06-697-002r-
w
y
I
SECOND - FIFTH FLOOR (TYPICAL)
PERMIT AREA ONLY
E.O.L.
vw_
NAC #1 (1.542 amp, 3.0 max)
Fire Alarm System Riser
N.T.S.
STYLE "Y"
n
75cd 75cd 75cd 75cd 75cd 75cd 75cd 75cd 75cd
N N N N N ,N N N N
L L L H L H L H L
H138 H137 H136 H135 H134 H133 H132 H131 H130
NEW SK"5495" AUX. POWER SUPPLY
LOCATED IN NEW RESTAURANT.
P5 A
D
FtC
SENN
_ C5
120V DEDICATED CIRCUIT TO ELECT J C
PANEL WITH 2OAmp CIRCUIT BREAKER.
B
E.O.L. E E V E E
H L H L
EXISTING BPS-10 BOOSTER - P2
POWER SUPPLY LOCATED IN D :V
ELECT. ROOM. B.P.S #1
C
120V DEDICATED CIRCUIT TO ELECT
E
PANEL WITH 2OAmp CIRCUIT BREAKER.
FIRST FLOOR
WIRE LEGEND
SYMBOL WIRE TYPE AND DESCRIPTION
A 18-2 FPLP FOR SIGNALING LINE CIRCUIT
B 14-2 FPLP WIRE FOR NOTIFICATION APPLIANCE CIRCUITS
C 12 AWG THHN WIRE FOR APS & FACP POWER
D 12 AWG THHN WIRE FOR APS & FACP_ GROUND
EXISTING EST-2 FIRE ALARM
CONTROL PANEL LOCATED IN
LOBBY.
STYLE "4"
SECOND - FIFTH FLOOR (TYPICAL)
PERMIT AREA Ol`NLY
D10 D111
LL
0 E P N O N
D5
SD
E E N
E E E E
81 120V BELL WITH SIGN
TS FS BF R
E E E E:
A
MAGNETIC LOCK
TO FACP \pR ATTACHED TO FACP
E
A
D
F.A.C.P. TELCO LINES FOR REMOTE TO FACP-- E
P1 E STATION NOTIFICATION R
- E
C
120V DEDICATED CIRCUIT TO ELECT
OC PANEL WITH 2OAmp CIRCUIT BREAKER.
FIRST FLOOR
Fire Alarm Control Panel EST Model:
STANDBY
DESCRIPTION CURRENT
PER UNIT
(Amp)
EST2
CITY
TOTAL
STANDBY
CURRENT
(Amp)
ALARM
CURRENT
PER UNIT
(Amp)
�•
TOTAL ALARM
CITY CURRENT
(Amp)
Main Board
0.147
X
1
=
0,147
0.216
X
1
=
0.2160
Addressable Photoelectric Smoke Detector (SIGA-PS)
0.000045
X
27
=
0.001215
0,000046
X
27
=
0.0012
Addressable Heat Detector (SIGA-HRS)
0.000045
X
4
=
0,00018
0.000045
X
4
=
0.0002
Addressable Duct Detector (SIGA-PS)
0,000045
X
6
=
0.00027
0.000045
X
6
=
0.0003
Addressable Pulh Station
0.000260
X
15
=
0.00375
0,0004
X
15
=
0.0060
Elevator Warning Light
0,000000
X
2
=
0.0000
0.0200
X
2
=
0.0400
Addressable Monitor Module (SIGA-CT1)
0.000250
X
9
=
0.00225
0.0004
X
9
=
0,0036
Addressable Dual Monitor Module (SIGA-WTM)
0,000396
X
5
=
0.00198
0.00068
X
5
=
0.0034
Addressable Control Module (SIGA-CC1)
0.000223
X
8
-IX0.0008
0.001784
0.00010
8
Addressable Relay SIGA-CR
0.000100
X
1 7
=
0.0007
0.000100
X
7
=
0.0007
0.159
0.2722
2 Hour Fire Rated Through
Penetration Firestop for
Multiple Metal Pipe through
3733 Green Rd.
Concrete floors or walls
Beachwood, OH, 44122
using FYRE-SHIELD.
e�
Drawing not to stale
CAJ1047
F-rating = 2 Hr.
(326)
T-rating - 0 Hr.
1D Floor or Wall assembly = 4 " thick concrete, Max. area of
opening is 288 sq. in.
® -Copper Pipe: 4" dia. (or smaller) regular (or heavier) copper.
-Steel Pipe: 8" dia. (or smaller) Sch.40 (or heavier) steel.
-Conduit: 4" dia. (or smaller) EMT or 6" dig. (or smaller)
steel conduit.
-Copper Tubing: 4" dia.(or smaller) Type L(or heavier) copper.
-Iron Pipe: 8' dia.(or smaller) cast or ductile iron.
-Max. number of pipes with opening is three (3).
(3 A) Forming Material - (Not shown) - Nom. 1" thick poly-
urethane backer rod friction fitted
into opening.
B) Nom. 3" FYRE-SHIELD thickness installed within opening.
NOTE: For wall apply FYRE-SHIELD to both surfaces of wail.
Project: ibs p.oduct• uad b ih• abo» 0"wo, ho. 1bn dto s dawE•d awmbly me
1 bwa tatwd G a dance with tb• fdfowin9 pprroo�d�eb have ban G.GO and we
• AS711 E51d (U1.747s) St=M tat Method bo.}/ an bop D m� mactpotN
Location: for mrou9 k.411 .11 FFatoppin4 D�rramana wn ,x wild
not be tlablo ra1 any dgmogM d4at
Instorer. mtaWo4�adupi-.e trtan�oo
Dots: 5/1/95 -7wing: TR-1a47 d,ae aniy w rwpan.bi fw ry(oa(ne
Signature [Approved b , C. TutteO moE,rid rouse Ee a ar«a.
SOLID, AWG
14:
_
20.4
Ohms er 1000
End Of Battery Life (Volts)
Max Ca acity (Amp)
N
Device #
Device Description
Ala
Curl
A
H130
Strobe 75cd
0.165
H131
Horn /Strobe 75cd
0.184
C
H 132
Strobe 75cd
0.165
#
H133
Horn lStrobe 75cd
0.184
H134
Strobe 75cd
0.165
H135
Horn /Strobe 75cd
0.184
H136
Strobe 75cd
0.165
H 137
Strobe 75cd
0' 165
H138
Strobe 75cd
0.165
1.542
AUX. POWER SUPPLY
"SK 5495"
3,
}
Distance
Applied
Voltage Drop
Voltage
�.
6
Feet
20.343 Volts
0.057
Volts
�.
27
Feet
20,115 Volts
0,228
Volts
>.
14
Feet
20.012 Volts
0.103
Volts
>.
38
Feet
19.773 Volts
0.240
Volts
>.
22
Feet
19,659 Volts
0.114
Volts
>.
1
Feet
19.654 Volts
0.004
Volts
1.L10
Feet
19,624 Volts
0.030
Volts
>.
22
Feet
19.579 Volts
0.045
Volts
r.
1
Feet
0.001
Volts
STROBE OR
HORN/STROBE
80' A.F.F. OR
6' BELOW CEILING
(WHICHEVER IS LOWER)
PULL STATION
48' A.F.F.
ADA HEIGHT REQUIREMENTS
NO SCALE
ALLOWABLE
AMPACITY FOR
COPPER
y
r
WIRES
SIZE
ALLOWABLE
AMPACITY
18
6
16
8
14
15
12
20
10
30
FROM NEC -TABLE 310-16 & 402-5
IFME ALARM SYSTEM TO 13E-
INSTALLED IN ACCORDANCE, WITH
NFPA 72 70;101-
APPRQVED
N AINII-DADE COUNTY FIRE DEPARTNT
BLDG, PERMIT FIRE ALARM
FIRE SUPPRESSION .WATE MAIN EXT.
bAT E: Em
REVISION:
FIRE DEP TMEN 03/22/06
fi 7
rl-
LO
-<�
n
N
,It
E-4
I
Q'"'
C�YJ
P-+-1
®
Q
C
Q
E4
®
O
E: 4
1Z
w
C)
E__4_
•
4`
"'.off°,i'.�..;
n`ii� `'•• ,^.
PROJECT NO.:
DRAWING NO.:
SCALE:
N.
DATE:.
02/1,/�6..
DOAYr"
YV�1;�8
. „
ISSUED:
FOR PERMIT