PARTITION TYPE GENERAL NOTES!
I. GENERAL CONTRACTOR. SHALL BE SOLELY RESPONSIBLE FOR THE APPROPRIATE
CONSTRUCTION OF ALL PARTITION TYPES AND WITH THE COORDINATION OF ALL
MECHANICAL, ELECTRICAL, AND PLUMBING SYSTEMS
THE CONTRACTOR SHALL GIVE SPECIAL CONSIDERATION TO EXAMINATION OF
ALL CONDITIONS THAT MAY PREVENT THE CONSTRUCTION OF SUCH
RATED PARTITIONS DETAILS/PLANS. VARIATION OF TYPICAL RATED PARTITION
DETAILS SHALL BE ANTICIPATED AND SHALL BE EXPRESSLY INCLUDED
AS PART OF THE WORK WHENEVER REQUIRED, AT NO ADDITIONAL COST TO THE
OWNER. A/E SHALL PROVIDE VARIATIONS TO DETAILS OF PARTITIONS REQUIRED .
IGNORANCE ON THE PART OF THE CONTRACTOR SHALL IN NO WAY
RELIEVE HIM OF THIS OBLIGATION AND RESPONSIBILITY ASSUMED UNDER
THIS CONTRACT.
2. GENERAL CONTRACTOR. SHALL IDENTIFY ALL FIRE WALLS ABOVE THE CEILING
WITH RED PAINT TO READ ACCORDING TO THE WALL RATING AS SUCH- LETTERS MUST BE 1 1/2, FOR
"ONE HOUR WALLS AND 3' FOR TWO HOUR AND SMOKE WALLS AS FOLLOWS -
TWO HOUR FIRE/SMOKE WALL (PROTECT ALL PENETRATIONS) 7�— 3'
M
TWO HOUR FIRE WALL (PROTECT ALL PENETRATIONS) 3'
ONE HOUR FIRE/SMOKE WALL (PROTECT ALL PENETRATIONS) 4�:: 1 1/2' (TYPICAL)
ONE HOUR FIRE WALL (PROTECT ALL PENETRATIONS)
SMOKE TIGHT WALL (PROTECT ALL PENETRATIONS)
3. PROVIDE 2 X 4 PRESSURE TREATED FIRE -RETARDANT PAINTED WOOD BLOCKING (NAILER) AT ALL
LOCATIONS SCHEDULED TO RECEIVE WOOD BASES (SEE FINISH SCHEDULES)
4. ALL PARTITIONS SHALL BE 4' NOMINAL DIMENSION (UNLESS OTHERWISE NOTED ON PLANS).
5. INTERIOR WALLS, PERMANENT PARTITIONS (RATED OR NOT) AND TEMPORARY PARTITIONS SHOULD
SUPPORT A MINIMUM OF (5) POUNDS PER SQUARE FOOT APPLIED PERPENDICULAR
TO THE WALL.
S. PROVIDE BACKING SUPPORT AT ALL PARTITIONS WHERE EQUIPMENT OR CASEWORK IS INDICATED
TO BE MOUNTED.
7. SOFFIT SUPPORTS ON RATED PARTITIONS SHALL BE PERMITTED, ONLY IF THEY ARE ATTACHED DIRECTLY
TO METAL STUDS AND/OR STRUCTURAL BACKING. ATTACHMENT TO GYPSUM WALLBOARD SHALL NOT BE
PERMITTED.
CONTRACTOR SHALL BE REQUIRED TO REMOVE ALL SUPPORTS NOT IN ACCORDANCE WITH ABOVE AT
NO ADDITIONAL COST TO OWNER.
8. PROVIDE CONTINUOUS (UNINTERRUPTED BY FURRING) R-11 (MIN.) RIGID INSULATION BOARD AT ALL
EXTERIOR BLOCK/CONCRETE WALLS FACING AIR CONDITIONED SPACES. INSTALL FROM FINISH SLAB TO
UNDERSIDE OF STRUCTURAL DECK. GYPSUM WALLBOARD TO CONCEAL INSULATION TO UNDERSIDE OF
FINISHED STRUCTURAL DECK.
i-0. ALL DIMENSIONS SHOWN ON FLOOR PLANS ARE ROUGH TO ROUGH (STUD TO STUD OR MASONRY
TO MASONRY OR MASONRY TO STUD) TYPICAL U.O.N.
10. RATED PARTITIONS SHALL BE BUILT FIRST IN COMPLIANCE WITH THE U.L. ASSEMBLY INDICATED.
ALL OTHER PARTITIONS ABUTTING RATED PARTITION SHALL NOT BE CONSTRUCTED UNTIL AFTER THE
RATED PARTITION IS COMPLETE.
11, y CONTRACTOR SHALL SUPERVISE AND INSPECT CONSTRUCTION OF ALL WALLS TO VERIFY THAT CONSTRUCTION
IS PERFORMED IN ACCORDANCE TO SPECIFICATIONS AND U.L. ASSEMBLIES. ANY VARIATIONS SHALL BE
BROUGHT TO THE ARCHITECTS ATTENTION.
12. CEILING BACK-UP STUDS ARE NOT REQUIRED AT ANY PARTITION TYPE WHERE GYPSUM WALLBOARD
EXTENDS UP TO THE UNDERSIDE OF THE FINISHED STRUCTURAL DECK ON BOTH SIDES OF THE PARTITION.
13. INSTALL BASE OF GYPSUM WALLBOARD A MINIMUM OF 3/8' ABOVE FINISHED FLOOR CONCRETE SLABS.
14. ALL PIPE, CONDUIT AND DUCT PENETRATIONS THRU RATED PARTITIONS
SHALL BE DONE AT 90 DEGREES (BOTH SIDES).
15. ANY RECESSED ITEM OVER 4'x4' IN SIZE INSTALLED IN A RATED PARTITION SHALL BE ENCASED
IN A FIVE SIDED 5/8' TYPE 'X' GYPSUM WALLBOARD ENCLOSURE (SEE TYP. DETAIL)
'PARTITION SYMBOLS (PROVIDE THE FOLLOWING, AS INDICATED ON FLOOR PLANS)
v
INDICATES SOUND ATTENUATION, FULL HEIGHT WITHIN PARTITION,
SAPROVIDE MINIMUM 45 STC RATING
STOOL
SEALANT (BOTH SIDES)
DETAIL 1
I �I
EXISTING 1 HR. �� ----�
2 MR RATED PARTITION L_----- --
PARTITION
(NEW)
hMARLITE WALL SYSTEM (SEE INT. ELEV.)
42"
-AfF----
AFF
4,.��,—---
2 > AF
2 7Ffl,
5.01
5.01
3 0 ;`RECEPTION
R
.w FURNITURE N 100
' BY OTHERSI
r LOUNGE b`' 2 C 11
102 * COM. EXISTING
EXISTING �o 101 102A NOTE PARTITION
2 4
EXI
7'-2" 4" 3' 10 4"
FURNITURE
BY OTHERS
i SA —�i J BOX J BOX
3 30TE (FLOOR) (FLOOR)
I.-- — _. __...............-- ._... — . _ _ .................I
102
A- u A
ELEC./TEL.
/> ROOM
! i EXISTING 1 HR.
RATED PARTITION
v
OFFICE 1 `; __
103 LO3103
DETAIL 1 I FURNITURE 2
--�,,
BY OTHERS
-7�—
i
� - �\ % EXISTI
NG
RATED�I
3„30TE CLERICAL��— -�� �� I 3 PARTITION
5.01 FILES I I
j AREA Imo— .._ ,,,
F -- 3
i:. _ � 101
2
2F-41v8 8
i
ELECTRICAL 1
J OX PANEL
5.01
io
OFFICE 2
I,
104 REFERENCE LO KED
-v TABLE STORA
QCD
I 110
r II
STEELCASE I -WALL SYSTEM
i v I f
' 110A
n
A --
-
--�
4B
SA 1 v
3
B I 110A 1
4 PARTIT ON 42" HIGH SA o lo@ 3 L
A I 5'-2' 3, 8' m I
M 2 5.01 5 fD
�
�n 5.01 NOTE 1 I •�/� �+ I
A O I 1t1�V I I I
Z STEELCASE I -WALL SYSTEM i 10111A
.. ......................... ...-- _.
L-- --�I
.. .... .... .....___.._ .................
„z
� II
1oaA
II
NOTE
a A a II
r O 3,` p
20'-8'
I `\ 7
13'-6"
SA
15 -8
I 1
-
„RYRA
4
$E0grTARYSE
1II I1I
w
/ D
(i� �� (
�'NOTE
I I
—
3
OFFICE 4
3
EXISTING
1 HR.
SA
3 ,0i
04
OFFICE 5
RATED ._ I I
PARTITION
3
ILU
STEELCASE I -WALL SYSTEM-----
�'
TYPICAL PARTITION
BOTTOM OF ROOF/FLOOR
STRUCTURAL DECK
CEILING BACK-UP RUNNER
io
SCHEDULED
CEILING —
ONE LAYER 5/8' TYPE 'X'
GYPSUM WALLBOARD EACH SIDE OF
METAL STUDS AT 16' O.C. (TYP. U.O.N.)
ACTUAL DIM. 4 7/8'
FOR 3 5/8' STUD
ACTUAL DIM. 7 1/4' FOR i' STUD
SOUND ATTENUATION BLANKET
TO UNDERSIDE OF STRUCTURE
(WHERE INDICATED ON PLANS)
DOTTED LINES INDICATE 5/8' GYPSUM
WALLBOARD EXTENDING TO
UNDERSIDE OF STRUCTURE FOR
SOUND ATTENUATION BLANKET (BOTH
SIDES - TYPICAL UNLESS OTHERWISE
NOTED)
SCHEDULED
CEILING
FINISH SLAB I� SEALANT (BOTH SIDES)
SECTION
(TYPICAL NONRATED PARTITION FOR ALL PARTITIONS WHERE SYMBOL
NOT USED ON PLANS TO IDENTIFY PARTITION TYPE)
33 WITH SOUND ATTENUATION
SA
EXI•
HEA
STE
BY
BY
SECTION A A
DIAGONAL BRACING SPACED
EVERY 4'-0'
SUSPENDED CEILING
:C
SECTION B B
TWO-HOUR WALL CONSTRUCTION
Al o �' � BOTTOM OF ROOF/FLOOR DECK
— — — — — — TILE CARPE
106A
OFFICE 3
7106
HI
1 II
EXISTING
--
I I IIII r; �
IIII I _ I
COORDINATE
EXACT LOCATION
WITH OWNER AN[
2LI II F�__ ARCHITEC
I III TV
NOTES:
1. LAMINATE DRYWALL TO EXISTING
CONCRETE COLUMN.
2. CONSTRUCT DRYWALL CHASE
AROUND EXISTING R.W.L. W/
DURAROCK". CONSTRUCT AS TIGHT
AS POSSIBLE TO EXISTING PIPES
3. COORDINATE EXACT LOCATION OF
PARTITION WITH VERTICAL MULLION
IN I -WALL SYSTEM.
4. COORDINATE CORE DRILLING FOR
J-BOXES WITH STRUCTURE TO
ELIMINATE CONFLICT WITH EXISTING
SLAB RE-INFORCEMENT.
...................................... . ............. .. .............................. ......................... .......... . ........ . ....... ......... ..
...................... .... ..... ........ ............................................... ..................... . .. . ..................... .. .... ..... ... .... ...................... ...
U.L. DESIGN No. U411
SEALANT (BOTH SIDES)
CEILING BACK-UP STUD
SCHEDULED
CEILING
TWO LAYERS 5/8' TYPE 'X' GYPSUM
WALLBOARD EACH SIDE OF
METAL STUDS
3 5/8' , 6' OR 8" METAL STUDS
AT 16' O.C.
PROVIDE METAL STUDS
AT WALLBOARD
HORIZONTAL JOINTS
ACTUAL DIM. 6 1/8' FOR 3 5/8' STUD
ACTUAL DIM. 8 1/2' FOR 6' STUD
ACTUAL DIM. FOR 10 1/2' FOR 8' STUD --
i
i
SOUND ATTENUATION BLANKET
TO UNDERSIDE OF STRUCTURE
(WHERE INDICATED ON PLANS)
SEALANT (BOTH SIDES)
FINISH SLAB
/\ SECTION
2� TYPICAL TWO-HOUR FIRE -RATED PARTITION
PARTIAL FIFTH FLOOR PLAN
1/4' -1'-0"
TWO HOUR CONSTRUCTION NOTE
BASE LAYER 5/11' TYPE X GYPSUM
_
WALLBOARD APPLIED (VERTICALLY)
PARALLEL TO EACH SIDE OF
3 5/8' METAL STUDS 1e' O.C.
WITH 1' TYPE S DRYWALL SCREWS
8' O.C. ALONG VERTICAL EDGES
AND 12' O.C. IN THE FIELD
u
FACE LAYER 5/8' PLAIN OR
j
PRE DECORATED TYPE 'X' GYPSUM
WALLBOARD APPLIED PARALLEL TO
STUDS OVER BASE LAYERS WITH
5
1-5/8' TYPE S STEEL SCREWS
SPACED 18' O.C. IN THE FIELD AND
e
ALONG VERTICAL EDGES AND 12' O.C.
ON FLOOR AND CEILING RUNNERS.
STAGGER JOINTS 16' O.C. EACH
LAYER AND SIDE (NLB).
NOTE- CONTRACTOR SHALL SUPERVISE
AND INSPECT CONSTRUCTION OF ALL WALLS
TO VERIFY THAT CONSTRUCTION IS
PERFORMED IN ACCORDANCE TO
SPECIFICATIONS AND U.L. ASSEMBLY. ANY VARIATIONS
SHALL BE BROUGHT TO THE
ARCHITECTS ATTENTION.
tTr 0VE BY
COU01 FIRE I)Err. VI1 013T
&71�._BLID6. PERMIT
WATRR MAIN EXTENSION
DATE�W,r
MGE ARCH I TECTS
150 Alhambra Circle, Suite 700
Coral Gables, Florida 33134
T.305.444,0413 F.305.441.6404
www.mgearchitects.com
AA-F000121
PROJECT NAME
GARSH
INVESTMENTS
CORPORATE
OFFICES
South Miami, Florida
JOB NUMBER: 2006.01C
DATE: 04/24/0(
CAD FILE NO:
AGENCY NO:
REVISIONS/SUBMISSIONS:
Q OWNER REQUESTED CHANGES
tLDG. DEBT. COMMENTS AND COORDITATION
08/1'8/04
0
A
0
n
SEAL:
* s,
r. 4.
a PEDRO GOICO IA, 1,ir�R�b00j77>t
a JOSE L. ESTEVVE AIA AN-20Q08463 ' y'
❑ ROLANDO CONEBA;`'AIA AR-66RT48, '
ROBERTO A. SMITH, AID' AR-0010406
DRAWING TITLE:
FIFTH FLOOR
FLOOR PLAN
DRAWING NO: A1.01
J