06-809-012FAN SCHEDULE PLAN MODEL STATIC VOLT/ DRIVE FAN TYPE CFM RPM WATTS AMPS ACCESSORIES MARK NO. PRESS. PHASE TYPE SERVICE EF-1 FR 100 INLINE 100 0.2 2900 19 0.18 115/1 DIRECT BATHROOM 1,3,12,13 NOTES: 1. MODEL NUMBERS AND FAN SELECTION ARE BASED ON FANTECH ACCESSORIES: 1) BACKDRAFT DAMPER 8) INLET SCREEN 15) WEATHER COVER 22) HINGED FRAMES 2) THERMOSTAT 9) CURB MOUNT ROOF JACK 16) 2 SPEED / 1 WINDING 23) SPARK/EXPLOSION PROOF 3) BIRDSCREEN 10) SPEED CONTROLLER 17) FILTERS 4) ROOF CURB 11) WALL SHUTTER 18) WALL COLLAR 5) DISCONNECT SWITCH 12) VIBRATION ISOLATORS 19) FAN GUARD/SCREEN 6) DRAIN 13) ROOF CAP 20) COMPANION FLANGES 7) EQUIPMENT SUPPORTS 14) WALL SHUTTER - MOTORIZED 21) INSULATED HOUSING FOR SOUND CONTROL HVAC DESIGN REQUIRES: YES NO DUCT SMOKE DETECTOR X FIRE DAMPER(S) X SMOKE DAMPER(S) X FIRE RATED ENCLOSURE X FIRE RATED ROOF/ FLOOR CEILING ASSEMBLY X FIRE STOPPING X SMOKE CONTROL X J TABLE 4-2 MINIMUM HANGER SIZES FOR ROUND DUCT DIA. MAXIMUM WIRE/ ROD STRAP SPACING DIA. 10" DN. 12' ONE 12 GA. 1 /4" 1 N 22 GA. 250MM DN 3.7M ONE 2.75MM 6.4MM 25.4x0.85MM 11-18" 12' TWO 12 GA. OR ONE 8 GA. 1 /4" 1 N 22 GA. 460MM 3.7M ONE 4.27MM 6.4MM 25.4x0.85MM 19-24" 12' TWO 10 GA. 1 /4" 1 N 22 GA. 610MM 3.7M TWO3.51 MM 6.4MM 25.4x0.85MM 25-36" 12' TWO 8 GA. 3/8" 1 N 20 GA. 9.00MM 3.7M TWO 2.7MM 9.5MM 25.4x0.85MM 12700MM 3.7 M TWO 9.5 MM () 25.4 xO1 00 MM 51-60" 12' TWO 3/8" TWO 1 N 18 GA. 1520 MM 3.7 M TWO 9.5 MM (2) 25.4 x 1.31 MM 61-84" 12' TWO 3/8" TWO 1 N 16 GA, 2130 MM 3.7 M TWO 9.5 MM (2) 25.4 x 1.61 MM NOTES 1. STRAPS ARE GALVANIZED STEEL; RODS ARE UNCOATED OR GALVANIZED STEEL; WIRE IS BLACK ANNEALED, BRIGHT BASIC, OR GALVANIZED STEEL. ALL ARE ALTERNATIVES 2. REFER TO SMACNA DUCT STANDARDS - SECOND EDITION: FIG. 4-4 FOR LOWER SUPPORTS. 3. REFER TO SMACNA DUCT STANDARDS - SECOND EDITION: FIG. 4-2 AND 4-3 FOR UPPER ATTACHMENTS. 4. TABLE ALLOWS FOR CONVENTIONAL WALL THICKNESS, AND JOINT SYSTEMS PLUS ONE LB/SF INSULATION WEIGHT. IF HEAVIER DUCTS ARE TO BE INSTALLED, ADJUST HANGER SIZES TO BE WITHIN THEIR LOAD LIMITS; REFER TO SMACNA DUCT STANDARDS - SECOND EDITION ALLOWABLE LOADS WITH TABLE 4-1. HANGER SPACING MAY BE ADJUSTED BY SPECIAL ANALYSIS. 5. DESIGNERS: FOR INDUSTRIAL GRADE SUPPORTS, INCLUDING SADDLES, SINGLE LOAD TRAPEZE LOADS, LONGER SPANS AND FLANGE JOINT LOADS, SEE SMACNA'S ROUND INDUSTRIAL DUCT CONSTRUCTION STANDARDS. 6. REFER TO SMACNA DUCT STANDARDS - SECOND EDITION: FIGS.3-9 AND 3-10 FOR FLEXIBLE DUCT SUPPORTS. COPYRIGHT: HVAC DUCT CONSTRUCTION STANDARDS METAL AND FLEXIBLE - SECOND EDITION AIR HANDLING UNIT SCHEDULE (DX SPLIT) J COOLING CAPACITY HEATER ELECTRICAL DATA PLAN MODEL AND COND. UNIT OUTSIDE TOTAL AIR EXT. SENS. LVG LVG FAN MAX FUSE VOLT/ MARK MANUFACTURER PLANTOT. MARK AIR CFM CFM S.P. KW/STEPS MODEL No. FLA MBH MBH DB VVB H.P. SIZE PHASE AC-1 4TEC3F60A1000A CU-1 100 1810 .75 60.0 42.5 55 52.4 7.20/2 BAYHTR1 41 OPDCA 1.00 7.2 50 208/1 AC-2 4TTE3F31 A1000A CU-2 140 1020 .75 29.8 22.4 55 52.8 5.76/2 BAYHTR1408PDCA 0.50 4.3 40 208/1 AC-3 MCW509AMUAO CU-3 0 265 .25 9.05 6.3 X X X .024 0.2 X 120/1 NOTES: 1. BASIS OF DESIGN: TRANE 2. AIR HANDLING UNIT AND EXHAUST FAN SHALL SHUT DOWN UPON FIRE ALARM SIGNAL, DUCT SMOKE DETECTOR SENSING PRODUCTS OF COMBUSTION OR MANUAL ACTUATION OF AHU OR EXHAUST STARTER TO "OFF" POSITION. 3. PROVIDE WITH 30% EFFICIENCY FILTERS IN COMPLIANCE WITH ASHRAE STANDARD 52-76. 4. HEAD PRESSURE CONTROLLER FOR OPERATION IN AMBIENT TEMPERATURES DOWN TO 30' F. 5. PROVIDE SINGLE POINT ELECTRICAL CONNECTION. STARTER, RELAY, HEATING ELEMENT AND CONTROLS TO BE PART OF PACKAGED UNIT. 6. AMBIENT DESIGN TEMP IS 95' F. 7. PROVIDE ALL THE LIEBERT UNITS WITH HUMIDIFIER AND CRS ELECTRIC REHEAT 8. HUMIDIFIER SUPPLY SHALL BE 1/4"DIAMETER. 9. PROVIDE OPTIONAL FIRLTER BOX ON ALL THE LIEBERT UNITS AIR DISTRIBUTION SCHEDULE MARK CFM NECK SIZE FACE SIZE LENGTH DESCRIPTION SUPPLY DIFFUSER A 000-100 BASIS OF DESIGN: TITUS OMNI AA 80 24x24 (OR APPROVED EQUAL) 101-200 COLOR: WHITE MATERIAL: ALUMINUM OPPOSED BLADE DAMPERS: YES RETURN GRILLE 000-95 6X6 BASIS OF DESIGN: TITUS 55FL B (OR APPROVED EQUAL) ❑ra 221-550 1196-220 8X10 COLOR: WHITE MATERIAL: ALUMINUM OPPOSED BLADE DAMPERS: NO 1/2, x1/2>'x1/2" GRID 131 EXHAUST/SUPPLY GRILLE 0 BASIS OF DESIGN: SEIHO JRA (OR APPROVED EQUAL) 000-120 60 COLOR: WHITE C1 O MATERIAL: ALUMINUM AMPERTUTE DAMPERS: YES SPOT DIFFUSER C BASIS OF DESIGN: SEIHO PK 000-130 80 (OR APPROVED EQUAL) COLOR: WHITE MATERIAL: ALUMINUM AMPETURE DAMPERS: YES SINGLE DEFLECTION D 4' PLENUM SLOT DIFFUSER BASIS OF DESIGN: TITUS TBD-10 000-170 60 (OR APPROVED EQUAL) COLOR: WHITE MATERIAL: ALUMINUM OPPOSED BLADE DAMPERS: YES SINGLE DEFLECTION NOTES: 1. AIR DISTRIBUTION DEVICES LOCATED WITHIN ACOUSTICAL TILE CEILINGS SHALL BE PROVIDED WITH BORDER TYPE 3 FOR LAY -IN MOUNTING. AIR DISTRIBUTION DEVICES LOCATED WITHIN GYPSUM BOARD CEILINGS OR WALLS SHALL BE PROVIDED WITH BORDER TYPE 1 FOR SURFACE MOUNTING. REFER TO ARCHITECTURAL DOCUMENTS FOR CEILING TYPES. 2. AIR DISTRIBUTION DEVICES LOCATED IN SMALL ROOMS WHERE FULL 24%24" GRID ARE NOT AVAILABLE SHALL BE PROVIDED WITH SURFACE MOUNTING BORDERS IN LIEU OF LAY --IN. SECURE EACH DEVICE TO CEILING GRID WITH FIELD -FABRICATED SUPPORTS. AIR COOLED CONDENSING UNIT SCHEDULE COOLING CAPACITY ELECTRICAL DATA PIPING DATA SYSTEM PLAN MARK M NO.ODE WEIGHT MIN. AMB. REF. NO. COMP. NO. COND. MAX VOLT/ RS RL MBH TEMP TYPE COMP. RLA(EA) FANS FLA(EA) MCA FUSE PHASE O.D. O.D. LBS CU-1 4TTR4060AlOOOA 60 95• R410A 1 30.1 1 1.4 39 60 208/1 7/a" 3/8" 300 CU-2 4TTR4030A1000A 29.8 95' R410A 1 14.7 1 1.4 20 30 208/1 3/4" 5/16" 200 CU-3 TTK509E5UAO 9.05 95' R22 1 4.9 1 0.2 6.6 10 120/1 3/8" 1/4" 66 NOTES: 1. MODEL NUMBERS AND SELECTIONS ARE BASED ON TRANE 2. REFRIGERANT PIPING SIZED BASED ON USING LONG RADIUS ELBOWS EXCEPT FOR SUCTION LINE TRAP AT CONDENSING UNIT. 3. PROVIDE START KIT 11 MGE ARCHITECTS 150 Alhambra Circle, Suite 700 Coral Gables, Florida 33134 T.305.444.0413 F.305.441.6404 www.mgearchitects.com AA-F000121 CONSULTANTS 6767 glue Lagoon Dr., 11400 Miami, FL 33120 Phone: 305-266-6553 Fax: 305-266-6695 ENGINEERING FOR ARCHITECTURE WWW.tIC-CngIrICCfS.00fr1 © Copyright 2005 TLC Engineering for Architecture, Inc. EB #0000015 TLC NO:606504 DRAWN BY. JM CHECKED BY: LR APPROVED BY: RM 1007. CONSTRUCTION DOCUMENTS PROJECT NAME GARSH INVESTMENTS CORPORATE OFFICES South Miami, Florida JOB NUMBER: 2006.00C DATE: ,C'4/24/04 CAD FILE NO: ' ' ` " ' AGENCY NO: ' w ♦ • • • y REVISIONS/SUBMISSIONS::,, • . W •• • • •• DODO N ♦ •yoo ♦� __�. t+`• �. • ♦ U • i ♦ **to • �• W • W y rWw• i w u r • SEAL: � r v Q:=r.,� i h Raul S. Mastrapa,\ Pt. Florida Licelnse' #401 82 DRAWING TITLE: SCHEDULES - HVAC DRAWING NO: M-1 J i