07-1025R-005ABBREVIATIONS:
A.F.F.
ABOVE FINISH FLOOR
A.I.C.S.
AMPERES INTERRUPTING CAPACITY SYMMETRICAL
C
CONDUIT
E
EXISTING
E.C.
EMPTY CONDUIT
E.M.T.
ELECTRIC METALLIC TUBE
E.W.C.
ELECTRIC WATER COOLER
E.W.H.
ELECTRIC WATER HEATER
FA
FIRE ALARM
G.F.I.
GROUND FAULT INTERRUPTER
G.N.D.
GROUND
H.P.
HORSE POWER
M.H.
MOUNTING HEIGHT
MTD
MOUNTED
N.I.C.
NOT IN CONTRACT
N.L.
NIGHT LIGHT
N.T.S.
NOT TO SCALE
P.C.
PULL CHAIN
R
RELOCATED
R.G.S.
RIGID GALVANIZED STEEL
R.S.C.
RIGID STEEL CONDUIT
T.Y.P.
TYPICAL
U.G.
UNDERGROUND
U.O.N. UNLESS OTHERWISE NOTED
W.P. WEATHERPROOF
WORKING NOTES
1. ALL RFI OR SIMILAR TO ENGINEER OFFICE TO BE SUBMITTED ON WRITING THOROUGH
ARCHITECT OFFICE.
2. IF ARCHITECTURAL CHANGES ARE MADE AFTER THE COMPLETION OF THE ENGINEERING
DRAWINGS, CONTACT ARCHITECT OFFICE FOR FIELD COORDINATION.
3. CONTRACTOR SHALL PATCH AND REPAIR EXISTING ROOFING MATERIAL AS REQUIRED
BY AN APPROVED ROOFING CONTRACTOR FOR ROOFING MEMBRANE ORIGINALLY
INSTALLED SO AS NOT TO VOID WARRANTY.
4. CONTRACTOR SHALL BE RESPONSIBLE FOR PROTECTION OF ANY OPENING AND SECURING
ACCESS WITHIN AREA OF WORK ON A DAILY 24 HR BASIS.
5• NO CHANGE ORDERS WILL BE APPROVED WITHOUT THE WRITING AUTHORIZATION OF THE
FRANCISCO GARCIA AND ASSOC. CONSULTING ENGINEERS.
6. AS BUILT DRAWINGS ARE RESPONSIBILITY OF THE CONTRACTOR . FRANCISCO GARCIA
AND ASSOC. IS NOT RESPONSIBLE OF THE EXECUTION OF AS BUILT DRAWINGS.
7. ANY CHANGES REQUESTED BY CONTRACTOR DURING THE CONSTRUCTION PROCESS SHOULD
BE SUBMITTED TO THE ARCHITECT FOR SHOP DRAWING REVIEW AND APPROVAL
ELECTRICAL NOTES
1. THIS WORK SHALL BE DONE AS PER REQUIREMENTS OF THE NATIONAL ELECTRICAL CODE
(NFPA A #70) AND ALL OTHER APPLICABLE CODES OR LOCAL ORDINANCES.
2. THE INSTALLATION SHALL BE MADE SO THAT THE COMPONENT PARTS FUNCTION TOGETHER
AS A WORKABLE SYSTEM. IT SHALL BE COMPLETED WITH ALL EQUIPMENT IN PROPER
ADJUSTMENT AND IN OPERATIVE CONDITION. THE WORK SHALL BE EXECUTED IN CONFORMITY
NTH THE BEST PRACTICE AND SO AS TO CONTRIBUTE TO EFFICIENCY OF OPERATION
MINIMUM MAINTENANCE ACCESSIBILITY OF SIGHTLINESS.
3. THE CONTRACT DRAWINGS INDICATE THE EXTENT AND GENERAL ARRANGEMENTS OF
EQUIPMENT AND WIRING SYSTEMS. CONTRACTOR SHALL COORDINATE HIS WORK
WITH THE WORK OF OTHER TRADES.
4. THE CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS, TAXES ROYALTIES, AND
OTHER FEES AS REQUIRED FOR THE INSTALLATION OF A COMPLETE ELECTRICAL SYSTEM.
5. THE PLANS ARE GENERALLY DIAGRAMMATIC AND THE CONTRACTOR SHALL COORDINATE
HIS WORK WITH THE WORK OF OTHER TRADES SO THAT INTERFERENCES BETWEEN CONDUITS,
PIPING, EQUIPMENT, ARCHITECTURAL, AND STRUCTURAL WORK WILL BE AVOIDED.
6. ALL MATERIALS AND EQUIPMENT SHALL BE GUARANTEED FOR A PERIOD OF (1) YEAR FROM
DATE OF FINAL ACCEPTANCE THEREOF AGAINST DEFECTIVE MATERIALS, CONSTRUCTION OR
WORKMANSHIP.
7. UPON COMPLETION OF THE WORK AND AS A CONDITION PRECEDENT TO FINAL PAYMENT,
THE CONTRACTOR SHALL PREPARE AND DELIVER TO THE OWNER A COMPLETE SET OF
"AS -BUILT" DRAWINGS.
8. RULES OF LOCAL UTILITY COMPANIES SHALL BE COMPLIED WITH, COORDINATE INSTALLATION
WITH REPRESENTATIVES BEFORE COMMENCING WORK.
9. FOLLOWING COMPLETION OF THE WORK REQUIRED HEREIN, THE CONTRACTOR SHALL BE
RESPONSIBLE FOR THE REMOVAL OF ALL EXCESS MATERIAL, AND DEBRIS GENERATED BY
THE WORK.
10. ALL ELECTRICAL MATERIAL AND EQUIPMENT SHALL BE APPROVED BY UNDERWRITER'S
LABORATORIES AND SHALL BEAR THE U.L. LABEL. MATERIAL SHALL BE NEW, OTHERWISE
NOTED.
11. AFTER THE SYSTEM, EQUIPMENT AND FIXTURES INSTALLATION HAVE BEEN COMPLETED, THE
CONTRACTOR SHALL CONDUCT AN OPERATING TEST FOR APPROVAL AND ACCEPTANCE BY OWNER.
12. SHOP DRAWINGS SHALL BE SUBMITTED ON ALL MATERIALS AND EQUIPMENT TO BE
USED BY THE ELECTRICAL CONTRACTOR FOR APPROVAL BY THE ENGINEER.
13. ALL WIRE #10 AWG AND SMALLER SHALL BE SOLID OR STRANDED COPPER, ALL WIRE #8 AWG
AND LARGER SHALL BE STRANDED COPPER. ELECTRICAL CONDUCTORS SHALL BE THHN/THWN
COPPER MIN. #12 FOR POWER CKT'S, #14 FOR CONTROL CKT'S. - 120V - HOME RUNS LONGER
THAN 120' - #1O'S.
14. ALL CONDUIT SHALL BE E.M.T. WHERE CONCEALED IN WALLS OR CEILINGS INSIDE
BUILDINGS, IT SHALL BE GALVANIZED RIGID STEEL WHERE EXPOSED OR IN
CONCRETE, CONDUIT UNDERGROUND COULD BE PVC SCHEDULE 40 CONDUIT PROVIDED THAT A
GROUND 'GREEN WIRE" IS BONDED AT EACH END TO THE METALLIC RACEWAYS. PROVIDE RGS.
INSIDE BUILDING UP TO 8'-0" ABOVE GROUND WHERE EXPOSED TO PHYSICAL DAMAGE.
15. CONTRACTOR SHALL COORDINATE THE ELECTRICAL AND TELEPHONE SERVICES WITH
FP&L CO. AND BELLSOUTH CO. RESPECTIVELY TO VERIFY THAT ALL THEIR
REQUIREMENTS ARE MET.
16. ANY DISCREPANCIES WITH ACTUAL FIELD CONDITIONS OR MANUFACTURED PRODUCTS
SHALL BE NOTIFIED TO ENGINEER BEFORE PROCEEDING WITH WORK AFFECTED.
17, CONTRACTOR SHALL VISIT THE SITE AND ASCERTAIN ALL EXISTING CONDITIONS THAT
MAY CAUSE LIMITATIONS, AND INCLUDE IN HIS BID PROPOSAL ALL COSTS NECESSARY
FOR A COMPLETE AND OPERATIONAL INSTALLATION.
18. DESIGN IS BASED ON COPPER CONDUCTORS.
19. CONTRACTOR IS DIRECTED TO REVIEW THE BUILDING SHELL PLANS AND SPECIFICATIONS
FOR LIMITATIONS OF CONSTRUCTION DEFINITION OF WORKMANSHIP AND IDENTIFICATION
OF MATERIALS AND PRODUCTS. CONTRACTOR SHALL INCLUDE IN HIS BID PROPOSAL
ALL COSTS NECESSARY TO INTEGRATE THOSE APPLICABLE SECTIONS OF DIVISION 15 & 16
INTO THE CONTRACT WORK.
20. ALL RFI OR SIMILAR TO ENGINEER OFFICE TO BE SUBMITTED ON WRITHING THOROUGH
ARCHITECT OFFICE.
21. NEW TYPEWRITTEN PANEL DIRECTORY SHALL BE FURNISHED AFTER JOB IS COMPLETED
REFLECTING ANY CHANGES AND ADDITIONS MADE DURING CONSTRUCTION.
22. ALL BRANCH CIRCUITS TO HAVE A GREEN EQUIPMENT GROUNDING CONDUCTOR
SIZED AS PER N.E.C. 250-95.
EXISTING 3 SETS OF 4#400kcmi
THWN CU IN 3" C EACH
EXISTING GROUND
wl"10
Im-
0
C
ELECTRICAL SYMBOL LEGEND
DUPLEX RECEPTACLE 2 POLE, 3 WIRE GROUND TYPE 20A, 125V HOMERUN TO PANEL (U.O.N. #12 IN 1/2"C.)
MOUNTED AT 18" AFF. (NEMA 5-20R)
SHORT TCKS DENOTE N0. OF PHASE WIRES.
SINGLE RECEPTACLE, SAME AS ABOVE LONG TICK DENOTES NEUTRAL WIRE.
DOT DENOTES GROUND WIRE.
SAME AS ABOVE WITH ISOLATED GROUND
CONDUIT RUN CONCEALED IN CEILING OR WALL
SAME AS ABOVE, MOUNTED ABOVE COUNTER OR MOUNTED
AT 42" A.F.F.
SAME AS ABOVE WITH DEDICATED CIRCUIT
SAME AS ABOVE WITH DEDICATED CIRCUIT. MOUNTED ABOVE
COUNTER OR MOUNTED AT 42" A.F.F.
SAME AS ABOVE, QUADRUPLEX RECEPTACLE.
DUPLEX FLOOR RECEPTACLE, 1 POLE, 3 WIRE GROUND TYPE, 20A
125V, FLUSH MTD. BOX IN SLAB.
TELEPHONE OUTLET WITH 3/4" EMPTY CONDUIT TO CEILING WITH
PULL STRING. MOUNTED AT 18" AFF. (UNLESS OTHERWISE
NOTED) 'V= MOUNTED AT 45' AFF P= PUBLIC PHONE.
DATA OUTLET WITH 3/4" EMPTY CONDUIT TO CEILING WITH
PULL STRING, MOUNTED AT 18 AFF. (UNLESS OTHERWISE NOTED)
COMBINATION DATA/TELEPHONE OUTLET WITH 3/4' EMPTY
CONDUIT TO CEILING WITH PULL STRING. MOUNTED AT 18" AFF.
(UNLESS OTHERWISE NOTED)
COMBINATION DATA/TELEPHONE OUTLET WITH 3/4' EMPTY
CONDUIT TO CEILING WITH PULL STRING. FLUSH FLOOR MOUNTED
O TELEPHONE FLUSH FLOOR OUTLET WITH 3/4' EMPTY CONDUIT TO
TO CEILING PULL STRING.
-� DATA FLUSH FLOOR OUTLET WITH 3/4" EMPTY CONDUIT TO
CEILING WITH PULL STRING.
TELEPHONE BACKBOARD
0
THERMOSTAT
Q / &
CEILING OR WALL MOUNTED JUNCTION BOX
PB
PULL BOX
PUSH BUTTOM
Dj A B DISCONNECT, SWITCH. (A = NUMBER OF POLES, B = SWITCH SIZE,
C = FUSE SIZE)
KEY NOTES: l�v
EXISTING 3 POLE/1200 AMP FUSIBLE MAIN 1 OF 4
� 2 EXISTING ELECTRICAL METER
EXISTING 3 POLE/400 AMP DISCONNECT SWITCH
4 EXISTING 3 POLE/100 AMP CIRCUIT BREAKER
EXISTING 3 POLE/150 AMP CIRCUIT BREAKER
EXISTING 3 POLE/600 AMP DISCONNECT SWITCH
/`� CONDUIT RUN UNDERGROUND, OR BELOW SLAB
CAPPED END
STUB -DOWN
1_1�SD
SU STUB -UP
FLEXIBLE CONDUIT (NO LONGER THAN 6'-0")
/\/ v v CONNECTION TO ITEM OF EQUIPMENT, EXACT POINT AND METHOD OF
CONNECTION TO BE IN THE FIELD OR COORDINATED WITH PRODUCT
MANUFACTURER.
PANELBOARD
Wp$ m MOTOR RATED SINGLE POLE SWITCH 20 AMPS MINIMUM WEATHERPROOF
I EXISTING 12x12 GUTTER A
EXISTING
3,P/1000A
MAIN 2 OF 4 O
120/208V 1 O
30-4W �
NOTE:
1.- THIS IS A LEGEND FOR GENERAL USE. SEVERAL SYMBOLS SHOWN MAY NOT
BE USED ON PLANS. ADDITIONAL SYMBOLS WHICH DO NOT APPEAR ON THIS LEGEND
ARE DESCRIBED ON PLANS.
EXISTI G 12x12 GUTTER
3 4
EXISTING SERVICE ENTRANCE
CONDUCTORS TO FP&L TRANSFORMER
PARTIAL ELECTRICAL RISER DIAGRAM
NOT TO SCALE
EXISTING
0000
1000 AMP
120/208
O
0
Q
0
O
0
3 PHASE
0
0
9
M.L.O.
0
0
000
0
o
a
Re�
EXISTING 2 POLE,
150 AMP CIRCUIT
BREAKER, 208V
NEW 4#2 THWN CU
IN 1-1/2" CONDUIT
101
NEW
'ANE
11810
NEW METER
EXIST.
'ANEL
,fA„
0
5TH FLOOR
EXIST. 3#1 /0 THWN CU
IN 1-1 /2" CONDUIT
4TH FLOOR
1ST FLOOR
CI'fY OF SOUTri N1IAN-; j
BIJILUING3 WEPT,
EL ECTRICA1, SE.Crjo7 j
APPROVED BY:
DATE: • J�
ERNESTO CERCAS , AIA
A R C H I T E C T
FIRM CERTIFICATION NO.
AR 0014405
2423 S.W. 25 TERRACE
MIAMI, FLORIDA
33133
Tel: 305.285.9812
Fax: 305.285.2299
Revisions:
10 2/29/08 ADD HVAC
0
Li
LLJ
I-
V)
V)
Q
�
O
LL1
U
O
U
U
r
4_�O
In
Z
Q
Q
U
p
Z
C _
O
V)
U
Lli
J
LLJ
Li.J
Z
Project: 270102
MARINA &
ASSOCIATES, P.A.
CONSULTING ENGINEERS
717 PONCE DE LEON BLVD.
SUITE 329
CORAL GABLES, FL 33134
CA0007454
TEL: (305) 444-4550
FAX: (305) 444-9696
info®marina-associates.com
VICTOR G. MARINA, P.E.
ELECTRICAL PE0048539
NOTES,
LEGEND
ELECTRICAL
RISER
& SCH ED.
Scale:
AS NOTED
Drawn:
VGM
Checked:
VGM
Date:
7 23 2007
Ew5