06-809-0171. OBTAIN AND PAY FOR THE REQUIRED PERMITS AND INSPECTION FEES,
2. MECHANICAL WORK SHALL COMPLY WITH STATE AND LOCAL CODES, FLORIDA
ADMINISTRATIVE CODES, 2001 FLORIDA BUILDING CODE, NFPA 90-A 1999,
NFPA 101 LIFE SAFETY CODE 2000, AND ALL STATE AND LOCAL ORDINANCES.
3, SUBMITTALS: SUBMIT 2 SETS OF SHOP DRAWINGS FOR THE FOLLOWING:
A. DUCT SYSTEMS SHOWING INTENDED ROUTING OF DUCTWORK MEET FIELD
CONDITIONS.
B. COMPLETE SET OF PUBLISHED MANUFACTURERS DATA ON ALL MECHANICAL
EQUIPMENT MEETING REQUIREMENTS CALLED FOR
IN SCHEDULES.
C. STATIC AND TOTAL PRESSURE DROP, FACE VELOCITY, THROW AND NOISE
LEVEL FOR EACH OF THE AIR DISTRIBUTION DEVICES AT THE AIR FLOWS
4, ARRANGE FOR, PAY FOR AND ACCOMPLISH ALL WORK REQUIRED TO PASS
TESTS REQUIRED BY AGENCIES HAVING AUTHORITY. OBTAIN CERTIFICATES OF
COMPLIANCE FROM SAID AUTHORITIES AND FORWARD SAME TO THE OWNER.
D.
1. GUARANTEE: MECHANICAL WORK SHALL BE GUARANTEED AGAINST FAULTY
MATERIAL OR WORKMANSHIP FOR A PERIOD OF ONE YEAR FROM THE DATE OF
FINAL ACCEPTANCE.
2. MAINTENANCE: EQUIPMENT AND MATERIAL INSTALLED UNDER THIS DIVISION
SHALL BE PERIODICALLY LUBRICATED, INSPECTED AND SERVICED BY
COMPETENT MECHANICS IN ACCORDANCE WITH MANUFACTURERS'
RECOMMENDATIONS. THIS FUNCTION BECOMES THE RESPONSIBILITY OF THE
OWNER WHEN THE SYSTEM IS ACCEPTED BY THE OWNER. THE ONE-YEAR
MATERIAL AND WORKMANSHIP GUARANTEE IS NOT INTENDED TO SUPPLANT
NORMAL INSPECTION OR SERVICE AND SHALL NOT BE CONSTRUED TO MEAN
THAT THE CONTRACTOR WILL PROVIDE FREE SERVICE FOR NORMAL
MAINTENANCE ITEMS SUCH AS PERIODIC LUBRICATION, ADJUSTMENT NOR TO
CORRECT BREAKAGE, MALADJUSTMENT AND OTHER TROUBLE CAUSED BY
IMPROPER MAINTENANCE. EQUIPMENT SHALL BE TURNED OVER TO THE
OWNER, OPERATING FREE FROM DEFECTS, CLEAN AND LUBRICATED, CLEAN
FILTERS SHALL BE INSTALLED IMMEDIATELY PRIOR TO TURNOVER TO OWNER,
INCLUDE DETAILED INSTRUCTIONS ON PERIODIC MAINTENANCE AND
LUBRICATION.
3, OPERATING INSTRUCTIONS: FURNISH TO THE OWNER THREE COMPLETE
BOUND SETS OF OPERATION AND MAINTENANCE INSTRUCTIONS. BOUND SETS
SHALL INCLUDE A RECOMMENDED SPARE PARTS LIST,
a iEST411D "C
1. TEST AND BALANCE TO BE PERFORMED BY INDEPENDENT, NEBB AND/OR AABC
CERTIFIED CONTRACTOR.
2. PROVIDE CERTIFIED TEST AND BALANCE REPORT SEVEN DAYS PRIOR TO FINAL
INSPECTION.
D. 0110M
APPLICABLE STANDARDS
SMACNA: USE MATERIAL, WEIGHT, THICKNESS, GAUGE, REINFORCING, SEAMS
AND JOINTS, SUSPENSION, WORKMANSHIP AND CONSTRUCTION AND
INSTALLATION METHODS AS OUTLINED IN THE SHEET METAL AND AIR
CONDITIONING CONTRACTORS NATIONAL ASSOCIATION, INC., HVAC DUCT
CONSTRUCTION STANDARDS, METAL & FLEXIBLE, FIRST EDITION, 1985.
MANUFACTURED ROUND DUCTWORK SHALL COMPLY WITH THE
MANUFACTURER'S PUBLISHED RECOMMENDATIONS AND INSTALLATION
INSTRUCTIONS.
SHEET METAL DUCTWORK
MATERIAL: PRIME QUALITY 48 INCH WIDE RESQUARE TIGHT COAT COLD -
ROLLED HOT -DIPPED GALVANIZED STEEL CAPABLE OF DOUBLE SEAMING
WITHOUT FRACTURE. CONFORM TO THE REQUIREMENTS OF ASTM A-525 AND
ASTM-G90 FOR A MINIMUM GALVANIZING COAT OF 1.25 OUNCES PER SQUARE
FOOT TOTAL FOR BOTH SIDES.
EQUIPMENT CONNECTIONS: PROVIDE AND INSTALL ALL DUCT CONNECTIONS
TO AIR HANDLING UNITS AND FANS AND PROVIDE FLEXIBLE CONNECTIONS,
ELBOWS AND BENDS WHICH MINIMIZE NOISE AND PRESSURE DROP.
COORDINATION: COORDINATE DIMENSIONS AT INTERFACES OF DISSIMILAR
TYPE OF DUCTWORK AND AT INTERFACES OF DUCTWORK WITH EQUIPMENT
SO THAT PROPER OVERLAPS, INTERFACES, ETC., OF INSULATION AND
CONTINUITY OF VAPOR BARRIERS ARE MAINTAINED. WHERE DUCTS OF TWO
DISSIMILAR METALS MEET, THE JOINTS SHALL BE INSTALLED SUCH THAT THE
METALS DO NOT CONTACT EACH OTHER.
DUCTWORK MINIMUM REQUIREMENTS:
UNLESS OTHERWISE INDICATED ALL DUCTWORK SHALL COMPLY WITH
THE FOLLOWING MINIMUM PRESSURE REQUIREMENTS:
2 INCH W.G. PRESSURE:
FROM THE SUPPLY FAN DISCHARGE TO A ROOM SUPPLY AIR
E
1. FLEXIBLE DUCT CONNECTIONS:
DUCT CONNECTOR SHALL BE WATERPROOF NEOPRENE -COATED
POLYMER FABRIC SPECIFICALLY MANUFACTURED TO PROVIDE AN
AIRTIGHT FLEXIBLE CONNECTION BETWEEN DUCTWORK AND ROTATING
OR VIBRATING EQUIPMENT. MINIMUM TEAR AND TENSILE STRENGTH
SHALL BE 125 AND 300 POUNDS RESPECTIVELY.
2. MANUAL VOLUME DAMPERS:
GENERAL: THESE DAMPERS ARE OTHER THAN THOSE SPECIFIED AS BEING
INTEGRAL WITH A REGISTER, DIFFUSER
DAMPERS SHALL BE MADE OF GALVANIZED STEEL, STAINLESS STEEL,
STEEL WITH ACID/SOLVENT CHEMICAL RESISTANT COATING, OR STEEL
SPRAYED OR DIPPED ALUMINUM RUST RESISTANT FINISH AS REQUIRED
TO MATCH THE ATTACHED DUCT MATERIAL; STIFFENED AND FABRICATED
TO PREVENT VIBRATION AND FLUTTER.
PRESSURE DROP THROUGH THE DAMPER SHALL NOT EXCEED 0,03
INCHES W.G. AT 1000 FPM VELOCITY BASED ON THE DAMPER FACE AREA.
THE DAMPER SHALL HAVE FULL SHUTOFF CAPABILITY, WITH LEAKAGE
RATES LESS THAN 10 CFM/SQUARE FT OF DAMPER FACE AREA AT 4
INCHES W.G. AIRFOIL OPPOSED BLADE DAMPERS SHALL BE PROVIDED IF
THE VELOCITY THROUGH A FULLY OPENED DAMPER EXCEEDS THE
MANUFACTURER'S PRINTED MAXIMUM VELOCITY LIMIT.
HVAC SPECIFICATIONS
3. DUCT ACCESS DOORS:
PROVIDE AND INSTALL AN ACCESS DOOR IN THE DUCTWORK FOR
EACH FIRE DAMPER; PERMANENT TEST PORTS; AND WHERE
ACCESS FOR OBSERVATION OR MAINTENANCE IS NECESSARY.
DOORS SHALL BE FACTORY PREFABRICATED DOUBLE WALL, 24 GAUGE
GALVANIZED STEEL. ACCESS DOORS SHALL BE ABLE TO WITHSTAND THE
SAME TEST PRESSURES WITHOUT DEFORMATION, VIBRATION OR
LEAKAGE AS THE DUCTWORK AND CASINGS IN WHICH THEY ARE
INSTALLED.
LATCHES: DOORS SHALL BE PROVIDED WITH ADJUSTABLE TENSION CATCHES
AND SHALL BE GASKETED AROUND THEIR PERIMETERS WITH FELT OR SOFT
RUBBER GASKETING ATTACHED TO THE DOORS WITH CEMENT AND
COUNTERSUNK RIVETS FOR AN AIRTIGHT SEAL. ACCESS DOORS LESS THAN
24 INCH IN HEIGHT SHALL HAVE A CONTINUOUS PIANO HINGE (OR TWO 1 INCH
BY 1 INCH BUTT HINGES WHERE CONCEALED) AND ONE PANEL LATCH;
ACCESS DOORS IN CASINGS AND DUCTS 24 INCH IN HEIGHT AND OVER SHALL
HAVE TWO HEAVY BUTT HINGES AND TWO PAIRS OF LEVER -TYPE LATCHES
OPERABLE FROM BOTH SIDES OF THE DOOR, INSTALLED TO OPEN AGAINST
AIR PRESSURE. ACCESS DOORS SHALL BE FASTENED WITH SPRING CLIPS
WHICH RELEASE IN THE EVENT OF SUDDEN NEGATIVE PRESSURE, SUCH AS
CREATED WHEN A DAMPER CLOSES, TO PREVENT DUCT IMPLOSION.
4.TRANSITIONS:
PROVIDE AND INSTALL TRANSITIONS WHERE REQUIRED FOR FINAL
CONNECTION TO ANY DUCT FITTING, ACCESSORY, DEVICE OR DUCT -
MOUNTED EQUIPMENT.
5. FIRE DAMPER:
FIRE DAMPERS SHALL COMPLY WITH UNDERWRITERS LABORATORIES
(UL) STANDARD 555 AND BEAR THE UL TEST LABEL WITH A 1-1/2 HOUR
FIRE PROTEC1ON RATING FOR PENETRATIONS IN 1-HOUR AND 2-HOUR
DAMPERS SHALL BE TESTED UNDER DYNAMIC LOAD.
DAMPERS SHALL BE SELECTED SO THAT THE FREE AIR SPACE IS NOT
LESS THAN THE CONNECTED DUCT FREE AREA.
PROVIDE ACCESS DOORS AT EACH FIRE DAMPER WITH DOOR SIZE
AND LOCATION WHICH WILL FACILITATE REPLACING FUSIBLE LINKS AND
RESETTING THE DAMPER. THE ACCESS DOOR SHALL BE INSULATED WHEN
INSTALLED IN INSULATED DUCTWORK.
F. +
SMOKE DETECTORS SHALL BE OF THE IONIZA11ON TYPE, UL-APPROVED.
THEY SHALL BE PROVIDED WITH RED LED INDICATORS AT SMOKE DETECTOR
LOCATION, REMOTE RED LED PULSATING INDICATOR AND KEYED TEST SWITCH
ASSEMBLY. THE REMOTE INDICATOR SHALL BE INSTALLED ON THE CEILING
AT A LOCA110N DIRECTLY UNDERNEATH THE SMOKE DETECTOR. THE KEYED
TEST SWITCH ASSEMBLY SHALL BE INSTALLED ON A WALL UNDER THE SMOKE
DETECTOR 5' ABOVE FINISHED FLOOR,
C� RU99M 14UINQ
SEAMLESS, HARD DRAWN, TYPE "L" COPPER TUBING REFRIGERANT SUCTION
LINES SHALL BE INSULATED USING 1" THICK FLEXIBLE UNICELLULAR PIPING
UNSPLIT INSULATION. ALL INSULA11ON SHALL COMPLY WITH NFPA 90-A.
P
BLOWER COIL UNITS SHALL BE COMPLETELY FACTORY ASSEMBLED INCLUDING COIL, CONDENSATE
DRAIN PAN, FAN, MOTOR, FILTERS AND CONTROLS IN AN INSULATED CASING THAT CAN BE
APPLIED IN HORIZONTAL OR VERTICAL CONFIGURATION. THE T" MODEL INDICATES AN
"AIRTITETM" MODEL WITH 4,2 "R" VALUE INSULATION AND ADDITIONAL SEALING SYSTEMS.
THIS NEW LINE OF TWE-P AIR HANDLERS PROVIDES EXCLUSIVE COMPACT SIZE COMBINED WITH
SIMPLE 6-WAY CONVERTIBILITY IN SIZES UP TO 5 TONS. THE UNIT SHIPS IN THE RIGHT-HAND
HORIZONTAL CONFIGURATION AND CONVERTS TO VERTICAL UPFLOW JUST BY STANDING THE
UNIT ON END. NO TOOLS REQUIRED. SIMPLE COIL ROTATION PROVIDES DOWNFLOW AND
HORIZONTAL LEFT APPLICATIONS.
CASING
UNITS SHALL HAVE A RUGGED SHEET METAL AND STEEL FRAME CONSTRUCTION AND SHALL BE
PAINTED WITH AN ENAMEL FINISH. CASING SHALL BE INSULATED AND KNOCKOUTS FOR
ELECTRICAL POWER AND CONTROL WIRING,
REFRIGERANT CIRCUITS
THE TWE-P UNITS HAVE A SINGLE REFRIGERANT CIRCUIT. TWE01 8-063P REFRIGERANT CIRCUIT
SHALL BE CONTROLLED BY A FACTORY- INSTALLED NON -BLEED THERMAL EXPANSION VALVE.
COIL
ALUMINUM FIN SURFACE SHALL BE MECHANICALLY BONDED TO 3/8-INCH OD COPPER TUBING,
COILS SHALL BE FACTORY PRESSURE AND LEAK TESTED.
FAN
FORWARD CURVED, DYNAMICALLY BALANCED AND STATICALLY BALANCED WITH 3-SPEED DIRECT
DRIVE SHALL BE STANDARD, FAN MOTOR BEARING SHALL BE PERMANENTLY LUBRICATED,
CONTROLS
LOW VOLTAGE PIG TAILS, FAN CONTACTOR, AND PLUG-IN MODULE FOR ACCESSORY ELECTRIC
HEAT CONTROL SHALL BE INCLUDED. TWE MODELS ALSO INCLUDE CHECK VALVES.
FILTERS
FILTERS SHALL BE INCLUDED AS STANDARD, ONE -INCH LOW VELOCITY SEMI -PERMANENT TYPE
(EXCEPT 5-TON - WASHABLE FILTER).
ACCESSORIES
ELECTRIC HEATERS - SHALL BE AVAILABLE IN A WIDE RANGE OF CAPACITIES AND VOLTAGES
WITH VARIOUS STAGING OPTIONS, AND PLUG-IN CONTROL WIRING. HEATERS SHALL FIT INSIDE
THE INTERNAL COMPARTMENT.
CONTROL SYSTEM
A CENTRALLY LOCATED WEATHERPROOF CONTROL PANEL SHALL CONTAIN THE FIELD DOWER
CONNECTION POINTS, CONTROL TERMINAL BLOCK AND CONTROL SYSTEM. POWER AND
STARTING COMPONENTS SHALL INCLUDE FAN MOTOR CONTACTORS, TIME DELAY RELAY(S) FOR
THE COMPRESSOR(S), INHERENT FAN MOTOR OVERLOAD PROTECTION AND UNIT POWER
TERMINAL BLOCKS FOR CONNECTION TO REMOTE DISCONNECT SWITCH. SAFETY AND
OPERATING CONTROLS SHALL INCLUDE A MANUALLY RESET HIGH PRESSURE SWITCH AND AN
AUTOMATIC RESET LOW PRESSURE SWITCH. BARRIER PANELS SHALL BE FURNISHED TO
PROTECT AGAINST ACCIDENTAL CONTACT WITH LINE VOLTAGE WHEN ACCESSING THE CONTROL
SYSTEM.
SERVICE ACCESSIBILITY
ENTRANCE TO THE SEPARATE COMPRESSOR(S) AND CONTROL COMPARTMENT SHALL BE
THROUGH AN ACCESS PANEL. INSTALLATION AND MAINTENANCE MANUALS SHALL BE SUPPLIED
WITH EACH UNIT WITHIN THE CONTROL COMPARTMENT.
DEVICES: PROVIDE AIR DISTRIBUTION DEVICES AS INDICATED. ALL AIR
DISTRIBUTION DEVICES PROVIDED SHALL BE THE PRODUCT OF A SINGLE
MANUFACTURER UNLESS SPECIFICALLY INDICATED OTHERWISE.
MATERIAL: ALL DEVICES SHALL BE CONSTRUCTED OF EXTRUDED ALUMINUM
UNLESS OTHERWISE INDICATED.
FINISH: EACH AIR DISTRIBUTION DEVICE SHALL HAVE A FACTORY APPLIED
BAKED ENAMEL FINISH. ALL DEVICES SHALL RE FINISHED IN WHITE
EXCEPT SIDEWALL DEVICES LOCATED ON STORAGES AND MECHANICAL ROOM
WITCH SHALL BE FINISHED IN ALUMINUM.
INTEGRAL COMPONENTS: ALL DAMPERS AND OTHER COMPANION DEVICES
WHICH FORM AN INTEGRAL PART OF AN AIR DISTRIBUTION DEVICE SHALL
BE FACTORY -MADE.
COORDINATE THE LOCATION OF AIR DISTRIBUTION DEVICES
SURFACE MOUNTED DEVICES SHALL BE SECURED TO AND SUPPORTED BY
METAL DUCT BRANCHES OR DROPS. DEVICES SHALL BE SUPPORTED BY
SEPARATE HANGERS WHERE FLEXIBLE DUCT CONNECTIONS ARE INDICATED.
SPOT LOUVER SHALL BE OF HEAVY DUTY CONSTRUCTION OF ALL ALUMINUM ALLOY MATERIALS
AND SHALL NOT BE WELDED, FASTENED OR RIVETED. THE DEVICE SHALL HAVE A PRECISION
AIRFLOW ADJUSTMENT TO MODULATE EXISTING AIRFLOW FROM ANY POSITION BETWEEN FULLY
OPEN TO COMPLETE SHUT-OFF WITHOUT OBJECTIONABLE NOISE OR VIBRATION. THE SEALING
GASKETS SHALL BE CLOSED -CELL NEOPRENE OR FELT PROVIDING LEAK -PROOF SEALS, THE
LOUVER SHALL BE CAPABLE OF DIRECTING THE AIRSTREAM UP TO A MINIMUM OF 39' FROM
LOUVER CENTER LINE TO ANY DIRECTION.
THE FLUSH FACED DIFFUSER SHALL CONSIST OF A TWO PIECE, HIGH DENSITY, HIGH STRENGTH
PLASTIC HOUSING, REMOVABLE LOCK CONNECTION BETWEEN THE MOUNTING BODY AND
REMOVABLE CORE. THE CONCEALED MOUNTING SYSTEM USES HIGH TENSILE SPRING CLIPS FOR
DUCT WALL INSTALLATION, A MINIMUM OF 3 # E SCREWS SHALL BE USED TO ENSURED
PERMANENT MOUNTING AT THE DUCT CONNECTION.
J.
PERFORMANCE DATA:
PROVIDE THERMAL PERFORMANCE, DENSITY AND VAPOR PERMEANCE FOR EACH
TYPE OF INSULATION, FINISH, COVER, FACING OR JACKET SPECIFIED IN THIS
SECTION.
UNLESS OTHERWISE STATED, INSULATION TYPES AND THICKNESSES SPECIFIED ARE
BASED ON INSULATING MATERIALS HAVING A "K" VALUE (BTU PER HOUR PER
SQUARE FOOT PER DEGREE TEMPERATURE DIFFERENCE) PER INCH OF THICKNESS
AS INDICATED.
VAPOR PERMEANCE IS BASED ON VAPOR RETARDANT MATERIALS HAVING WATER
VAPOR TRANSMISSION RATES IN PERMS (GRAINS OF VAPOR PER HOUR PER SQUARE
FOOT PER INCH OF MERCURY VAPOR PRESSURE DIFFERENTIAL).
ALTERNATE MATERIALS SHALL BE APPROVED ON THE BASIS OF THICKNESS
PROVIDING EQUIVALENT HEAT TRANSFER OR VAPOR TRANSMISSION RATES.
APPLICABLE STANDARDS
NFPA: ALL MATERIALS AND ADHESIVES USED SHALL CONFORM TO THE
REQUIREMENTS OF NFPA 90A, 1993 REVISION, AS TO FLAME SPREAD AND SMOKE
DEVELOPED RATINGS THROUGHOUT THEIR OPERATING TEMPERATURE RANGE. ALL
INSULATION, JACKETS, FACINGS AND ADHESIVES USED TO ADHERE THE JACKET OR
FACING TO THE INSULATION, INCLUDING FITTINGS AND BUTT STRIPS, SHALL HAVE A
NON-COMBUSTIBLE FIRE AND SMOKE HAZARD RATING AND LABEL AS TESTED BY
ASTM E-E4, NFPA 255, 1990 REVISION AND UL-723 NOT EXCEEDING FLAME SPREAD
VALUE OF 25 AND SMOKE DEVELOPED/FUEL CONTRIBUTED VALUE OF 50.
ACCESSORIES SUCH AS MASTICS, CEMENTS, TAPES AND CLOTH FOR FITTINGS
SHALL HAVE THE SAME RATINGS.
FLORIDA ENERGY CODE: INSULA11ON THERMAL CONDUCTANCE VALUES AND
INSULATION THICKNESS SHALL COMPLY WITH THE FLORIDA ENERGY EFFICIENCY
CODE FOR BUILDING CONSTRUCTION, 1997 REVISION.
INSULATION FOR DUCT SYSTEMS
GENERAL: AIR HANDLING UNIT CASINGS DOWNSTREAM OF COOLING COILS SHALL
BE INSULATED.
INSULATE WITH A MINIMUM OF 2 INCH THICK FIBERGLASS BLANKET WRAP APPLIED
OVER CLEAN, DRY SHEET METAL DUCTWORK INSTALLED TO ALLOW MAXIMUM
FULLNESS AT CORNERS (AVOID EXCESSIVE COMPRESSION). ADHERE DUCT
INSULATION TO METAL AND PROVIDE CONTINUITY OF VAPOR RETARDANT IN
ACCORDANCE WITH THE MANUFACTURER'S RECOMMENDATIONS. WHERE DUCT
WIDTH EXCEEDS 24 INCHES, THE INSULATION SHALL BE ADDITIONALLY SECURED TO
THE BOTTOM OF THE DUCT USING MECHANICAL FASTENERS SPACED 1 FOOT ON
CENTER TO PREVENT SAGGING OF THE INSULATION.
DUCTWORK INSULATION SHALL BE INORGANIC FIBROUS GLASS, FLEXIBLE BLANKET
OF GLASS FIBER FACTORY LAMINATED TO A REINFORCED FOIL KRAFT (FRK) VAPOR
RETARDANT WITH A MINIMUM 2 INCH TAPING AND STAPLING FLANGE ON ONE EDGE.
SUITABLE FOR OPERATION AT TEMPERATURES FROM 40 DEGREES F. TO 250
DEGREES F. THERMAL CONDUCTIVITY OF 0.31 AT 75 DEGREES F. MINIMUM DENSITY
OF 1-1/2 PCF.
MGE ARCHITECFS
150 Alhambra Circle, Suite 700
Coral Gables, Florida 33134
T.305.444.0413 F.305.441.6404
www.mgearchitects.com
AA-F000121
CONSULTANTS
5757 Blue Lagoon Dr., •400
Miami, FL 33128
Phone: 305-266-6553
Fax: 305-266-6695
ENGINEERING PGR ARCHITECTURE www.tic-eng ineers.com
b Copyright 2005 TLC Engineering for Architecture, Inc.
EB #0000015 TLC NO:606504
DRAWN BY: JM CHECKED BY: LR
APPROVED BY: RM
1007. CONSTRUCTION DOCUMENTS
PROJECT NAME
GARSH
INVESTMENTS
CORPORATE
OFFICES
South Miami, Florida
JOB NUMBER:
DATE:
CAD FILE NO:
AGENCY NO:
:' •»:
: • : »:
'
2006.000
. "04/24/(X
' "'
REVISIONS/SUBMISSIONS: :
•
Cep.
».00
«« Y
» Y
» »
Y
W • W u
Y •
O Y •
SEAL:
OW
y,
• t• r
Raul S. Mastrap'a,\ pt.
Florida License` #40182
DRAWING TITLE:
SPECIFICATIONS
HVAC
DRAWING NO: M-6