1 CFM/sq Pt November 16, 1998 W-L-1156 - A Card System No. W-L-1049 December OZ 1997 F Ratings — 1 and 2 Hr (See Item 1B) T Rating — 0 Hr L Rating At Ambient — Less Than 1 CFM/sq ft L Rating At 400 F — Less Than 1 CFM/sq ft 1. Wall Assembly The 1 or 2 hr fire —rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner described in the Individual U300 or U400 Series Wall or Partition Design in the UL Fire Resistance Directory and shall include the following construction features: A. Studs Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. (51 by 102 mm) lumber spaced 16 in. (406 mm) OC. Steel studs to be min 3-1/2 in. (89 mm) wide and spaced max 24 in. (610 mm) OC. When steel studs are used and the diem of opening exceeds the width of stud cavity, the opening shall be framed on all sides using lengths of steel stud installed between the vertical studs and screw —attached to the steel studs at each end. The framed opening in the wall shall be 4 to 6 in. (102 to 152 mm) wider and 4 to 6 in. (102 to 152 mm) higher than the diem of the penetrating item such that, when the penetrating item is installed in the opening, a 2 to 3 In. (51 to 76 mm) clearance is present between the penetrating item and the framing on all four sides. B. Gypsum Board* 5/8 in. (16 mm) thick, 4 ft (1.22 m) wide with square or tapered edges. The gypsum board type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual U300 or U400 Series Design in the UL Fire Resistance Directory. Max diem of opening is 26 in. (660 mm) for steel stud walls. Max diem of opening is 14-1/2 in. (368 mm) for wood stud walls. The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed. 2. Through Penetrant One metallic pipe, conduit or tubing to be installed either concentrically or eccentrically within the firestop system. Pipe, conduit or tubing may be installed at an angle not greater than 45 degrees from perpendicular. The annular space between pipe, conduit or tubing and periphery of opening shall be min 0 in. (0 mm, point contact) to max 2 in. (51 mm). Pipe. conduit or tubing to be rigidly supported on both sides of wall assembly. The following types and sizes of metallic pipes, conduits or tubing may be used: A. Steel Pipe Nom 24 in. (610 mm) diem (or smaller) Schedule 10 (or heavier) steel pipe. B. Iron Pipe Nom 24 in. (610 mm) diam (or smaller) cast or ductile iron pipe. C. Conduit Nom 4 in. (102 mm) diam (or smaller) steel electrical metallic tubing, nom 6 in. (152 mm) diam (or smaller) steel conduit or nom 1 in. (25 mm) diam (or smaller) flexible steel conduit. D. Copper Tubing Nom 6 in. (152 mm) diam (or smaller) Type L (or heavier) copper tubing. E. Copper Pipe Nom 6 in. (152 mm) diam (or smaller) Regular (or heavier) copper pipe. 3. Fill, Void or Cavity Material* — Sealant Min 5/8 in. (16 mm) thickness of fill material applied within annulus, flush with both surfaces of wall. At the point contact location between through penetrant and gypsum board, a min 3/8 In. (10 mm) diam bead of fill material shall be applied at the gypsum board/through penetrant interface on both surfaces of wall. SPECIFIED TECHNOLOGIES INC — SpecSeal 100, 101, 102 or 105 Sealant *Bearing the UL Classification Mark Subscriber ID: 650692002 Directory: FIRERES Guide XHEZ (W-L-1156 - B Card) Through -Penetration Firestop Systems (Cont'd from W-L-1156 - A Card) System No. W-L-1156 November 16, 1998 F Ratings - 1, 2 and 3 Hr (See Item 1) T Rating - 0 Hr L Rating at Ambient - Less Than 1 CFM/sq ft L Rating at 40OF - Less Than 1 CFM/sq ft 1. Wall Assembly - The 1, 2 or 3 hr fire -rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner described in the individual U300 or U400 Series Wall or Partition Designs in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Wall framing shall consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in.1 lumber spaced 16 in. OC. Steel studs to be min 3-5/8 in. wide and spaced 24 in. OC. B. Gypsum Board* - 1/2 or 5/8 in. thick, 4 ft wide with square or tapered edges. The gypsum wallboard type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual U300 or U400 Series Designs in the UL Fire Resistance Directory. Max diam of opening is 1-1/2 in. The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed. 2. Through Penetrants - One metallic pipe or conduit installed concentrically or eccentrically within the firestop system. The annular space within the firestop system shall be min 1/4 in. to max 1/2 in. Pipe or conduit to be rigidly supported on both sides of wall assembly. The following types and sizes of metallic pipe or conduit may be used: A. Steel Pipe - Nom 3/4 in. diam (or smaller) Schedule 5 (or heavier) steel pipe. B. Conduit - Nom 3/4 in. diam (or smaller) rigid steel conduit, steel electrical metallic tubing (EMT) or flexible steel conduit. 3. Fill, Void or Cavity Materials* - Sealant - Fill material installed to completely fill annular space between pipe or conduit and gypsum wallboard with a min 1/4 in. diam bead of caulk applied to perimeter of pipe or conduit at its egress from both sides of the wall. SPECIFIED TECHNOLOGIES INC - SpecSeal 100, 101, 102 or 105 Sealant *Bearing the UL Classification Marking (Cont'd on W-L-1156 - 5 Card) Guide XHEZ (W-L-8011 - B Card) Through -Penetration Firestop Systems (Cont'd from W-L-8011 - A Card) System No. W-L-8011 November 26, 1996 Guide XHEZ December 22, 1998 F Ratings - 1 & 2 Hr. (See Item 1B) Through -Penetration Firestop Systems W-L-3135 - A Card T Rating - 1/2 Hr. System No. W-L-3135 1. Wall Assembly - The 1 or 2 hr fire -rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner described in the F Ratings - 1 and 2 Hr (See Item 1) individual U300 or U400 Series Wall or Partition Design in the UL Fire Resistance Directory and shall include the following construction features: T Rating - 0 Hr A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. lumber spaced 16 in. O.C. with nom 2 by 4 in. lumber end plates and cross braces. Steel studs to be min 3-5/8 in. wide and spaced max 24 in. O.C. B. Gypsum Board* - 5/8 in. thick, 4 ft wide with square or tapered edges. The gypsum wallboard type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual U300 or U400 Series Design in the UL Fire Resistance Directory. Max diam of opening is 3-1/2 in. The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed. 2. Through Penetrant - A max of two pipes or tubing to be installed within the opening. Of the two pipes, or tubing, only one of the pipes or tubing shall have a nom diam greater than 1/2 in. The annular space between pipes or tubing and periphery of opening shall be min 0 in. (point contact) to max 1/2 in. Pipes or tubing to be rigidly supported on both sides of wall assembly. The following types and sizes of metallic pipes or tubing may be used: A. Steel Pipe - Nom 1 in. diam (or smaller) Schedule 10 (or heavier) steel pipe. B. Iron Pipe - Nom 1 in. diam (or smaller) cast or ductile iron pipe. C. Copper Tubing - Nom 1 in. diam (or smaller) Type L (or heavier) copper tubing. D. Copper Pipe - Nom 1 in. diam (or smaller) Regular (or heavier) copper pipe. 3. Tube Insulation - Plastics+ - Nom 3/4 in. thick acrylonitrile butadiene/polyvinyl chloride (AB/PVC) flexible foam furnished in the form of tubing. The tube insulation may be installed on a max of one pipe or tubing. The annular space between penetrating item and periphery of opening shall be min 1/2 into max 3/4 in. The space between pipes or tubing shall be 0 in. (point contact) See Plastics+ (QMFZ2) category in the Recognized Component Directory for names for manufacturers. Any Recognized Component tube insulation material meeting the above specifications and having a UL 94 Flammability Classification of 94-5VA may be used. 4. Cables - One 4 pair No. 18 AWG (or smaller) thermostat cable with polyvinyl chloride (PVC) insulation and jacket materials. Cable to be spaced a min 0 in. (point contact) to max 1/2 in. from the other penetrants. The space between the cable and the periphery of the opening shall be a min 0 in. (point contact) to Section A -A max 1/2 in. Cable to be rigidly supported on both sides of wall assembly. 5. Fill, Void or Cavity Material* - Sealant - Min 5/8 in.thickness of fill material applied within annulus, flush with both surfaces of wall. Additional fill material to be to be forced into intersties within groups of penetrating items to max extent possible and installed such that a min 1/4 in. thick crown is formed around the penetrating items and lapping 1/4 in. beyond the periphery of the opening. (Cont'd on W-L-3135 - B Card) SPECIFIED TECHNOLOGIES INC - SpecSeal 100, 101, 102 or 105 Sealant +Bearing the UL Recognized Component Mark *Bearing the UL Classification Marking Guide XHEZ Through -Penetration Firestop Systems System No. W-L-2093 F-Rating - 1 and 2 Wr (See Item 1) T-Rating - 1 and 1-1/2 Hr (See Item 2) A 2 3 A Details scale: nis. April 30, 1998 W-L-20S3 - A Card Section A -A (Cont'd on W-L-2093 - B Card) Guide XHEZ (W-L-2093 - B Card) Through -Penetration Firestop Systems (Cont'd from W-L-2093 - A Card) System No. W-L-2093 April 30, 1998 F Ratings - 1 & 2 Hr. (See Item 1) T Ratings - 1 and 1-1/2 Hr. (See Item 2) 1. Wall Assembly - The 1 or 2 hr fire -rated gypsum wallboard/stud wall assembly shall be constructed of the materials and in the manner described in the individual U300 or U400 Series Wall or Partition Design in the UL Fire Resistance Directory and shall include the following construction features: A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in. lumber spaced 16 in. O.C. with nom 2 by 4 in. lumber end plates and cross braces. Steel studs to be min 3-5/8 in. wide and spaced max 24 in. O.C. B. Gypsum Board* - 5/8 in. thick, 4 ft wide with square or tapered edges. The gypsum wallboard type, thickness, number of layers, fastener type and sheet orientation shall be as specified in the individual U300 or U400 Series Design in the UL Fire Resistance Directory. Max diam of opening is 3 in. The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed. 2. Through Penetrants - One nonmetallic pipe, conduit or raceway to be centered within the firestop system. A nom annular ,space of 5/16 in. is required within the firestop system. Pipe, conduit or raceway to be rigidly supported on both sides of the floor or wall assembly. The following types and sizes of nonmetallic pipes, conduits or raceway may be used: A. Polyvinyl Chloride (PVC) Pipe - Nom 2 in. diam (or smaller) Schedule 40 cellular or solid core PVC pipe for use in closed '(process or supply) piping systems. B. Rigid Nonmetallic Conduit+ - Nom 2 in. diam (or smaller) Schedule 40 PVC conduit installed in accordance with Article 347 of the National Electrical Code (NFPA No. 70). C. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nom 2 in. diam (or smaller) SDR17 CPVC pipe for use in closed (process or supply) piping systems. D. Optical Fiber Raceway+ - Nom 2 in. diam (or smaller) optical fiber raceway formed from polyvinyl chloride (PVC) or nom 1-1/4 in. diam (or smaller) optical fiber raceway formed from polyvinylidene fluoride (PVDF). Raceway to be installed in accordance with Article No. 770 of the National Electrical Code. Raceway to be rigidly supported on both sides of wall assembly. See Optical Fiber Raceway (QAZM) category in the Electrical Construction Materials Directory for names of manufacturers. E. Electrical Nonmetallic Tubing+ - Nom 2 in. diam (or smaller) PVC tubing installed in accordance with Article 331 of the National Electrical Code (NFPA No. 70). See Electrical Nonmetallic Tubing - (FKHU) category in the Electrical Construction Materials Directory for names of manufacturers. The hourly T Rating of the firestop system is dependent upon the hourly fire rating of the wall and the diam of the through - penetrant as shown below: Wall HrMax Diem of Through Penetrant In.T Rating Hr2111-1/4122121-1/41-1/23. Fill, Void or Cavity Material* - Sealant - Min 5/8 in. thickness of fill material applied within annulus, flush with both surfaces of wall. Additional fill material to be installed such that a min 1/4 In. thick crown is formed around the penetrating item and lapping 1 in. beyond the periphery of the opening. SPECIFIED TECHNOLOGIES INC - SpecSeal 100, 101, 102 or 105 Sealant +Bearing the UL Listing Mark *Bearing the UL Classification Marking POLISHED 4 BROKEN TOP 4 SIDE EDGES 1/2" THK CLEAR GLASS PANELS Ix 8 FIN FiR CAP (CONT) 1 1/2" WIDE CONT. WOOD RAIL EA. SIDE NEW DRYWALL PARTITION W/ 3 5/8", 20 GAUGE MTL. STUD * 16" OTC. W/ 5/8 GYPSUM DRYWALL (50TH SIDES) PROVIDE BRACING AS NECESSARY 3 5/8", 20 GAUGE MOTT. PLATE HILTi POWER ACTUATED PINS W/ WASHERS a 16" O.C. 5�s" 1 13-S�s'1 15/s" Fdruousm Detail scale: nis. ©REGLET OREGLET Ql PARTITION W/ RIB BATTS iNSUL. 1/2" TEMPERED CLEAF SAFETY GLASS CAT II ii'-ON CLG. HCsT. UNDERSIDE OF EXIST'G METAL DECK (OR STRUCTa T.O. GLASS 5'-0" HEIGHT TOP OF PLATE 3 5/5", 20 GAUGE TOP PLATE 4 HORIZ CATT • MiD SPAN NEW 4" DECORATIVE WOOD BASE (TYPJ NEW FLOORING (COORD. W/ OWNER) — — — — — — 0'-0" FiN. FLR 3 WX 20 GAGE DRAG 15RACING AT 32" O.C. -00 ACCOSTICAL DROP TOP. OF Ri;SLET CLG INSTALLED PER MANUF. SPECS 3" CONT SATINLESS BOTT SNAPON TRESHOLD TRIM COVER TAPEEACHSIDE_ +/-O'-0" FIN. FLR. GEILIN& — 3%I'X 20 GAGE HEADER PLATE (2) -1 Y4 X 20 GAGE HEADER 2 "X 4" YELLOW PINE NAILER EDGE 2" CONT. STAINLESS GLASS SUPPORT BRACKET %4" REDOAK PLANKS FINISHED PER OWNERS SPECS AND APPROVED VIS=EEN INSTALLED PER MANUFACTURER SPECS. CiT BUI`� CF1J NG�D pT Vj MI L. BUILDING SECTION APPROVED BY: DATE: n --- - - ----- ----- sft ---- ,.. r er era ArChite,Ctblre; ManLi9erne;rit De;s 94 8450 sw 201 teef md, flodda 33189 754.264.4773 A I A NGAKE5 General Note: Any errors, amblguhlm, and omiss m In drawtps and speciltcolloru shoe be reported to the orchbd for correch n before any part of the work b darted. Unlo ape* shpdated, no additional aba ce will be mode In the contrad w4or manufochaers to or by vHw of errors, ambi fiiesand/oronbons Ad should taus been dscovered durkg the preparation of to bid estimate and directed to our dla tion In a timely manner. DO NOT SCAtF DRAWINGS. the %ured dmenNons only. Contractor shall verify all dmeN ns and corrditiorn. In fie event of a confid, notiythe Designer before proceeding ym the work sheet A-3 of q